Alarms

Table 4 - Status, warnings and alarm messages

No

Message

Reset Type

Unit status

Description

1

No Alarm

-

Unit On

See unit status on Main display

2

Ext. Ckt1 Stop

-

Circuit 1 Off

Circuit 1 Off by Digital Input (Dual circuit units)

3

Ext. Ckt2 Stop

-

Circuit 2 Off

Circuit 2 Off by Digital Input (Dual circuit units)

4

User Ckt1 Stop

-

Circuit 1 Off

Circuit 1 Disable by Settings (via keyboard)

5

User Ckt2 Stop

-

Circuit 2 Off

Circuit 2 Disable by Settings (via keyboard)

6

Remote Ckt1 Stop

-

Circuit 1 Off

Circuit 1 Disable by Supervision

7

Remote Ckt2 Stop

-

Circuit 2 Off

Circuit 2 Disable by Supervision

8

Clock Unit Stop

-

Unit Off

Unit Off by Program (Hourly, Weekly)

9

Operator Stop

-

Unit Off

Unit Off by Operator (via keyboard)

10

Ckt1 Defrost

-

Unit On

Circuit 1 under defrosting

11

Ckt2 Defrost

-

Unit On

Circuit 2 under defrosting

12

Warning Comp.1 Maintenance

Manual

Unit On

Compressor running hours above the threshold defined in unit

13

Warning Comp.2 Maintenance

Manual

Unit On

14

Warning Comp.3 Maintenance

Manual

Unit On

configuration.Each compressor start is equal to 3 running hours.

15

Warning Comp.4 Maintenance

Manual

Unit On

 

16

Alarm Air Sensor

Auto

Unit Off

Defective Air sensor -

17

Alarm Ckt 1 Fault

Manual

Circuit 1 Off

Simultaneous manual reset faults CMP A1 and (B1 or C1)

18

Alarm Ckt 2 Fault

Manual

Circuit 2 Off

Simultaneous manual reset faults CMP A2 and (B2 or C2)

19

Alarm Ckt1 HP Limit

Auto

Unit On

Compressor B1C1 Off for high HP ckt1

20

Alarm Ckt1 Limiting

Auto

Unit On

Compressor B1C1 Off for Hot water or low LP ckt1

21

Alarm Ckt2 HP Limit

Auto

Unit On

Compressor B2C2 Off for high HP ckt2

22

Alarm Ckt2 Limiting

Auto

Unit On

Compressor B2C2 Off for Hot water or low LP ckt2

23

Alarm Comp. A1 Fault

Auto/Manual

CMP A1 Off

Manu if CMP A1 failure > 35 min or 6 failures within

 

 

 

 

3 hours 30 min

24

Alarm Comp. B1 Fault

Auto/Manual

CMP B1 Off

Manu if CMP B1 failure > 35 min or 6 failures within

 

 

 

 

3 hours 30 min

25

Alarm Comp. C1 Fault

Auto/Manual

CMP C1 Off

Manu if CMP C1 failure > 35 min or 6 failures within

 

 

 

 

3 hours 30 min

26

Alarm Comp. A2 Fault

Auto/Manual

CMP A2 Off

Manu if CMP A2 failure > 35 min or 6 failures within

 

 

 

 

3 hours 30 min

27

Alarm Comp. B2 Fault

Auto/Manual

CMP B2 Off

Manu if CMP B2 failure > 35 min or 6 failures within

 

 

 

 

3 hours 30 min

28

Alarm Comp. C2 Fault

Auto/Manual

CMP C2 Off

Manu if CMP C2 failure > 35 min or 6 failures within

 

 

 

 

3 hours 30 min

29

Alarm Ext. Setpoint Signal

Auto

Unit Off

Defective device or bad device configuration

30

Alarm Fan Protection 1

Auto

Unit On

Defective fan on the circuit 1

31

Alarm Fan Protection 2

Auto

Unit On

Defective fan on the circuit 2

32

Alarm HP Ckt1 Fault

Manual

Circuit 1 Off

High Pressure Cut-Out circuit 1

33

Alarm HP Ckt2 Fault

Manual

Circuit 2 Off

High Pressure Cut-Out circuit 2

34

Alarm HP Sensor Ckt1

Auto

Circuit 1 Off

Defective pressure sensor HP1

35

Alarm HP Sensor Ckt2

Auto

Circuit 2 Off

Defective pressure sensor HP2

36

Alarm Low Ambient

Auto

Unit Off

Ambient temperature too low for unit operation

37

Alarm Low Water Temp

Manual

Unit Off

LWT < antifreeze or INT (antifreeze-EWT)<=10°Cxsecond

38

Alarm LP Ckt1 Fault

Auto/Manual

Circuit 1 Off

Suction pressure too low on circuit 1

39

Alarm LP Ckt2 Fault

Auto/Manual

Circuit 2 Off

Suction pressure too low on circuit 2

40

Alarm LP Sensor Ckt1

Auto

Circuit 1 Off

Defective pressure sensor LP1

41

Alarm LP Sensor Ckt2

Auto

Circuit 2 Off

Defective pressure sensor LP2

42

Alarm Unit Fault

Manual

Unit Off

All the compressors are defectives

43

Alarm Water Flow (**)

Auto

Unit Off

No water flow. Reset by unit Off/On when pump Off

44

Alarm Water In Sensor

Auto

Unit On

Defective Return water sensor

45

Alarm Water Out Sensor

Auto

Unit Off

Defective Leaving water sensor

46

Alarm Water Pump1

Manual

Unit On

Defective water pump 1

47

Alarm Water Pump2

Manual

Unit On

Defective water pump 2

(**)When the unit is shut down after a waterflow alarm for more than 1 minute, it is necessary to switch the unit Off and On again to reset the fault. The fault will automatically reset if the water pump is still running.

CG-SV01B-E4

23

Page 23
Image 23
American Standard TRACER CH532 manual Status, warnings and alarm messages, Message, Unit status Description