Sanyo 85464359982001 Tube diameter Tightening torque Tube thickness Approximate

Page 64

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 64

Caution Before Connecting Tubes Tightly

(1)Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used.

(2)Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks.

(Fig. 6-4)

(3)For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 6-5)

Adjust the shape of the liquid tube using a tube bender at the installation site and connect it to the liquid tubing side valve using a flare.

Cautions During Brazing

Replace air inside the tube with nitrogen gas to prevent copper oxide film from forming during the brazing process. (Oxygen, carbon dioxide and Freon are not acceptable.)

Do not allow the tubing to get too hot during brazing. The nitrogen gas inside the tubing may overheat, causing refrigerant system valves to become damaged. Therefore allow the tubing to cool when brazing.

Use a reducing valve for the nitrogen cylinder.

Do not use agents intended to prevent the formation of oxide film. These agents adversely affect the refrigerant and refrigerant oil, and may cause damage or malfunctions.

6-2. Connecting Tubing Between Indoor and Outdoor Units

(1)Tightly connect the indoor-side refrigerant tubing extended from the wall with the outdoor-side tubing.

(2)To fasten the flare nuts, apply specified torque as at right:

When removing the flare nuts from the tubing connections, or when tightening them after connecting the tubing, be sure to use 2 monkey wrenches or spanners as shown. (Fig. 6-6)

If the flare nuts are over-tightened, the flare may be damaged, which could result refrigerant leakage and cause in injury or asphyxiation to room occupants.

For the flare nuts at tubing connections, be sure to use the flare nuts that were supplied with the unit, or else flare nuts for R410A (type 2). The refrigerant tubing that is used must be of the correct wall thickness as shown in the table at right.

Apply refrigerant

lubricant here and here

Fig. 6-4

Union Flare nut

Fig. 6-5

Torque wrench

Indoor unit

 

 

Spanner

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

Fig. 6-6

 

 

 

 

 

 

Tube diameter

Tightening torque,

Tube thickness

approximate

 

 

 

 

 

 

ø1/4" (ø6.35 mm)

120 – 160 lbs · inch

1/32"

(140 – 180 kgf · cm)

 

(0.8 mm)

 

 

ø3/8" (ø9.52 mm)

300

– 360 lbs · inch

1/32"

(340

– 420 kgf · cm)

 

(0.8 mm)

 

 

ø1/2" (ø12.7 mm)

430 – 530 lbs · inch

1/32"

(490

– 610 kgf · cm)

 

(0.8 mm)

 

 

ø5/8" (ø15.88 mm)

590

– 710 lbs · inch

5/128"

(680

– 820 kgf · cm)

 

(1.0 mm)

ø3/4" (ø19.05 mm)

870

– 1040 lbs · inch

 

over 5/128"

(1000 – 1200 kgf · cm)

 

(1.0 mm)

Because the pressure is approximately 1.6 times higher

than conventional refrigerant pressure, the use of ordinary

flare nuts (type 1) or thin-walled tubes may result in tube

rupture, injury, or asphyxiation caused by refrigerant

leakage.

In order to prevent damage to the flare caused by over- tightening of the flare nuts, use the table above as a guide when tightening.

When tightening the flare nut on the liquid tube, use a monkey wrench with a nominal handle length of 7-7/8 in.

64

Image 64
Contents R410A Models Indoor Units Outdoor UnitsOptional Controllers Gunma, Japan…In a Room …In Moist or Uneven Locations…In an Area with High Winds …In a Snowy Area for Heat Pump-type SystemsCheck of Density Limit Care regarding tubing Be sure to recharge the refrigerant only in liquid formDifferent tools required NewCompressor specifications are different Use R410A exclusive cylinder onlySingle-outlet valve Existing tubing cannot be used especially R22Contents HOW to Process Tubing AIR PurgingAir Purging with a Vacuum Pump for Test Run Preparation Test RUNGeneral Outdoor Unit Part name’ty Model 10 hp 16 hp1-Way Air Discharge Semi-Concealed 4-Way Air Discharge Semi-ConcealedConcealed Duct Ceiling-Mounted Concealed Duct High-Static PressureWall-Mounted Mark ContentsLength ft Tubing Size Main Tubing Size LA 10 Main Tubing Size After Distribution LB, LC11 Outdoor Unit Tubing Connection Size a BTU/h 28.0 45.0Straight Equivalent Length of Joints 13 Straight Equivalent Length of JointsAdditional Refrigerant Charge 16 Refrigerant Charge Amount at Shipment for outdoor unitWhen not using ball valve When using ball valveTube branching methods horizontal use Optional Distribution Joint Kits Model name Cooling capacity after distribution RemarksTubing size with thermal insulation Example232,000 BTU/h 68.0 kW Example Main tubing Distribution joint tubingMain tubing Selecting the Installation Site Indoor UnitFront view Side viewInstallation Space Outdoor UnitLeave space open above UnitPrecautions When Installing in Heavy Snow Areas Shield for Horizontal Exhaust DischargeUnit installation Air direction Front directionAir direction Suspending the Indoor Unit Placing the Unit Inside the Ceiling12, 18, 24 12, 18Installing the Drain Piping Be careful since the fan will Start when you short the pinOn the indoor control board Removing the corner cover Installing the Ceiling Panel Panel installation locations so that the panel isAttached tightly to the unit. Fig Check that the panel is attached tightly toWiring the Ceiling Panel Checking After Installation When Removing the Ceiling Panel for ServicingAdjusting the Auto Flap Special Remarks DC Fan Tap Change Procedure29/64 Full-scale Installation diagram Suspension lug 25/32 1 Installing the Drain Piping When you short the pin on the indoor Be careful since the fan will startControl board Bottom drain port is for use onlyElectrical Power Wiring Wiring connections WiringAppearance Part name AppearanceRemoving the intake grille Removing the side panelAdjust so that there is no gap Installing the side panel and intake grille Installing the intake grilleOther Check after installation If a wireless remote controller is used62 and -4 show the detailed dimensions of the indoor unit Type LengthSuspension bolts referring to the dimensional data on Previous page. -61 and TableTubing must be laid and connected inside the ceiling when Unit inside the ceilingDo not use adhesive at the drain connection port on Indoor unitDo not use the supplied drain hose bent at a 90 angle Maximum permissible bend isBe careful since the fan will start when you How to read the diagramShort the pin on the indoor control board Increasing the Fan SpeedThis air conditioner is usually installed above the ceiling Minimum space for installation and service is shownSo that the indoor unit and ducts are not visible. Only Air intake and air outlet ports are visible from belowEnough to suport the weight of the unit It is important that you use extreme careSupporting the indoor unit inside Ceiling. Ensure that the ceiling is strongIndoor Fan Performance How to Read the Diagram Service Refrigerant tubing drain hose positionWeight of the unit. Before Wall and ceiling side opening positionIt is important that you use Extreme care in supportingInside Shaping the Tubing Duct for Fresh AirRear outlet port How to carry out power supply wiring When removing the fasteningRegulations before wiring Bracket from the coverSelecting and Making a Hole Removing the Grille to Install the Indoor Unit If the Wall is Brick, Concrete or SimilarRemoving the grille Attaching the grilleInstalling the Drain Hose Shaping the Tubing Right-rear tubingLeft or left-rear tubing Unit are completedKHX0752 / 0952 / 1252 Installing the Outdoor Unit HOW to Install the Outdoor UnitTransporting Routing the Tubing Connect the Tubing Prepare the TubingRefrigerant tubing Connection method Supplied parts used? Refrigerant tube port Tightening torque for each capWork method Cap tightening torqueGeneral Precautions on Wiring Electrical WiringInter-outdoor unit control wiring Wiring System Diagram U, D, T TypeOutdoor unit Indoor unit How to connect wiring to the terminal For stranded wiring Shielded wire GroundGroundHOW to Process Tubing Connecting the Refrigerant Tubing Use of the Flaring MethodFlaring Procedure with a Flare Tool DeburringTube diameter Tightening torque Tube thickness Approximate 870 Lbs · inch Over 5/128 1000 1200 kgf · cmTwo tubes arranged together Three tubes arranged togetherInsulating the Refrigerant Tubing Tubing Insulation Insulation materialFinishing the Installation Taping the TubesBottom when you pressurize Air Purging with a Vacuum Pump for Test Run PreparationLeak test Use a manifold valve for air purgingEvacuation 45 min. or more 90 min. or moreCharging additional refrigerant Use a cylinder designed for use With R410A respectivelyFinishing the job Test RUN Test Run Procedure Items to Check Before the Test RunMain Outdoor Unit PCB Setting Indoor unit setting S004 Rotary switch, red Examples of the No. of outdoor units settings S0063P DIP switch, blue Address setting of main outdoor unit S007 Unit No. settingAutomatic Address Setting from the Outdoor Unit Auto Address Setting Basic wiring diagram ExampleCase 22-9 Case 2 Automatic Address Setting no compressor operation Automatic Address Setting from Outdoor UnitAutomatic Address Setting from Outdoor Unit Automatic Address Setting in Heating ModeCase 3A Automatic Address Setting* from the Remote Controller Automatic Address Setting in Cooling ModeCase 3B Display during automatic address setting On outdoor main unit PCBRemote Controller Test Run Settings If 1 indoor unit is connected to 1 remote controllerChecking the indoor unit addresses 07-007 W-2WAYIINA 1/23/07 609 PM Alarm contents Possible cause of malfunctionAlarm Alarm messages displayed on system controller Appendix Care and CleaningName of Parts Troubleshooting Should the power fail while the unit is runningLatch Air intake Safety chain Grille Bolt screws Tips for Energy SavingType 1-WAY Water drain Air outlet Air intake Ceiling panel optionalTroubleshooting Concealed Duct High-Static Pressure Type U, D Type Type standard static pressure Type high static pressureTroubleshooting Components and cause an electric shock hazard Air intake grille air intakeOr soot Type Wall-Mounted Tips for Energy Saving