Customer settings menu: “Settings”

From the menu screen, select

Settings” then press . Following screen will appear:

User password

0000

Enter password:”0000” (factory-set)

Press and cursor will move to first field of password. Pressing

or will change the value from 0

to 9999. Keeping pressure on or

will move the numbers fast.

Press to confirm password.

Pressing will allow navigation from screen 1 to 5 as shown hereafter:

1. Setpoints

Cooling Stp

07.0°C

Heating Stp

45.0°C

Aux Wat Stp

10.0°C

Aux Wat

Disable

 

 

To access one of the parameters

displayed, press

 

and change

value using

or

. Confirm the

value by pressing

 

Cooling StP

 

07.0°C

Heating StP

 

45.0°C

Aux Wat StP

 

10.0°C

Aux Wat

 

Disable

Cooling Stp = Cold water setpoint (-12 to 20°C - factory setting: 7°C) Heating Stp = Hot water setpoint

(20 to 60°C - factory setting: 45°C) Aux Wat Stp = Auxiliary setpoint (-12 to 60°C - factory setting: 10°C) Aux Wat = Auxiliary setpoint from external source:

Enable = Auxiliary setpoint validated Disable = Auxiliary setpoint non- validated

. Automatic cooling and heating mode setpoints reset

TRACER CH532 offers the possibility to offset cold and/or hot water setpoints according to ambient air temperature.

The automatic setpoint reset program will allow you to change the water temperature setpoint (cooling and heating mode) with the ambient temperature. This function can be used in conjunction with the external setpoint reset function.

Figure 4

5

4

1

 

Ambient

2 temperature 3

1.Leaving water temperature setpoint

2.Starting point

3.Ending point

4.Reset delta

5.Active set point

Below the reset starting point, the water temperature setpoint will be the normal setting. Between the starting and ending point the setpoint will vary proportionally with the ambient temperature. After the ending point, the setpoint will stay at its maximum or minimum value.

2.1Cooling mode setpoint reset To access one of the parameters

displayed, press

 

and change

value using

or

. Confirm the

value by pressing

 

Cold water reset

N

Start Point

 

20.0°C

End Point

 

30.0°C

Reset Delta

 

10.0°C

Cold Water Reset: Ambient temperature based cold water setpoint offset

Y = Enabled

N = Disabled (factory setting) Start Point: Starting point (-15 to 50°C - factory setting: 20°C)

End Point: Ending point (-15 to 60°C

- factory setting: 30°C)

Reset Delta: Reset amplitude (-15 to

15°C - factory setting: 10°C)

3.Heating mode setpoint reset (Reversible chillers only)

To access one of the parameters

displayed, press

 

and change

value using

or

. Confirm the

value by pressing

 

Hot water reset

N

Start Point

 

20.0°C

End Point

 

30.0°C

Reset Delta

 

10.0°C

Hot Water Reset: Ambient temperature based hot water setpoint offset

Y = Enabled

N = Disabled (Factory setting) Start Point: Starting point

(-15 to 50°C - factory setting: 20°C)

End Point: Ending point

(-15 to 60°C - factory setting: 30°C)

Reset Delta: Reset amplitude

(-15 to 15°C - factory setting: 10°C)

12

CG-SVU01B-E4

Page 12
Image 12
American Standard TRACER CH532 manual Customer settings menu Settings