American Standard TRACER CH532 Unit configuration menu “Configuration”, Single pump operation

Models: TRACER CH532

1 32
Download 32 pages 38.41 Kb
Page 17
Image 17
Unit configuration menu: “Configuration”

Unit configuration menu: “Configuration”

From the menu screen, select

Configuration” then press Figure 5 - Single pump operation . Following screen will appear:

User password

0000

Enter default password:”0000” (factory-set)

Press Figure 6 - Dual pump operation and cursor will move to first field of password. Pressing Figure 7 - Single pump protection

or Manual background will increment the value from 0 to 9999. Keeping pressure on Manual background

or Manual background will move the numbers fast.

Press Manual background to confirm password.

Pressing Manual background or Manual background will allow navigation from screen 1 to 11 as shown hereafter:

1. Unit definition

To access one of the 4 parameters

displayed, press

 

and change

value using

or

. Confirm the

value by pressing

 

Unit type:

 

Chiller

Refrg

 

R407C

Figure 5 - Single pump operation

Note: figures 5 to 8, Unit Off means that the unit is stopped by keyboard or by an external contact

On

On

Pump

Off

t

Figure 6 - Dual pump operation

On

Unit

Off

On

Pump 1

Off

On

Pump 2

Off

t

Fans/ckt

3

Water pump

Single

Unit Type: Unit type Chiller: Cooling only

Heat pump: Reversible chiller

Refrg: Refrigerant R407C, R134a, R410A or R22

Fans/ckt: Number of fans per circuit: 1, 2, or 3

Note: Setting number of fans at 0, will stop all the fans, but will allow the compressors to run before being stopped by HP switch.

Water Pump: Water pump type Single: Single pump control Dual: Dual pump control

Note: Pump operation

The water pumps can be single or dual. A timer is used to delay the pump shut down in normal operating conditions. The timer is reset at each unit start.

When twin pumps are used, a pump switch will occur at each start and also in case of fault on the pump in operation.

Figure 7 - Single pump protection

Pump protection- input

Pump protection- output

Unit stopped

(manual reset)

CG-SV01B-E4

17