Always check the gas density WARNING limit for the room in which the
unit is installed.
When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room.
If the density could exceed the limit level, it is necessary to provide an opening between the unit and the adjacent room, or to install mechanical ventilation which is interlocked with a leak detector.
(Total refrigerant charged amount: oz)
(Min. indoor volume where the indoor unit is installed: ft.3)
<Limit density 0.3 (oz/ft.3)
The limit density of refrigerant R410A which is used in this unit is 0.3 oz/ft.3 (ISO 5149).
The shipped outdoor unit comes charged with the amount of refrig- erant fixed for each type, so add it to the amount that is charged in the field. (For the refrigerant charge amount at shipment, refer to the unit’s nameplate.)
Pay special attention to any location,
CAUTION such as a basement, etc., where leak- ing refrigerant can accumulate, since
refrigerant gas is heavier than air.
(1)Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed with the optional distribution joint kit
(2)When creating a branch using a commercially available
(3)If there are height differences between indoor units or if branch tubing that follows a distribution joint is connected to only 1 unit, a trap or ball valve must be added to that
distribution joint. (When adding the ball valve, locate it within 1.3 ft. of the distribution joint.)
If a trap or ball valve is not added, do not operate the sys- tem before repairs to a malfunctioning unit are completed. (The refrigerant oil sent through the tubing to the malfunctioning unit will accumulate and may damage the compressor.)
Minimum indoor volume & floor area as against the amount of refrigerant is roughly as given in the following table.
| ft.3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ft.2 |
|
| |
| 10000 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1136 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 9500 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1079 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 9000 |
| Range below |
|
|
|
|
|
|
|
|
|
| 1022 |
| h) | |||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| 8500 |
| the density limit of |
|
|
|
|
|
|
| 966 |
| g | ||||||
|
|
|
|
|
|
|
|
|
| ||||||||||
| 8000 |
|
|
|
|
|
|
|
| 909 | Min. indoor floor area | n the ceiling is 8.8 ft. hi | |||||||
Min. indoor volume |
| 0.3 oz/ft.3 |
|
|
|
|
|
|
|
|
|
| |||||||
7500 |
|
|
|
|
|
|
|
|
|
|
| 852 | |||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||
7000 |
| (countermeasures |
|
|
|
|
|
|
| 795 | |||||||||
|
|
|
|
|
|
|
| ||||||||||||
6500 |
| not needed) |
|
|
|
|
|
|
|
|
|
| 738 | ||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||
6000 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 682 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
5500 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 625 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
5000 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 568 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
4500 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 511 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
4000 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 454 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
3500 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 398 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
| 3000 |
|
|
|
|
|
| Range above |
|
| 341 |
| (whe | ||||||
|
|
|
|
|
|
|
|
|
| ||||||||||
| 2500 |
|
|
|
|
|
| the density limit of |
|
| 284 |
| |||||||
|
|
|
|
|
|
|
|
|
| ||||||||||
| 2000 |
|
|
|
|
|
|
|
| 227 |
|
| |||||||
|
|
|
|
|
|
| 0.3 oz/ft.3 |
|
|
|
|
|
| ||||||
| 1500 |
|
|
|
|
|
|
|
|
|
| 170 |
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| 1000 |
|
|
|
|
|
| (countermeasures |
|
| 114 |
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| |||||||||
| 500 |
|
|
|
|
|
| needed) |
|
|
|
| 57 |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
| 0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 0 | 500 | 1000 | 1500 | 2000 | 2500 | 3000 |
|
| ||||||||||
|
|
| Total amount of refrigerant |
|
| oz |
|
| |||||||||||
|
|
|
|
|
|
|
|
Tube branching methods (horizontal use)
|
| ° |
| to | 30 |
15 |
| |
|
|
|
|
|
| B |
| |
|
| A | Horizontal | A | ||
B | line | View as seen | ||||
| ||||||
|
| |||||
|
|
|
| from arrow | ||
|
| Arrow view |
|
| ||
Types of vertical trap specifications |
| |||||
(When using ball valve) |
|
| ||||
Main tubing |
|
|
| |||
Ball valve | Indoor unit (more than 2 units) | |||||
(If only 1 unit is connected, a ball valve | ||||||
(BV: purchased | ||||||
separately) | is also needed on this side.) | |||||
Indoor unit (1) |
|
|
| |||
(When not using ball valve) |
| |||||
Main tubing | Horizontal |
|
| |||
|
|
|
| |||
|
| Indoor unit (Each unit is connected | ||||
Branch tubing is |
| to tubing that is either | ||||
| level or is directed | |||||
directed upward. |
| |||||
| downward.) | |||||
|
| More than |
| |||
|
|
|
|
| ||
|
| 8 inch |
|
|
| |
|
|
|
|
| ||
Indoor unit is directed downward |
|
|
|
14