Cable characteristics

LonTalk® option

Cable characteristics

Level 4 cable may be used with TP/FT-10 channels. The level 4 cable specification used by Echelon and as originally defined by the National Electrical Manufacturers Association (NEMA) differs from the Category 4 specification proposed by the Electronic Industries Association / Telecommunication Industries Association (EIA / TIA).

The following specifications can be used by cable suppliers to identify a compliant Level 4 cable.

Specifications apply to shield or unshielded 22AWG (0.65mm2) cable

D-C resistance (ohms/1000 feet at 20°C) maximum for a

 

single copper conductor regardless of whether it is solid

18.0

or stranded and is or is not metal coated

D-C resistance unbalance (percent) maximum

5

Mutual capacitance of a pair (pF/foot) maximum

17

Pair to ground capacitance unbalance (pF/1000 feet) maximum

1000

Characteristic impedance (ohms)

 

772 kHz

102+/- 15%

1.0 MHz

100 +/- 15%

4.0 MHz

100 +/- 15%

8.0 MHz

100 +/- 15%

10.0 MHz

100 +/- 15%

16.0 MHz

100 +/- 15%

20.0 MHz

100 +/- 15%

Attenuation (dB/1000 feet at 20°C) maximum

 

772 kHz

4.5

1.0 MHz

5.5

4.0 MHz

11

8.0 MHz

15

10.0 MHz

17

16.0 MHz

22

20.0 MHz

24

Worst pair to pair near end crosstalk (dB) minimum. Values are shown for information only. The minimum NEXT coupling loss for any pair combination at room temperature is to be greater than the value determined using the formula NEXT (F MHz)>NEXT (0.772)-15log10(F MHz / 0.772) for all frequencies in the range of 0.772 MHz for a length of 1000 feet.

772 kHz

58

1.0 MHz

56

4.0 MHz

47

8.0 MHz

42

10.0 MHz

41

16.0 MHz

38

20.0 MHz

36

For the TP/FT-10 channel operating in a bus topology , the maximum bus length of level 4 22AWG (0.65 mm2) cabling is 1400 meters with a maximum stub length of 3 meters.

It is recommended to use shielded cable if high amplitude modulation noise exist or transient protection is required.

28

CG-SV01B-E4

Page 28
Image 28
American Standard TRACER CH532 manual LonTalk option, Cable characteristics, Characteristic impedance ohms