Bosch Appliances D9412GV3 manual SDI RPS/Enhanced Communications Configuration, Path # Ack Wait

Page 135

D9412GV3/D7412GV3 Program Entry Guide 5.0 AUXPARM

EN 135

Example of Retry Count:

An acknowledgment of the heartbeat was not received within 10 sec. The control panel sends the next Heartbeat Poll after the first 10-sec ACK wait period expires. If the central station does not acknowledge this Heartbeat Poll, the control panel continues to re-send. When the resend count is reached, the control panel declares this path as failed (and generates the Comm Trouble ## Event). The control panel continues to re-send the Heartbeat Poll at the original poll rate time until it receives an acknowledgment, even after declaring a Comm Trouble.

When the control panel receives acknowledgment from the central station, the control panel returns to the normal Poll Rate (which, in this example, is 120 sec).

If more than one SDI Path is used, the control panel handles them on a successive basis. For example, if acknowledgment from SDI Path 1 is not received within 10 sec (using the previous example), the control panel moves to SDI Path 2 to send its Heartbeat Poll (and subsequently waits for the ack) before returning to SDI Path 1 to re-send its heartbeat.

If Heartbeat Polls are enabled to send by an SDI path, and the Path # Ack Wait time is exceeded, a COMM TRBL SDI ## event occurs. When this condition occurs, all events routed to this path go immediately to the backup path destination.

Entries are made in one-sec increments.

5 min = 300 sec

1 hour = 3600 sec

12 hours = 43,200 sec

18 hours = 64,800 sec

Path # Ack Wait

Default: 13

Selection: 5 sec to 65535 sec

5 to 65535 The control panel waits this amount of time to receive an acknowledgment from the central station.

Determines how long the control panel waits for an acknowledgment from the central station after a Heartbeat Poll or an actual event was transmitted. This prompt is applicable to SDI transmitted events and Heartbeat Polls. Entries are made in one-sec increments.

Path # Retry Count

Default: 5

Selection: 0 to 255

0COMM FAIL RG# SDI ### Events are not generated.

1to 255 COMM FAIL RG# SDI ### Events are generated after resending Heatbeat Poll the number of times selected for a given SDI path.

Determines how many times the control panel resends the Heartbeat Poll before declaring a path failure and generating a COMM FAIL RG# SDI ###

(RG # = 1 to 4, SDI ### = 88 for Path 1, 89 for Path 2, 90 for Path 3, 91 for Path 4) Event.

If using IP Addresses as the

communication means for UL 864 Commercial Fire applications, program this parameter as necessary.

The default settings meet or exceed the UL specifications.

5.5.1 Ant-Replay Security Feature

The Anti-Replay feature is always enabled in the control panel and must be supported by the central station receiver.

Anti-replay is a strategy that counters “replay” attacks. This feature prevents a malicious attack that substitutes a control panel or another network interface module (NIM) from delivering counterfeit events over a network in place of events sent by the actual control panel. A replay attack occurs when someone records a message sent over the network by Device A, and replays this message at a later time while pretending to be Device A.

5.6SDI RPS/Enhanced Communications Configuration

This section provides the necessary prompts for configuring the SDI-Network Interface Module (NIM) when using it for SDI RPS or SDI enhanced communication applications.

Supervise SDI 88

Default:

 

No

Selection:

 

Yes or No

Yes

 

Supervise the network interface

 

 

module (NIM) at SDI address 88.

 

 

Do not supervise the network

No

 

 

 

interface module (NIM) at SDI

 

 

address 88.

 

 

 

Bosch Security Systems, Inc. 10/11 F01U170807-02

Image 135
Contents D9412GV3/D7412GV3 v8.11 and Higher Type Styles Used in this Manual System RequirementsTable of Contents Tables 147Programming Prompts Directory 148 Document Name Part Number Using this Program Entry GuideDifferences between the D9412GV3 and D7412GV3 Features Literature ReferencedGuide to Programming Options D1255 Keypad Programming Menu and Page References D1260 Keypad Programming Menu and Page References Guide to UL 864 Programming Requirements D9412GV3/D7412GV3 Program Entry Guide 1.0 Introduction For Ground Fault Enable Switch UL 864 Programming Recommendations Prompt Possible SettingsRecommendation For SIA CP-01 Compliance Call Waiting Disable PhonePhone # D1260 D1255Phone # Format Default Modem IIIa2 Selection Modem IIIa2 or Contact IDDefault Yes Selection Yes or No Phone ParametersDtmf Dialing D6000 User IDs and ZonesModem IIIa2 Communication Format Data Point Numbers Two Phone Lines Alarm On FailPhone Supv Time Buzz on FailRoute Number Groups Which Has the Highest Priority? Default Selection Yes or NoExpand Test Report Called Party DisconnectRouting Destination Communication Failures Programming Primary and Backup DestinationsEnhanced Routing Programming a Duplicate Report# Primary Device Route GRP 1 4 optionRoute Group 1 4 option # Backup Device Burglar Reports Fire ReportsBurglar Reports Fire Reports Selections DescriptionSending Test Reports User ReportsTest Reports User Reports Selections DescriptionTest Reports Selections Description Diagnostics ReportsReport Selections Description Diagnostic ReportsRelay Reports Selections Report DescriptionRPS Reports Selections Report Description Auto Function ReportsRPS Reports Auto-Function Reports Selections Report DescriptionUser Change Reports Selections Description Point ReportsUser Chng Reports Point Reports Selections DescriptionAccess Reports Access Reports Selections Report DescriptionEvent Descriptions, Priorities, and Numbers Event Descriptions, Priorities, and Numbers Power Supervision Printer Parameters ## Fire Events ## Access Event## Scope ## A1 through A# in ScopeRPS Passcode RPS Parameters## Point Event ## Usr Chng EvtDefault Selection 0 to Log % FullContact RPS if Log % Full Answer Armed Default Refer to the program record sheet SelectionRPS Call Back RPS Line MonitorRPS Modem Speed Default Blank Selection Blank or up to 24 charactersDefault Selection 300, 1200 RPS Phone #Area Parameters MiscellaneousArea# Account Number # Force Arm/Bypass MaxArea On to Yes # Auto Watch # Delay Restorals# Exit Tone # Exit Dly Time# Duress Enable # Duress Enable must be set to YesVerify Time to 60 sec # Area Type Shared Area Arming Sequence Shared-Area Characteristics Arming a Shared AreaAccess Control Readers Assigned to the Shared Area Disarming a Shared Area# Burg Pattern # Fire Time# Fire Pattern # Burg Time# Single Ring # Bell TestRing # Account O/C # Fail to Open # Disable O/C in Window# Area O/C # Auto CloseExit Dly Time  If Disable O/C in Window is# Fail to Close # Restrictd O/C# Latest Close Time Default Selection 0000 toArming Features # Perimeter O/CD1255 Keypad Parameter Setup RequirementTo Early Ambush Timer on # Early Ambush# Exit Warning must be set to Yes # Exit Restart# Arm No Exit # Exit Warning# Entry Warning must be set to Yes Keypad Command Center# Entry Warning Cmd CenterCC# Area Assign CC# Enhanced Command CenterDefault Selection 1 to 32 on D9412GV3 1 to 8 on D7412GV3 CC# SupervisedCC# Scope CC# A1 through A# in ScopeSame A# Account Number, CC# Enter Key Relay CC# Enter Key Cycle DoorCC# Assign Door Trouble Tone to Yes CC# Trouble ToneCC# Entry Tone CC# Exit Tone## Passcode Arm CC# Arm Now WarningCC# Close Door CC# Passcode Follows ScopeCC# Abort Display CC# Cancel DisplayCC# Scroll Lock CC# Menu Key LockArea# Account Is On Area# Is OnArea# Not Ready Area# Is OffSee .9.2 Area Text on Custom FunctionCF### Text CF### Key StrokesExample User InterfaceMaster Arm Delay Master Arm InstantPerimeter Instant View Area Stat Perimeter DelayWatch Mode Perimeter PartialDoor Control Access Ctl LevelView Point Status Walk TestExtend Close Change Time/DateChange Passcode Del UserUnbypass a Point Bypass a PointPrint Log User CmdRemote Program Reset SensorsService Walk Change RelayFunction 128 through Default TextChange Skeds Invisible Walk Test## Disarm Default Selection 1 toDefault Refer to the program record sheet Selection Or E Authority Level## Master Arm Instant ## Master Arm Delay## Perimeter Delay ## Watch Mode## Fire Test ## View Memory## View Point Status ## Walk Test## Unlock Door ## Send Report## Door Control ## Cycle Door## Change Passcode ## Access Control Level## Change Display ## Change Time/Date## View Log ## Add User## Del User ## Extend Close## Change Relay ## Reset Sensors## Service Walk ## Bypass a Point## Default Text ## Change Skeds## Invisible Walk Test ## Area O/C ## C Function 128 through## Force Arm ## Passcode ArmDefault Refer to the program record sheet Selection C, or ## Disarm Level## Function Level Function List Menu Item## Function ## CC Address 1 through Relay ParametersArea Relays # Alarm Bell# Reset Sensors # Fire Bell# Force Armed # Fail to Close # Watch Mode# Area Fault # Area ArmedAC Failure # Perimeter Fault# Silent Alarm # Duress RelayPasscode or Token Worksheet User Group Window User GroupsPasscodes Passcode TamperUser passcode User token or card Reporting and Logging### User Group Default Selection 0, 1 toUser ### ### Passcode### SU1 through SU3 Site ### Name### Mstr Site ### Mstr Crd DataPoint Index Point Index## Type ## Type Description On next Program Point Response as Disarmed is YesApplications for Point Responses 9, D, and E Point ResponsesExample of Controlled point ## Entry Delay## Pt Response Hour Points## Audible After 2 Failures ## Ring Until Restored## Entry Tone Off ## Silent Bell## Invisible Point Regardless of the armed state . The buzz ## Buzz On FaultKeypad for any fault condition while the point Point Response## Local While Disarmed ## Watch Point## Relay Response Type ## Display as Device## Disable Restorals ## Local While Armed## Force Arm Returnable ## Bypass Returnable ## BypassableA# Auto Close prompt ## Cross Point ## Swinger Bypass## Report Bypass at Occurrence ## Defer Bypass Report## Alarm Verify ## Resettable## Fire Point Parameter Abort Window ## Alarm AbortPoint Number ### Point Index### Debounce ### Area Assign### Relay ### Point Text### Relay Codes/Relays CMD9 Relay CMD7 Point IndexCMD7 Relay CMD9 Point IndexWindows Window# Sunday # Thursday # Monday# Tuesday # Wednesday# Open Window Stop Default Selection Hhmm hours and minutesDisable O/C in Window is programmed Yes # Open Window StartProgramming to Link Two Days over Midnight # Close Early Begin# Close Window Stop # Close Window StartHoliday Indexes for O/C Windows # Xept Holiday# Holiday # Area 1 throughNormal Store Hours Opening and Closing Windows WorksheetMonthly Auditor’s Schedule User Windows #UW# User Group Delivery ScheduleUW# Monday UW# Group EnableUW# Group Disable UW# SundaySchedules Skeds Bypass Max setting ## Area 1through ### Point Number ## Relay Number prompt defines ## Relay NumberSelections Blank To 128 for D9412GV3 To 64 for D7412GV3Report ## Defer Test## Hourly Report If Expand Test Report in Phone## Cmd Center Cmd Center and Custom Func## Custom Func Sound Watch Tone at Command Center Keypad ThisAccess Control Level On This ## Access Ctl Level ### Door 1 through Default Selection To 24, 28 Access Control Level OffAccess Authority Events Unlock Door This functionDefault Selection To 24, 28 Access Authority Events No Entry Events OnNo Entry Events Off D9412GV3/D7412GV3 Program Entry Guide 4.0 Schedules Skeds ## Tuesday ## Time## Date ## MondayHoliday Index # Holiday Indexes## Holiday # DateSDI Automation Enable SDI AutoIntroduction RPS RequirementsStatus Rate SDI RPS ParametersEntered in RPS IP Address Configuration for RPS Over NetworkAnswer RPS Over Network RPS Address VerificationCommand 43, Remote Program Command 43 Flow Chart D1265 Default Selection 0.0.0.0 to RPS IP Address #RPS Port Number Enhanced Comm Path # IP AddressPath # Port Number  Path # Poll Rate is set to 120 sec Default Selection 0, 5 to 65535 secPath # Poll Rate Example of HeartbeatD1260 Poll Rate Timeline Path # Retry Count SDI RPS/Enhanced Communications ConfigurationDefault Selection 5 sec to 65535 sec Path # Ack WaitRoute Group Parameters Supervise SDIRG# Same Network Receiver Fire Supervision Restoral Type Early Ambush TimerFire Summary Sustain Secondary Ambush CodeRemote Warning Crystal Time AdjustPasscode Length Swinger CountEarly Armed Relay Default Disabled Selection Disabled or US CalendarCross Point Parameters Perimeter Relay# Entry Area # Door ProfileCross Point Time Door ## Door Point Default Selection To 127, 129 to 2470 to 75 on D7412GV3#CC#Scope # Custom Function# Interlock Point # Auto Door?# Fire Unlock? # Strike Time Strike Profile# Disarm on Open? # Card Type# RTE Shunt Only? # Buzz Time# Extend Time # Deactivate On Open?# No Entry? # Access Granted?Event Profile # REXShunt Only?# Exit Request? # Enter Request?Programming the Control Panels for SIA CP--01 Compliance SIA CP-01 Quick ReferenceRouting Power SupervisionPhone Phone ParametersKeypad Command Center Assignment50 Area Relays 101 Command 7 and Command 104140 145 143Bosch Security Systems, Inc Perinton Parkway Fairport, NY
Related manuals
Manual 76 pages 25.33 Kb

D9412GV3 specifications

The Bosch Appliances D9412GV3 is a perfect blend of functionality and innovation, designed to meet the needs of modern households. This dishwasher is part of Bosch's reputation for creating high-quality, energy-efficient home appliances. With a sleek design and advanced technology, the D9412GV3 stands out in the crowded market of dishwashers.

One of the main features of the D9412GV3 is its remarkable efficiency. With an Energy Star rating, this model is designed to minimize water and energy consumption while still delivering exceptional cleaning performance. The EcoSense technology optimizes water usage, ensuring every wash cycle is both effective and economical, making it a responsible choice for energy-conscious consumers.

The dishwasher offers a spacious interior, capable of accommodating large loads. Its flexible rack system includes adjustable tines and folding platforms, making it easy to fit various dish sizes, from pots and pans to delicate glassware. Additionally, the third rack feature provides extra space for utensils and smaller items, enhancing its capacity and versatility.

In terms of cleaning power, the D9412GV3 is equipped with the PrecisionWash system. This cutting-edge technology features intelligent sensors that continuously scan and check the load, adjusting the wash cycle as needed for optimal results. Coupled with the 40 dBA noise level, it ensures that the dishwasher operates quietly in the background, so you can enjoy your home without disruptive sounds.

Another standout characteristic is the PureDry technology, an integrated drying system that uses a condensation process to gently dry dishes without the need for extra heat. This not only protects sensitive items but also saves energy, further enhancing the appliance's eco-friendly nature.

Ease of use is a priority for Bosch, as seen in the D9412GV3's user-friendly controls. The intuitive interface allows for selecting various wash cycles and options, including Heavy, Auto, and Quick options, catering to different cleaning needs. Additionally, the Time Delay feature provides the flexibility to set the dishwasher to run at a later time, great for aligning with your schedule.

In summary, the Bosch D9412GV3 combines innovative technologies with a user-centered design to deliver a top-tier dishwasher experience. Its energy-efficient operation, spacious interior, and advanced cleaning features make it an excellent choice for any kitchen, ensuring spotless dishes with minimal effort. With Bosch's commitment to quality, the D9412GV3 stands as a reliable and stylish addition to any modern home.