7-4. Precautions during Brazing
●Replace air inside the tube with nitrogen gas to prevent copper oxide film from forming during the brazing process.
●Do not allow the tubing to get too hot during the brazing process.
The nitrogen gas inside the tubing may overheat, causing refrigerant system valves to become damaged. Therefore allow the tubing to cool be- tween brazings.
7-5. Connecting Tubing between Indoor and Outdoor Units
(1)Tightly connect the indoor side refrigerant tubing with the outdoor side tubing. (Fig.
(2)To fasten the flare nuts, apply specified torque as:
Table
Tube Dia. | Tightening Torque | |
|
| |
1/4" (6.35 mm) | Approx. 140 — 180 | |
(120 — 160 | ||
| ||
|
| |
5/8" (15.88 mm) | Approx. 680 — 820 | |
(590 — 710 | ||
|
Torque wrench
Spanner
Indoor unit
Outdoor unit
0131_C_I
Fig.
Refrigerant tubing
Seal (supplied)
| Insulation tape (white) |
| (supplied) |
| Flare insulator (supplied) |
Unit side | Tube insulator |
(not supplied) | |
insulator |
|
Flare nut | Vinyl clamps (supplied) |
| |
| 1015_X_I |
Fig.
Always insulate tubes after
CAUTION completing leak tests on all connection points.
Important
To avoid condensation and water leaks, the wide and narrow tubes must be insulated with the supplied insulation materials.
Taping the flare nuts
Wind white insulation tape around the flare nuts at the wide and narrow tube connections. Place the seal (supplied) on the unit. Then cover up the tubing connections with the flare nut insulator, and cover the gap at the union with the supplied black insulation tape. Finally, fix the insulator at both ends with vinyl clamps. (Fig.
Insulation material
The material used for insulation must have good insuIation characteristics, be easy to use, be age resistant, and must not easily absorb moisture.
After a tube has been insu-
CAUTION lated, never try to bend it because it can cause the tube to break or crack.
| Refrigerant tubing and insulator | |
Drain insulator | (not supplied) | |
Drain pipe and insulator | ||
and clamp. | ||
Large | (not supplied) | |
(supplied) |
| |
Packing |
| |
clamp. | Insulation | |
Small | tape | |
hose band | Vinyl | |
(supplied) | ||
Flare clamp | ||
| ||
| insulator | |
| Seal |
0558_X_I
Never grasp the drain or refrigerant connecting outlets when moving the unit.
Fig.
22S4359128