Hardware architecture

Table 2 - Inputs and output summary list

 

TRACER CH532 Medium

TRACER CH532 Large

 

Single circuit units

Dual circuit units

AI: Leaving water temperature sensor

B3: NTC

B3: NTC

AI: Entering water temperature sensor

B4: NTC

B4: NTC

AI: Ambient temperature sensor

B5: NTC

B5: NTC l

AI: Suction pressure circuit 1 - LP1 transducer

B1: 4..20mA

B1: 4..20mA

AI: Suction pressure circuit 2 - LP2 transducer

 

B6: 4..20mA

AI: Discharge pressure circuit 1 - HP1 transducer

B2: 4..20mA

B2: 4..20mA

AI: Discharge pressure circuit 2 - HP2 transducer

 

B7: 4..20mA

AI: External water setpoint reset (option)

B8: 0..10V-0..20mA

B8: 0..10V-0..20mA

AI: Unused

B6, B7

B9, B10

DI: Compressor C circuit 1 fault

ID1: 24Vac

ID1: 24Vac

DI: Compressor C circuit 2 fault

 

ID17: 24Vac

DI: Compressor A circuit 1 fault

ID3: 24Vac

ID3: 24Vac

DI: Compressor B circuit 1 fault

ID4: 24Vac

ID4: 24Vac

DI: Compressor A circuit 2 fault

 

ID11: 24Vac

DI: Compressor B circuit 2 fault

 

ID12: 24Vac

DI: High pressure Cut-out circuit 1 - HP1 switch

ID14H: 230Vac

ID14H: 230Vac

DI: High pressure Cut-out circuit 2 - HP2 switch

 

ID15H: 230Vac

DI: Auxiliary set point On/Off

ID8: 24Vac

ID8: 24Vac

DI: Fans circuit 1 fault

ID5: 24Vac

ID5: 24Vac

DI: Fans circuit 2 fault

 

ID18: 24Vac

DI: Circuit 1 On/Off (or Unit On/Off CH 532 medium)

ID13H: 230Vac

ID13H: 230Vac

DI: Circuit 2 On/Off

 

ID16H: 230Vac

DI: Water flow control input

ID2: 24Vac

ID2: 24Vac

DI: Water pump 1 fault

ID9: 24Vac

ID9: 24Vac

DI: Water pump 2 fault

ID10: 24Vac

ID10: 24Vac

DI: Faults external reset

ID6: 24Vac

ID6: 24Vac

DI: Cooling/Heating mode switch

ID7: 24Vac

ID7: 24Vac

DI: Unused

ID11, ID12

-

DO: Compressor A circuit 1 output

NO7: NO-230Vac

NO7: NO-230Vac

DO: Compressors B and C circuit 1 output

NO8: NO-230Vac

NO8: NO-230Vac

DO: Compressor A circuit 2 output

 

NO13: NO-230Vac

DO: Compressors B and C circuit 2 output

 

NO14: NO-230Vac

DO: Fan 1 output Wye (Y) contactor - circuit 1

NO3: NO-230Vac

NO3: NO-230Vac

DO: Fan 1 output Delta (D) contactor - circuit 1

NO4: NO-230Vac

NO4: NO-230Vac

DO: Fan 2 output circuit 1

NO5: NO-230Vac

NO5: NO-230Vac

DO: Fan 3 output circuit 1

NO6: NO-230Vac

NO6: NO-230Vac

DO: Fan 1 output Wye (Y) contactor - circuit 2

 

NO15: NO-230Vac

DO: Fan 1 output Delta (D) contactor - circuit 2

 

NO16: NO-230Vac

DO: Fan 2 output circuit 2

 

NO17: NO-230Vac

DO: Fan 3 output circuit 2

 

NO18: NO-230Vac

DO: Water pump 1

NO1: NO-230Vac

NO1: NO-230Vac

DO: Water pump 2

NO2: NO-230Vac

NO2: NO-230Vac

DO: Antifreeze heater

NC12: NO-230Vac

NC12: NO-230Vac

DO: Circuit 1 fault

NO9: NO-230Vac

NO9: NO-230Vac

DO: Circuit 2 fault

 

NO11: NO-230Vac

DO: Unit status or additional heating demand

NO10: NO-230Vac

NO10: NO-230Vac

DO: Unused

NO11, NO13

-

AO: Speed inverter - fan circuit 1 - HP1 output

Y1: 0..10V

Y1: 0..10V

AO: Speed inverter - fan circuit 2 - HP2 output

 

Y2: 0..10V

AO: 4-way valve circuit 1

Y3: 0..10V + CONVONOFF

Y3: 0..10V + CONVONOFF

AO: Unused

Y4

Y4

AO: 4-way valve circuit 2

 

Y5: 0..10V + CONVONOFF

AO: Unused

 

Y6

AO: Unused

Y2

Y2

Legend:

 

 

AI: Analog Input

 

 

DI: Digital Input

 

 

AO: Analog Output

 

 

DO: Digital Output

 

 

CONVONOFF: ON/OFF converter

 

 

CG-SVU01B-E4

7

Page 7
Image 7
American Standard TRACER CH532 Inputs and output summary list, Tracer CH532 Medium, NO11, NO13, Y3 0..10V + Convonoff