Sanyo 85464359982001 Test Run Procedure, Items to Check Before the Test Run

Page 71

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 71

8-2. Test Run Procedure

Recheck the items to check before the test run.

Items to Check Before the Test Run

1.

Turn the remote power switch on at least 5 hours

 

before the test, in order to energize the crank

 

case heater.

2.

After performing the leak inspection, applying

 

vacuum, and performing refrigerant charge for

<Outdoor unit control PCB> Unit No. setting switch (S007)

<Outdoor unit control PCB> Unit No. setting switch (S006)

<Outdoor unit control PCB> Unit No. setting switch (S004 and S005)

(Check the link wiring.)

<Outdoor unit control PCB> Unit No. setting switch (S002 and S003)

NO

Have the outdoor sub units been connected?

YES

Set the unit address.

*1

 

 

 

 

 

 

 

 

Set the No. of outdoor units.

 

 

 

 

 

 

 

 

 

 

 

 

Set the No. of indoor units.

 

 

 

NO

 

 

Are the inter-unit control wires

connected to more than 1 refrigerant

 

system?

 

 

 

YES

 

 

 

 

Set the system address.

 

*1 The unit with the unit No. set to 1 is the main unit. All other units are sub units.

CASE 1

 

the tubing which is connected on-site, fully open

 

the outdoor unit service valve. However if only

 

one outdoor unit is installed, a balance tube is

 

not used. Therefore, leave the valve fully closed.

3.

When replacing the control PCB, be sure that

 

the settings on the new PCB match those on the

 

old PCB.

4.

Use caution when making the settings. If there

 

are duplicated system addresses, or if the

 

settings for the Nos. of the indoor units are not

 

consistent, an alarm will occur and the system

 

will not start.

5.

These settings are not made on the indoor unit

 

PCB.

When multiple outdoor main units exist, disconnect the terminals

Refer to Fig. 8-4extended from the shorted plugs (CN003) at all outdoor main unit PCBs except for 1.

Alternatively, move the sockets to the OPEN side.

Note: It is not necessary to remove the socket that is used to short-circuit the terminal plugs from the outdoor sub unit PCBs.

 

 

Is it possible to turn ON the power only

 

YES CASE 2

 

 

 

 

 

for the 1 refrigerant system where the

 

 

 

 

 

 

 

 

 

 

 

test run will be performed?

 

 

 

 

 

 

 

 

Turn ON the indoor and

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor unit power for that

 

 

 

 

 

 

 

 

 

 

 

 

refrigerant system only.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Will automatic address setting be

 

 

 

Make necessary corrections.

 

 

 

 

 

 

 

 

Short-circuit the automatic address pin (CN100)

 

NO

performed in Heating mode?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on the outdoor main unit PCB for 1 second or

 

 

 

 

 

 

 

 

 

 

 

 

longer, then release it.

 

CASE 3B

 

YES

CASE 3A

Turn OFF the indoor and

 

 

 

 

 

 

 

 

 

outdoor unit power.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is it OK to start the compressors?

Is it OK to start the compressors?

 

 

 

 

 

 

 

LED 1 and 2 blink alternately

 

 

 

 

Check the alarm contents.

 

(about 2 or 3 minutes).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn ON the indoor and

Turn ON the indoor and

 

 

 

 

 

 

NO

 

 

 

outdoor unit power.

outdoor unit power.

 

 

 

 

 

 

 

Are LEDs 1 and 2 on the

*2

 

*2

 

 

 

Make necessary

 

 

 

 

outdoor unit PCB OFF?

Short-circuit the mode change pin

Short-circuit the automatic address

 

corrections

 

Refer to “Table of

 

 

 

 

 

 

(CN101) on the outdoor main unit PCB.

pin (CN100) on the outdoor main

 

 

 

 

Self-Diagnostic Functions and

 

 

 

 

 

 

Description of Alarm Displays.”

 

YES

At the same time, short-circuit the

unit PCB for 1 second or longer,

 

 

 

 

 

Turn OFF the indoor and

 

 

 

 

automatic address pin (CN100) for 1

then release it.

 

 

outdoor unit power.

 

 

 

 

 

second or longer, then release it.

 

 

 

 

 

 

 

 

 

 

 

 

*3

 

*3

 

Start indoor and outdoor unit

Start indoor and outdoor unit

cooling operation.

 

heating operation.

LED 1 and 2 blink alternately.

LED 1 and 2 blink alternately.

 

 

NO

 

 

 

 

Are LEDs 1 and 2 on the

 

outdoor unit PCB OFF?

 

YES

Check the alarm

contents.

*2 A minimum of 5 hours must have passed after the power was turned ON to the outdoor unit.

*3 All indoor units operate in all refrigerant systems where the power is ON.

Check that test run preparation is OK.

(Do not allow the short-circuited pins to remain short-circuited.)

Set the wired remote controller for test run.

Refer to the remote

 

 

NO

 

 

controller test-run

 

 

Does system operate?

settings.

 

 

 

Check and make corrections according to “Table of Self-Diagnostic Functions.”

YES

Return remote control to normal mode

Fig. 8-3

End test run.

71

Image 71
Contents Gunma, Japan R410A Models Indoor UnitsOutdoor Units Optional Controllers…In a Snowy Area for Heat Pump-type Systems …In a Room…In Moist or Uneven Locations …In an Area with High WindsCheck of Density Limit New Care regarding tubingBe sure to recharge the refrigerant only in liquid form Different tools requiredExisting tubing cannot be used especially R22 Compressor specifications are differentUse R410A exclusive cylinder only Single-outlet valveContents Test RUN HOW to Process TubingAIR Purging Air Purging with a Vacuum Pump for Test Run PreparationModel 10 hp 16 hp GeneralOutdoor Unit Part name ’tyConcealed Duct 4-Way Air Discharge Semi-Concealed1-Way Air Discharge Semi-Concealed Wall-Mounted Concealed Duct High-Static PressureCeiling-Mounted Length ft ContentsMark 28.0 45.0 Tubing Size Main Tubing Size LA10 Main Tubing Size After Distribution LB, LC 11 Outdoor Unit Tubing Connection Size a BTU/h16 Refrigerant Charge Amount at Shipment for outdoor unit Straight Equivalent Length of Joints13 Straight Equivalent Length of Joints Additional Refrigerant ChargeTube branching methods horizontal use When using ball valveWhen not using ball valve Example Optional Distribution Joint KitsModel name Cooling capacity after distribution Remarks Tubing size with thermal insulation232,000 BTU/h 68.0 kW Main tubing Distribution joint tubing ExampleMain tubing Side view Selecting the Installation SiteIndoor Unit Front viewUnit Installation SpaceOutdoor Unit Leave space open aboveShield for Horizontal Exhaust Discharge Precautions When Installing in Heavy Snow AreasAir direction Front direction Unit installationAir direction 12, 18 Suspending the Indoor UnitPlacing the Unit Inside the Ceiling 12, 18, 24Installing the Drain Piping On the indoor control board Start when you short the pinBe careful since the fan will Removing the corner cover Check that the panel is attached tightly to Installing the Ceiling PanelPanel installation locations so that the panel is Attached tightly to the unit. FigWiring the Ceiling Panel Special Remarks DC Fan Tap Change Procedure Checking After InstallationWhen Removing the Ceiling Panel for Servicing Adjusting the Auto Flap29/64 Full-scale Installation diagram Suspension lug 25/32 1 Installing the Drain Piping Bottom drain port is for use only When you short the pin on the indoorBe careful since the fan will start Control boardAppearance Electrical Power Wiring Wiring connectionsWiring Appearance Part nameRemoving the side panel Removing the intake grilleAdjust so that there is no gap If a wireless remote controller is used Installing the side panel and intake grilleInstalling the intake grille Other Check after installationType Length 62 and -4 show the detailed dimensions of the indoor unitUnit inside the ceiling Suspension bolts referring to the dimensional data onPrevious page. -61 and Table Tubing must be laid and connected inside the ceiling whenMaximum permissible bend is Do not use adhesive at the drain connection port onIndoor unit Do not use the supplied drain hose bent at a 90 angleIncreasing the Fan Speed Be careful since the fan will start when youHow to read the diagram Short the pin on the indoor control boardAir intake and air outlet ports are visible from below This air conditioner is usually installed above the ceilingMinimum space for installation and service is shown So that the indoor unit and ducts are not visible. OnlyCeiling. Ensure that the ceiling is strong Enough to suport the weight of the unitIt is important that you use extreme care Supporting the indoor unit insideIndoor Fan Performance How to Read the Diagram Refrigerant tubing drain hose position ServiceExtreme care in supporting Weight of the unit. BeforeWall and ceiling side opening position It is important that you useInside Rear outlet port Duct for Fresh AirShaping the Tubing Bracket from the cover How to carry out power supply wiringWhen removing the fastening Regulations before wiringSelecting and Making a Hole Attaching the grille Removing the Grille to Install the Indoor UnitIf the Wall is Brick, Concrete or Similar Removing the grilleUnit are completed Installing the Drain HoseShaping the Tubing Right-rear tubing Left or left-rear tubingKHX0752 / 0952 / 1252 Transporting HOW to Install the Outdoor UnitInstalling the Outdoor Unit Routing the Tubing Refrigerant tubing Connection method Supplied parts used? Prepare the TubingConnect the Tubing Cap tightening torque Refrigerant tube portTightening torque for each cap Work methodInter-outdoor unit control wiring Electrical WiringGeneral Precautions on Wiring U, D, T Type Wiring System DiagramOutdoor unit Indoor unit Shielded wire GroundGround How to connect wiring to the terminal For stranded wiringDeburring HOW to Process TubingConnecting the Refrigerant Tubing Use of the Flaring Method Flaring Procedure with a Flare Tool870 Lbs · inch Over 5/128 1000 1200 kgf · cm Tube diameter Tightening torque Tube thickness ApproximateInsulation material Two tubes arranged togetherThree tubes arranged together Insulating the Refrigerant Tubing Tubing InsulationTaping the Tubes Finishing the InstallationUse a manifold valve for air purging Bottom when you pressurizeAir Purging with a Vacuum Pump for Test Run Preparation Leak test45 min. or more 90 min. or more EvacuationFinishing the job Use a cylinder designed for use With R410A respectivelyCharging additional refrigerant Test RUN Items to Check Before the Test Run Test Run ProcedureMain Outdoor Unit PCB Setting Address setting of main outdoor unit S007 Unit No. setting Indoor unit setting S004 Rotary switch, redExamples of the No. of outdoor units settings S006 3P DIP switch, blueCase Auto Address Setting Basic wiring diagram ExampleAutomatic Address Setting from the Outdoor Unit 22-9 Automatic Address Setting from Outdoor Unit Case 2 Automatic Address Setting no compressor operationCase 3A Automatic Address Setting in Heating ModeAutomatic Address Setting from Outdoor Unit Case 3B Automatic Address Setting in Cooling ModeAutomatic Address Setting* from the Remote Controller On outdoor main unit PCB Display during automatic address settingChecking the indoor unit addresses If 1 indoor unit is connected to 1 remote controllerRemote Controller Test Run Settings 07-007 W-2WAYIINA 1/23/07 609 PM Possible cause of malfunction Alarm contentsAlarm Alarm messages displayed on system controller Name of Parts Care and CleaningAppendix Tips for Energy Saving TroubleshootingShould the power fail while the unit is running Latch Air intake Safety chain Grille Bolt screwsWater drain Air outlet Air intake Ceiling panel optional Type 1-WAYTroubleshooting Type standard static pressure Type high static pressure Concealed Duct High-Static Pressure Type U, D TypeTroubleshooting Air intake grille air intake Components and cause an electric shock hazardOr soot Type Wall-Mounted Tips for Energy Saving