Sanyo XS1852 Precautions during Brazing, Connecting Tubing between Indoor and Outdoor Units

Page 22

7-4. Precautions during Brazing

Replace air inside the tube with nitrogen gas to prevent copper oxide film from forming during the brazing process.

Do not allow the tubing to get too hot during the brazing process.

The nitrogen gas inside the tubing may overheat, causing refrigerant system valves to become damaged. Therefore allow the tubing to cool be- tween brazings.

7-5. Connecting Tubing between Indoor and Outdoor Units

(1)Tightly connect the indoor side refrigerant tubing with the outdoor side tubing. (Fig. 7-6)

(2)To fasten the flare nuts, apply specified torque as:

Table 7-1

Tube Dia.

Tightening Torque

 

 

1/4" (6.35 mm)

Approx. 140 — 180 kg-cm

(120 — 160 Ibs-in.)

 

 

 

5/8" (15.88 mm)

Approx. 680 — 820 kg-cm

(590 — 710 lbs-in.)

 

Torque wrench

Spanner

Indoor unit

Outdoor unit

0131_C_I

Fig. 7-6

Refrigerant tubing

Seal (supplied)

 

Insulation tape (white)

 

(supplied)

 

Flare insulator (supplied)

Unit side

Tube insulator

(not supplied)

insulator

 

Flare nut

Vinyl clamps (supplied)

 

 

1015_X_I

Fig. 7-7

7-6. Insulating the Refrigerant Tubing

Always insulate tubes after

CAUTION completing leak tests on all connection points.

Important

To avoid condensation and water leaks, the wide and narrow tubes must be insulated with the supplied insulation materials.

Taping the flare nuts

Wind white insulation tape around the flare nuts at the wide and narrow tube connections. Place the seal (supplied) on the unit. Then cover up the tubing connections with the flare nut insulator, and cover the gap at the union with the supplied black insulation tape. Finally, fix the insulator at both ends with vinyl clamps. (Fig. 7-7)

Insulation material

The material used for insulation must have good insuIation characteristics, be easy to use, be age resistant, and must not easily absorb moisture.

After a tube has been insu-

CAUTION lated, never try to bend it because it can cause the tube to break or crack.

 

Refrigerant tubing and insulator

Drain insulator

(not supplied)

Drain pipe and insulator

and clamp.

Large

(not supplied)

(supplied)

 

Packing

 

clamp.

Insulation

Small

tape

hose band

Vinyl

(supplied)

Flare clamp

 

 

insulator

 

Seal

0558_X_I

Never grasp the drain or refrigerant connecting outlets when moving the unit.

Fig. 7-8

22S4359128

Image 22
Contents Installation Instructions Please Read Before Starting General Tubing Length Models C1852 Tubing Data CL1852Selecting the Installation Site Indoor UnitProvide a solid base level concrete pad, concrete Outdoor UnitBaffle Plates for the Outdoor Unit CL⋅⋅ models only Preparation for Suspending How to Install the Indoor UnitSuspending the Indoor Unit Unit inch mmPlacing the Unit Inside the Ceiling Do not install the pipe with an upward Installing the Drain PipingDo not install an air Backwards and leak when the unit isBe careful since the fan will Start turning when checkingChecking the Drainage DrainageLatch Screw Air intake grille Ceiling panel Installing the Ceiling Panel When Removing the Ceiling Panel for ServicingSetup for the indoor unit Duct for Fresh AirInstalling the Indoor Unit Installing the AIR-INTAKE ChamberInstalling the Duct Connection BOX Take adequate precautions Caution when installing ontoRemovable mounting Mounting on a WallNon-removable mounting Wired Remote Control Unit Option Installing the Wired Remote Control UnitSwitch Positions for 2 Units or 2 Groups of Units Address SwitchesFinding the Address Switches Remote Control Unit Remote Control Indoor Unit Unit No Address switchWiring Instructions for the Outdoor Unit Electrical WiringGeneral Precautions on Wiring Models Problem Indoor Indoor Unit Outdoor UnitFor stranded wiring Screwdriver. FigPrecaution before Connecting Tubes Tightly How to Process TubingFlaring Procedure with a Flare Tool Use of the Flaring MethodRefrigerant tubing Precautions during BrazingConnecting Tubing between Indoor and Outdoor Units Taping the flare nutsFinishing the Installation Taping the TubesAir Purging 10 min. or more 15 min. or moreBe sure to completely insert Hex wrench beforeTest Run Performing Test Run with Optional Wired Remote Control UnitPerforming Test Run Be careful since the fan will Valve 2-Way Valve 3-Way Basic Function of the Service ValvesAction Pump Down
Related manuals
Manual 45 pages 15.8 Kb