Sanyo 85464359982001 Optional Distribution Joint Kits, Tubing size with thermal insulation

Page 15

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 15

1-12. Optional Distribution Joint Kits

See the installation instructions packaged with the distribution joint kit for the installation procedure.

Table 1-18

 

Model name

Cooling capacity after distribution

Remarks

 

 

 

 

 

1.

APR-CHP680BA

232,000

BTU/h (68.0 kW) or less

For outdoor unit

 

 

 

 

2.

APR-CHP1350BA

460,700 BTU/h (135.0 kW) or less

For outdoor unit

 

 

 

 

 

3.

APR-P160BA

76,400

BTU/h (22.4 kW) or less

For indoor unit

 

 

 

 

 

4.

APR-P680BA

232,000

BTU/h (68.0 kW) or less

For indoor unit

 

 

 

 

5.

APR-P1350BA

460,700 BTU/h (135.0 kW) or less

For indoor unit

 

 

 

 

 

Tubing size (with thermal insulation)

1.APR-CHP680BA

For outdoor unit (Capacity after distribution joint is 232,000 BTU/h (68.0 kW) or less.)

Example:

 

Gas tubing

 

 

Liquid tubing

B

 

6-59/64

 

 

4-21/64

 

 

5-5/16

 

 

3-13/16

 

 

 

 

 

 

 

 

C

4-3

F

 

G

D

C

D E F

E F

G

 

 

 

 

1/64

I H

 

G

 

 

C

 

 

 

 

 

 

Distribution

 

 

 

 

 

H

Distribution

 

 

Joint

 

 

 

 

I

Joint

 

 

 

Insulation

 

 

 

 

 

 

 

 

Reducing

JointsInsulation

Table 1-19 Size of connection point on each part (Shown are inside diameters of tubing)

H I

F

2-53

 

/64

Reducing

Joints

Unit: in.

Size

Part A

Part B

Part C

Part D

Part E

Part F

Part G

Part H

Part I

 

 

 

 

 

 

 

 

 

 

in. (mm)

ø1-1/2"

ø1-1/4"

ø1-1/8"

ø1"

ø7/8"

ø3/4"

ø5/8"

ø1/2"

ø3/8"

(ø38.1)

(ø31.75)

(ø28.58)

(ø25.4)

(ø22.22)

(ø19.05)

(ø15.88)

(ø12.7)

(ø9.52)

 

 

 

 

 

 

 

 

 

 

 

2. APR-CHP1350BA

For outdoor unit (Capacity after distribution joint is greater than 232,000 BTU/h (68.0 kW) and no more than

Example:

 

 

 

460,700 BTU/h (135.0 kW).)

Gas tubing

 

Liquid tubing

 

 

6-57/64

5-5/16

AB B

A

 

 

C

D

4-3

1/64

 

 

4-21/64

3-13/16

FG

E FG

H I

F

2-53

 

/64

Distribution B

I H

G

Joint

C

D

Insulation

E

F

Reducing Joints

Distribution

JointH

I

Insulation

Reducing

Joints

Unit: in.

Table 1-20 Size of connection point on each part (Shown are inside diameters of tubing)

Size

Part A

Part B

Part C

Part D

Part E

Part F

Part G

Part H

Part I

 

 

 

 

 

 

 

 

 

 

in. (mm)

ø1-1/2"

ø1-1/4"

ø1-1/8"

ø1"

ø7/8"

ø3/4"

ø5/8"

ø1/2"

ø3/8"

(ø38.1)

(ø31.75)

(ø28.58)

(ø25.4)

(ø22.22)

(ø19.05)

(ø15.88)

(ø12.7)

(ø9.52)

 

 

 

 

 

 

 

 

 

 

 

15

Image 15
Contents Gunma, Japan R410A Models Indoor UnitsOutdoor Units Optional Controllers…In a Snowy Area for Heat Pump-type Systems …In a Room…In Moist or Uneven Locations …In an Area with High WindsCheck of Density Limit New Care regarding tubingBe sure to recharge the refrigerant only in liquid form Different tools requiredExisting tubing cannot be used especially R22 Compressor specifications are differentUse R410A exclusive cylinder only Single-outlet valveContents Test RUN HOW to Process TubingAIR Purging Air Purging with a Vacuum Pump for Test Run PreparationModel 10 hp 16 hp GeneralOutdoor Unit Part name ’ty4-Way Air Discharge Semi-Concealed 1-Way Air Discharge Semi-ConcealedConcealed Duct Concealed Duct High-Static Pressure Ceiling-MountedWall-Mounted Contents MarkLength ft 28.0 45.0 Tubing Size Main Tubing Size LA10 Main Tubing Size After Distribution LB, LC 11 Outdoor Unit Tubing Connection Size a BTU/h16 Refrigerant Charge Amount at Shipment for outdoor unit Straight Equivalent Length of Joints13 Straight Equivalent Length of Joints Additional Refrigerant ChargeWhen using ball valve When not using ball valveTube branching methods horizontal use Example Optional Distribution Joint KitsModel name Cooling capacity after distribution Remarks Tubing size with thermal insulation232,000 BTU/h 68.0 kW Main tubing Distribution joint tubing ExampleMain tubing Side view Selecting the Installation SiteIndoor Unit Front viewUnit Installation SpaceOutdoor Unit Leave space open aboveShield for Horizontal Exhaust Discharge Precautions When Installing in Heavy Snow AreasAir direction Front direction Unit installationAir direction 12, 18 Suspending the Indoor UnitPlacing the Unit Inside the Ceiling 12, 18, 24Installing the Drain Piping Start when you short the pin Be careful since the fan willOn the indoor control board Removing the corner cover Check that the panel is attached tightly to Installing the Ceiling PanelPanel installation locations so that the panel is Attached tightly to the unit. FigWiring the Ceiling Panel Special Remarks DC Fan Tap Change Procedure Checking After InstallationWhen Removing the Ceiling Panel for Servicing Adjusting the Auto Flap29/64 Full-scale Installation diagram Suspension lug 25/32 1 Installing the Drain Piping Bottom drain port is for use only When you short the pin on the indoorBe careful since the fan will start Control boardAppearance Electrical Power Wiring Wiring connectionsWiring Appearance Part nameRemoving the side panel Removing the intake grilleAdjust so that there is no gap If a wireless remote controller is used Installing the side panel and intake grilleInstalling the intake grille Other Check after installationType Length 62 and -4 show the detailed dimensions of the indoor unitUnit inside the ceiling Suspension bolts referring to the dimensional data onPrevious page. -61 and Table Tubing must be laid and connected inside the ceiling whenMaximum permissible bend is Do not use adhesive at the drain connection port onIndoor unit Do not use the supplied drain hose bent at a 90 angleIncreasing the Fan Speed Be careful since the fan will start when youHow to read the diagram Short the pin on the indoor control boardAir intake and air outlet ports are visible from below This air conditioner is usually installed above the ceilingMinimum space for installation and service is shown So that the indoor unit and ducts are not visible. OnlyCeiling. Ensure that the ceiling is strong Enough to suport the weight of the unitIt is important that you use extreme care Supporting the indoor unit insideIndoor Fan Performance How to Read the Diagram Refrigerant tubing drain hose position ServiceExtreme care in supporting Weight of the unit. BeforeWall and ceiling side opening position It is important that you useInside Duct for Fresh Air Shaping the TubingRear outlet port Bracket from the cover How to carry out power supply wiringWhen removing the fastening Regulations before wiringSelecting and Making a Hole Attaching the grille Removing the Grille to Install the Indoor UnitIf the Wall is Brick, Concrete or Similar Removing the grilleUnit are completed Installing the Drain HoseShaping the Tubing Right-rear tubing Left or left-rear tubingKHX0752 / 0952 / 1252 HOW to Install the Outdoor Unit Installing the Outdoor UnitTransporting Routing the Tubing Prepare the Tubing Connect the TubingRefrigerant tubing Connection method Supplied parts used? Cap tightening torque Refrigerant tube portTightening torque for each cap Work methodElectrical Wiring General Precautions on WiringInter-outdoor unit control wiring U, D, T Type Wiring System DiagramOutdoor unit Indoor unit Shielded wire GroundGround How to connect wiring to the terminal For stranded wiringDeburring HOW to Process TubingConnecting the Refrigerant Tubing Use of the Flaring Method Flaring Procedure with a Flare Tool870 Lbs · inch Over 5/128 1000 1200 kgf · cm Tube diameter Tightening torque Tube thickness ApproximateInsulation material Two tubes arranged togetherThree tubes arranged together Insulating the Refrigerant Tubing Tubing InsulationTaping the Tubes Finishing the InstallationUse a manifold valve for air purging Bottom when you pressurizeAir Purging with a Vacuum Pump for Test Run Preparation Leak test45 min. or more 90 min. or more EvacuationUse a cylinder designed for use With R410A respectively Charging additional refrigerantFinishing the job Test RUN Items to Check Before the Test Run Test Run ProcedureMain Outdoor Unit PCB Setting Address setting of main outdoor unit S007 Unit No. setting Indoor unit setting S004 Rotary switch, redExamples of the No. of outdoor units settings S006 3P DIP switch, blueAuto Address Setting Basic wiring diagram Example Automatic Address Setting from the Outdoor UnitCase 22-9 Automatic Address Setting from Outdoor Unit Case 2 Automatic Address Setting no compressor operationAutomatic Address Setting in Heating Mode Automatic Address Setting from Outdoor UnitCase 3A Automatic Address Setting in Cooling Mode Automatic Address Setting* from the Remote ControllerCase 3B On outdoor main unit PCB Display during automatic address settingIf 1 indoor unit is connected to 1 remote controller Remote Controller Test Run SettingsChecking the indoor unit addresses 07-007 W-2WAYIINA 1/23/07 609 PM Possible cause of malfunction Alarm contentsAlarm Alarm messages displayed on system controller Care and Cleaning AppendixName of Parts Tips for Energy Saving TroubleshootingShould the power fail while the unit is running Latch Air intake Safety chain Grille Bolt screwsWater drain Air outlet Air intake Ceiling panel optional Type 1-WAYTroubleshooting Type standard static pressure Type high static pressure Concealed Duct High-Static Pressure Type U, D TypeTroubleshooting Air intake grille air intake Components and cause an electric shock hazardOr soot Type Wall-Mounted Tips for Energy Saving