American Standard TRACER CH532 Hardware architecture, use an auxiliary setpoint, CG-SVU01B-E4

Models: TRACER CH532

1 32
Download 32 pages 38.41 Kb
Page 8
Image 8
-use an auxiliary setpoint

Hardware architecture

TRACER CH532 offers customer the possibility to use inputs or outputs in order to:

-use an external water setpoint reset using an analog input (refer to figure 3)

-use an auxiliary setpoint

-connect a remote on/off of the unit or a circuit

-reset faults

-connect a remote Cooling/Heating switch

-return a circuit fault

Note: External water setpoint Based on a external signal input, it will be possible to offset the active setpoint from 0°C to 20°C. This function can be used in conjunction with the automatic setpoint reset function.

Figure 3

setpoint

 

5

4

1

 

 

 

Water

 

 

 

 

 

 

2

Ambient

3

 

temperature

1.Leaving water temperature setpoint

2.Minimum value

3.Maximum value

4.Reset = 20°C

5.Active setpoint

Table 3: Customer Inputs and output summary list

 

 

TRACER CH532 Medium

TRACER CH532 Large

 

 

Single circuit units

Dual circuit units

AI

External water setpoint reset (option)

B8: 0..10V-0..20mA

DI

Auxiliary setpoint On/Off

ID8: 24Vac

DI

Circuit 1 On/Off (or Unit On/Off

 

 

 

for single circuit units)

ID13H: 230Vac

DI

Circuit 2 On/Off

-

ID16H: 230Vac

DI

Faults external reset

ID6: 24Vac

DI

Cooling/Heating mode switch

ID7: 24Vac

DO

Circuit 1 fault

NO9: NO-230Vac

DO

Circuit 2 fault

-

NO11: NO-230Vac

DO

Unit status or additional

 

 

 

heating demand

NO10: NO-230Vac

Legend:

AI: Analog Input

DI: Digital Input

DO: Digital Output

8

CG-SVU01B-E4

Page 8
Image 8
American Standard TRACER CH532 Hardware architecture, use an auxiliary setpoint, Customer Inputs and output summary list