Sanyo 85464359982001 Care regarding tubing, Different tools required, New, Tool?

Page 4
3/4 (19.05)
over 5/128 (1.0)
Unit: in. (mm)

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 4

Precautions for Installation Using New Refrigerant

1. Care regarding tubing

1-1. Process tubing

Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.”

For tubes of ø7/8" (ø22.22 mm) or larger, use C1220 T-1/2H material or H material, and do not bend the tubes.

Tubing size: Be sure to use the sizes indicated in the table below.

Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints (optional).

When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.

CAUTION

Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to prevent dirt, moisture, or other foreign substances from entering. These substances can result in system malfunction.

Material

 

 

O

 

 

 

 

 

 

 

 

 

Copper tube

Outer diameter

1/4 (6.35)

3/8 (9.52)

1/2 (12.7)

5/8 (15.88)

 

 

 

 

 

 

 

Wall thickness

1/32 (0.8)

1/32 (0.8)

1/32 (0.8)

5/128 (1.0)

 

 

 

 

 

 

 

 

 

 

Unit: in. (mm)

Material

 

 

1/ 2 H, H

 

 

 

 

 

 

 

 

 

 

Copper tube

Outer diameter

7/8 (22.22)

1 (25.4)

1-1/8 (28.58)

1-1/4 (31.75)

1-1/2 (38.1)

1-5/8 (41.28)

 

 

 

 

 

 

 

Wall thickness

5/128 (1.0)

5/128 (1.0)

5/128 (1.0)

3/64 (1.1)

over 3/64 (1.15)

over 3/64 (1.20)

 

 

 

 

 

 

 

 

 

1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A refriger- ant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the prevention of water and other impurities becomes more important than ever.

2. Be sure to recharge the refrigerant only in liquid form.

2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects in the unit.

2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining refriger- ant and recharge the required total amount of new refrigerant after fixing the leak.

3. Different tools required

3-1. Tool specifications have been changed due to the characteristics of R410A. Some tools for R22- and R407C-type refrigerant systems cannot be used.

 

New

R407C tools

 

Item

compatible

Remarks

tool?

 

with R410A?

 

 

 

 

 

Manifold gauge

Yes

No

Types of refrigerant, refrigerating machine

 

 

 

oil, and pressure gauge are different.

 

 

 

 

Charge hose

Yes

No

To resist higher pressure, material must be changed.

 

 

 

 

Vacuum pump

Yes

Yes

Use a conventional vacuum pump if it is equipped

 

 

 

with a check valve. If it has no check valve,

 

 

 

purchase and attach a vacuum pump adapter.

 

 

 

 

Leak detector

Yes

No

Leak detectors for CFC and HCFC that

 

 

 

react to chlorine do not function because

 

 

 

R410A contains no chlorine. Leak detector

 

 

 

for HFC134a can be used for R410A.

 

 

 

 

Flaring oil

Yes

No

For systems that use R22, apply mineral oil (Suniso oil)

 

 

 

to the flare nuts on the tubing to prevent refrigerant

 

 

 

leakage. For machines that use R407C or R410A, apply

 

 

 

synthetic oil (ether oil) to the flare nuts.

 

 

 

 

Manifold gauge

Vacuum pump

Outlet

Inlet

* Using tools for R22 and R407C and new tools for R410A together can cause defects.

4

Image 4
Contents R410A Models Indoor Units Outdoor UnitsOptional Controllers Gunma, Japan…In a Room …In Moist or Uneven Locations…In an Area with High Winds …In a Snowy Area for Heat Pump-type SystemsCheck of Density Limit Care regarding tubing Be sure to recharge the refrigerant only in liquid formDifferent tools required NewCompressor specifications are different Use R410A exclusive cylinder onlySingle-outlet valve Existing tubing cannot be used especially R22Contents HOW to Process Tubing AIR PurgingAir Purging with a Vacuum Pump for Test Run Preparation Test RUNGeneral Outdoor Unit Part name’ty Model 10 hp 16 hp1-Way Air Discharge Semi-Concealed 4-Way Air Discharge Semi-ConcealedConcealed Duct Ceiling-Mounted Concealed Duct High-Static PressureWall-Mounted Mark ContentsLength ft Tubing Size Main Tubing Size LA 10 Main Tubing Size After Distribution LB, LC11 Outdoor Unit Tubing Connection Size a BTU/h 28.0 45.0Straight Equivalent Length of Joints 13 Straight Equivalent Length of JointsAdditional Refrigerant Charge 16 Refrigerant Charge Amount at Shipment for outdoor unitWhen not using ball valve When using ball valveTube branching methods horizontal use Optional Distribution Joint Kits Model name Cooling capacity after distribution RemarksTubing size with thermal insulation Example232,000 BTU/h 68.0 kW Example Main tubing Distribution joint tubingMain tubing Selecting the Installation Site Indoor UnitFront view Side viewInstallation Space Outdoor UnitLeave space open above UnitPrecautions When Installing in Heavy Snow Areas Shield for Horizontal Exhaust DischargeUnit installation Air direction Front directionAir direction Suspending the Indoor Unit Placing the Unit Inside the Ceiling12, 18, 24 12, 18Installing the Drain Piping Be careful since the fan will Start when you short the pinOn the indoor control board Removing the corner cover Installing the Ceiling Panel Panel installation locations so that the panel isAttached tightly to the unit. Fig Check that the panel is attached tightly toWiring the Ceiling Panel Checking After Installation When Removing the Ceiling Panel for ServicingAdjusting the Auto Flap Special Remarks DC Fan Tap Change Procedure29/64 Full-scale Installation diagram Suspension lug 25/32 1 Installing the Drain Piping When you short the pin on the indoor Be careful since the fan will startControl board Bottom drain port is for use onlyElectrical Power Wiring Wiring connections WiringAppearance Part name AppearanceRemoving the intake grille Removing the side panelAdjust so that there is no gap Installing the side panel and intake grille Installing the intake grilleOther Check after installation If a wireless remote controller is used62 and -4 show the detailed dimensions of the indoor unit Type LengthSuspension bolts referring to the dimensional data on Previous page. -61 and TableTubing must be laid and connected inside the ceiling when Unit inside the ceilingDo not use adhesive at the drain connection port on Indoor unitDo not use the supplied drain hose bent at a 90 angle Maximum permissible bend isBe careful since the fan will start when you How to read the diagramShort the pin on the indoor control board Increasing the Fan SpeedThis air conditioner is usually installed above the ceiling Minimum space for installation and service is shownSo that the indoor unit and ducts are not visible. Only Air intake and air outlet ports are visible from belowEnough to suport the weight of the unit It is important that you use extreme careSupporting the indoor unit inside Ceiling. Ensure that the ceiling is strongIndoor Fan Performance How to Read the Diagram Service Refrigerant tubing drain hose positionWeight of the unit. Before Wall and ceiling side opening positionIt is important that you use Extreme care in supportingInside Shaping the Tubing Duct for Fresh AirRear outlet port How to carry out power supply wiring When removing the fasteningRegulations before wiring Bracket from the coverSelecting and Making a Hole Removing the Grille to Install the Indoor Unit If the Wall is Brick, Concrete or SimilarRemoving the grille Attaching the grilleInstalling the Drain Hose Shaping the Tubing Right-rear tubingLeft or left-rear tubing Unit are completedKHX0752 / 0952 / 1252 Installing the Outdoor Unit HOW to Install the Outdoor UnitTransporting Routing the Tubing Connect the Tubing Prepare the TubingRefrigerant tubing Connection method Supplied parts used? Refrigerant tube port Tightening torque for each capWork method Cap tightening torqueGeneral Precautions on Wiring Electrical WiringInter-outdoor unit control wiring Wiring System Diagram U, D, T TypeOutdoor unit Indoor unit How to connect wiring to the terminal For stranded wiring Shielded wire GroundGroundHOW to Process Tubing Connecting the Refrigerant Tubing Use of the Flaring MethodFlaring Procedure with a Flare Tool DeburringTube diameter Tightening torque Tube thickness Approximate 870 Lbs · inch Over 5/128 1000 1200 kgf · cmTwo tubes arranged together Three tubes arranged togetherInsulating the Refrigerant Tubing Tubing Insulation Insulation materialFinishing the Installation Taping the TubesBottom when you pressurize Air Purging with a Vacuum Pump for Test Run PreparationLeak test Use a manifold valve for air purgingEvacuation 45 min. or more 90 min. or moreCharging additional refrigerant Use a cylinder designed for use With R410A respectivelyFinishing the job Test RUN Test Run Procedure Items to Check Before the Test RunMain Outdoor Unit PCB Setting Indoor unit setting S004 Rotary switch, red Examples of the No. of outdoor units settings S0063P DIP switch, blue Address setting of main outdoor unit S007 Unit No. settingAutomatic Address Setting from the Outdoor Unit Auto Address Setting Basic wiring diagram ExampleCase 22-9 Case 2 Automatic Address Setting no compressor operation Automatic Address Setting from Outdoor UnitAutomatic Address Setting from Outdoor Unit Automatic Address Setting in Heating ModeCase 3A Automatic Address Setting* from the Remote Controller Automatic Address Setting in Cooling ModeCase 3B Display during automatic address setting On outdoor main unit PCBRemote Controller Test Run Settings If 1 indoor unit is connected to 1 remote controllerChecking the indoor unit addresses 07-007 W-2WAYIINA 1/23/07 609 PM Alarm contents Possible cause of malfunctionAlarm Alarm messages displayed on system controller Appendix Care and CleaningName of Parts Troubleshooting Should the power fail while the unit is runningLatch Air intake Safety chain Grille Bolt screws Tips for Energy SavingType 1-WAY Water drain Air outlet Air intake Ceiling panel optionalTroubleshooting Concealed Duct High-Static Pressure Type U, D Type Type standard static pressure Type high static pressureTroubleshooting Components and cause an electric shock hazard Air intake grille air intakeOr soot Type Wall-Mounted Tips for Energy Saving