American Standard TRACER CH532 manual HVACHEAT=1, HVACCOOL=3

Models: TRACER CH532

1 32
Download 32 pages 38.41 Kb
Page 27
Image 27

LonTalk® option

Nv1

0=off

 

 

 

1=on

 

 

nv2 range -12.2°C 48.8°C

 

nv3

0=chiller off

 

 

 

1=chiller on

 

 

nv4 range -40°C 93°C

 

nv7

1=heat mode

 

 

 

3=cooling mode

 

nv8

range 10°C 93°C

 

nv11 range -40°C 118°C

 

nv12 range -40°C 118°C

 

nv13 range -40°C 118°C

 

nv15

manual reset alarm

 

 

auto reset alarm

 

 

informational warning

 

 

circuit 1 fans fault

 

 

circuit 2 fans fault

 

 

compressor A1 fault

 

 

compressor B1 fault

 

 

compressor C1 fault

 

 

compressor A2 fault

 

 

compressor B2 fault

 

 

compressor C2 fault

 

 

pump 1 fault

 

 

 

pump 2 fault

 

 

nv16 chlr_off=0, chlr_run=2

 

 

HVAC_HEAT=1, HVAC_COOL=3

 

 

Chiller state

0=No alarm, 1=In alarm

 

 

Run _enable

0=Chiller not allowed to start,

1=Chiller can start

 

Local 0=Values can be changed remotely,

1=Values cannot be changed remotely

 

Limited (Not used)

 

 

CHW_flow 0=No water flow, 1=Water flow detected

 

CONDW_flow (Not used)

 

 

All other bits unused

 

Configuration properties

 

nc73

ChillerEnable (m)

 

nc52

inSendTime (m)

 

nc4

MaxSendTime (m)

 

nc7

CoolSetpt (m)

 

nc74

Mode (o)

 

 

nc78

HeatSetpt (o)

 

 

nc48

Heartbeat (o)

 

 

(m)= mandatory

(o)= optional

CG-SV01B-E4

27

Page 27
Image 27
American Standard TRACER CH532 manual HVACHEAT=1, HVACCOOL=3