Page 37

D9412GV3/D7412GV3 Program Entry Guide 2.0 Panel and Area Wide Parameters

EN 37

Area 1 must be enabled:

 System events such as power and phone supervision do not send a report correctly if Area 1 is disabled.

When programmed No, points assigned to this area do not generate events, show at the keypad when arming and disarming, or send status reports. All user authority in this area is turned off while the area is disabled.

To meet UL 864 requirements, set A#

Area On to Yes.

Area# Account Number

Default: 0000

Selection: For Modem and Contact ID (four- digit account numbers): 0000 to 9999,

BBBB to FFFF

For Modem (ten-digit account numbers): 0000000000 to 9999999999, BBBBBBBBBB to

FFFFFFFFFF

Determines the account number for this area. An account number must be assigned to each active area.

Account numbers are used to group areas together. Each area can have a different account number, or several areas can share the same account number. The control panel uses the account number as a reference for arming and keypad text displays.

Contact ID: Only the last four digits are sent.

Modem IIIa2: Enter a four-digit or ten-digit number.

Keypad Programming of Area # On and Area# Account Number

D1255

1.Refer to Figure 1 on page 7 to access Keypad Programming and navigate to the AREA PARAMETERS option. Press [ENT].

2.The keypad reads AREA NUM 1 – 32 (1 – 8 for the D7412GV3).

3.Enter the area number you wish to configure and press [ENT]. The current area status shows (for example, AREA 1 ON: YES).

4.Press [ENT] to change the area’s status.

5.Press the [PREV] or [NEXT] button to toggle between YES and NO, and then press [ENT] when the desired configuration option shows.

When the keypad reads PARAMETER SAVED, your selection is configured.

6.When the keypad reads AREA STATUS, press [NEXT] to advance to the A# ACCOUNT NUMBER option. The keypad shows the currently configured account number.

7.Press [ENT] to change the account number.

8.The [PREV] button acts as a [Backspace] key. The [COMMAND] key cycles though the special account number characters (B, C, D, E, F); [NEXT] select the account number character. Press [PREV] to delete the characters of the account number and then enter the new account number.

9.Press [ENT] to save the changes.

When the keypad reads Parameter Saved, your selection is configured.

D1260

1.Refer to Figure 2 on page 8 to access Keypad Programming and navigate to the Area Parameters option. Press [ENT].

2.The keypad reads Area Number 1 – 8.

3.Enter the area number you wish to configure and press [Enter]. The current area status shows (for example, Area 1 On: Yes).

4.Press the Edit softkey to change the area’s status.

5.Press the Yes or No softkey, and then press the Save softkey to save the changes.

When the keypad reads Parameter Saved, your selection is configured.

6.When the keypad reads Area Status, press the Account Number softkey. The keypad shows the currently configured account number.

7.Press the Edit softkey to change the account number.

8.Use the softkeys and the number buttons on the keypad to enter the new account number. The Backspace softkey allows you to erase characters. The Clear softkey allows you to clear the entire account number. When entering a letter character, press the letter's softkey to select it. The Previous and Next softkeys advance through the letter characters (A, B, C, D, E, F).

9.Press the Save softkey to save the changes.

When the keypad reads Parameter Saved, your selection is configured.

A# Force Arm/Bypass Max

Default: 1

Selection: 0 to 99

Specify the maximum number of combined Controlled points that can be faulted or bypassed when arming this area.

Bosch Security Systems, Inc. 10/11 F01U170807-02

Image 37
Contents D9412GV3/D7412GV3 v8.11 and Higher Type Styles Used in this Manual System RequirementsTable of Contents 147 TablesProgramming Prompts Directory 148 Differences between the D9412GV3 and D7412GV3 Features Using this Program Entry GuideLiterature Referenced Document Name Part NumberGuide to Programming Options D1255 Keypad Programming Menu and Page References D1260 Keypad Programming Menu and Page References Guide to UL 864 Programming Requirements D9412GV3/D7412GV3 Program Entry Guide 1.0 Introduction UL 864 Programming Recommendations Prompt Possible Settings For Ground Fault Enable SwitchRecommendation Phone For SIA CP-01 Compliance Call Waiting DisablePhone # D1260 D1255Default Yes Selection Yes or No Default Modem IIIa2 Selection Modem IIIa2 or Contact IDPhone Parameters Phone # FormatD6000 User IDs and Zones Dtmf DialingModem IIIa2 Communication Format Data Point Numbers Phone Supv Time Alarm On FailBuzz on Fail Two Phone LinesExpand Test Report Default Selection Yes or NoCalled Party Disconnect Route Number Groups Which Has the Highest Priority?Enhanced Routing Programming Primary and Backup DestinationsProgramming a Duplicate Report Routing Destination Communication FailuresRoute GRP 1 4 option # Primary DeviceRoute Group 1 4 option # Backup Device Burglar Reports Fire ReportsFire Reports Selections Description Burglar ReportsTest Reports User ReportsUser Reports Selections Description Sending Test ReportsTest Reports Selections Description Diagnostics ReportsRelay Reports Diagnostic ReportsSelections Report Description Report Selections DescriptionRPS Reports Auto Function ReportsAuto-Function Reports Selections Report Description RPS Reports Selections Report DescriptionUser Chng Reports Point ReportsPoint Reports Selections Description User Change Reports Selections DescriptionAccess Reports Selections Report Description Access ReportsEvent Descriptions, Priorities, and Numbers Event Descriptions, Priorities, and Numbers Power Supervision Printer Parameters ## Scope ## Access Event## A1 through A# in Scope ## Fire Events## Point Event RPS Parameters## Usr Chng Evt RPS PasscodeLog % Full Default Selection 0 toContact RPS if Log % Full RPS Call Back Default Refer to the program record sheet SelectionRPS Line Monitor Answer ArmedDefault Selection 300, 1200 Default Blank Selection Blank or up to 24 charactersRPS Phone # RPS Modem SpeedArea Parameters Miscellaneous# Force Arm/Bypass Max Area# Account NumberArea On to Yes # Exit Tone # Delay Restorals# Exit Dly Time # Auto Watch# Duress Enable must be set to Yes # Duress EnableVerify Time to 60 sec # Area Type Access Control Readers Assigned to the Shared Area Shared-Area Characteristics Arming a Shared AreaDisarming a Shared Area Shared Area Arming Sequence# Fire Pattern # Fire Time# Burg Time # Burg Pattern# Bell Test # Single RingRing # Account O/C # Area O/C # Disable O/C in Window# Auto Close # Fail to Open# Fail to Close  If Disable O/C in Window is# Restrictd O/C Exit Dly TimeArming Features Default Selection 0000 to# Perimeter O/C # Latest Close TimeTo Early Ambush Timer on Parameter Setup Requirement# Early Ambush D1255 Keypad# Arm No Exit # Exit Restart# Exit Warning # Exit Warning must be set to Yes# Entry Warning Keypad Command CenterCmd Center # Entry Warning must be set to YesDefault Selection 1 to 32 on D9412GV3 1 to 8 on D7412GV3 CC# Enhanced Command CenterCC# Supervised CC# Area AssignCC# A1 through A# in Scope CC# ScopeSame A# Account Number, CC# Enter Key Cycle Door CC# Enter Key RelayCC# Assign Door CC# Entry Tone CC# Trouble ToneCC# Exit Tone Trouble Tone to YesCC# Close Door CC# Arm Now WarningCC# Passcode Follows Scope ## Passcode ArmCC# Scroll Lock CC# Cancel DisplayCC# Menu Key Lock CC# Abort DisplayArea# Not Ready Area# Is OnArea# Is Off Area# Account Is OnCF### Text Custom FunctionCF### Key Strokes See .9.2 Area Text onExample User InterfaceMaster Arm Instant Master Arm DelayPerimeter Instant Watch Mode Perimeter DelayPerimeter Partial View Area StatView Point Status Access Ctl LevelWalk Test Door ControlChange Passcode Change Time/DateDel User Extend ClosePrint Log Bypass a PointUser Cmd Unbypass a PointService Walk Reset SensorsChange Relay Remote ProgramChange Skeds Default TextInvisible Walk Test Function 128 throughDefault Refer to the program record sheet Selection Or E Default Selection 1 toAuthority Level ## Disarm## Perimeter Delay ## Master Arm Delay## Watch Mode ## Master Arm Instant## View Point Status ## View Memory## Walk Test ## Fire Test## Door Control ## Send Report## Cycle Door ## Unlock Door## Change Display ## Access Control Level## Change Time/Date ## Change Passcode## Del User ## Add User## Extend Close ## View Log## Service Walk ## Reset Sensors## Bypass a Point ## Change Relay## Change Skeds ## Default Text## Invisible Walk Test ## Force Arm ## C Function 128 through## Passcode Arm ## Area O/C## Disarm Level Default Refer to the program record sheet Selection C, or## Function Level Menu Item Function List## Function ## CC Address 1 through Relay Parameters# Reset Sensors # Alarm Bell# Fire Bell Area Relays# Area Fault # Fail to Close # Watch Mode# Area Armed # Force Armed# Silent Alarm # Perimeter Fault# Duress Relay AC FailurePasscode or Token Worksheet Passcodes User GroupsPasscode Tamper User Group WindowUser passcode User token or card Reporting and LoggingUser ### Default Selection 0, 1 to### Passcode ### User Group### Mstr Site ### Name### Mstr Crd Data ### SU1 through SU3 SitePoint Index Point Index## Type ## Type Description On next Program Point Response as Disarmed is YesApplications for Point Responses 9, D, and E Point Responses## Pt Response ## Entry DelayHour Points Example of Controlled point## Entry Tone Off ## Ring Until Restored## Silent Bell ## Audible After 2 Failures## Invisible Point Keypad for any fault condition while the point ## Buzz On FaultPoint Response Regardless of the armed state . The buzz## Relay Response Type ## Watch Point## Display as Device ## Local While Disarmed## Local While Armed ## Disable Restorals## Force Arm Returnable ## Bypassable ## Bypass ReturnableA# Auto Close prompt ## Report Bypass at Occurrence ## Swinger Bypass## Defer Bypass Report ## Cross Point## Resettable ## Alarm Verify## Fire Point Point Number ## Alarm Abort### Point Index Parameter Abort Window### Debounce ### Area Assign### Point Text ### Relay### Relay Codes/Relays CMD7 Relay CMD7 Point IndexCMD9 Point Index CMD9 RelayWindow Windows# Sunday # Tuesday # Monday# Wednesday # ThursdayDisable O/C in Window is programmed Yes Default Selection Hhmm hours and minutes# Open Window Start # Open Window StopProgramming to Link Two Days over Midnight # Close Early Begin# Close Window Stop # Close Window Start# Holiday # Xept Holiday# Area 1 through Holiday Indexes for O/C WindowsNormal Store Hours Opening and Closing Windows WorksheetUW# User Group User Windows #Delivery Schedule Monthly Auditor’s ScheduleUW# Group Disable UW# Group EnableUW# Sunday UW# MondaySchedules Skeds ## Area 1through # Bypass Max setting## Point Number Selections Blank ## Relay NumberTo 128 for D9412GV3 To 64 for D7412GV3 ## Relay Number prompt defines## Hourly Report ## Defer TestIf Expand Test Report in Phone ReportCmd Center and Custom Func ## Cmd Center## Custom Func Access Control Level On This Command Center Keypad This## Access Ctl Level # Sound Watch Tone atAccess Authority Events Default Selection To 24, 28 Access Control Level OffUnlock Door This function ## Door 1 throughNo Entry Events On Default Selection To 24, 28 Access Authority EventsNo Entry Events Off D9412GV3/D7412GV3 Program Entry Guide 4.0 Schedules Skeds ## Date ## Time## Monday ## Tuesday## Holiday # Holiday IndexesDate Holiday Index #Introduction Enable SDI AutoRPS Requirements SDI AutomationStatus Rate SDI RPS ParametersAnswer RPS Over Network Configuration for RPS Over NetworkRPS Address Verification Entered in RPS IP AddressCommand 43, Remote Program Command 43 Flow Chart D1265 RPS IP Address # Default Selection 0.0.0.0 toRPS Port Number Path # IP Address Enhanced CommPath # Port Number Path # Poll Rate Default Selection 0, 5 to 65535 secExample of Heartbeat  Path # Poll Rate is set to 120 secD1260 Poll Rate Timeline Default Selection 5 sec to 65535 sec SDI RPS/Enhanced Communications ConfigurationPath # Ack Wait Path # Retry CountSupervise SDI Route Group ParametersRG# Same Network Receiver Fire Summary Sustain Early Ambush TimerSecondary Ambush Code Fire Supervision Restoral TypePasscode Length Crystal Time AdjustSwinger Count Remote WarningCross Point Parameters Default Disabled Selection Disabled or US CalendarPerimeter Relay Early Armed RelayCross Point Time Door ProfileDoor # # Entry Area ##CC#Scope Default Selection To 127, 129 to 2470 to 75 on D7412GV3# Custom Function # Door Point# Auto Door? # Interlock Point# Fire Unlock? # Disarm on Open? Strike Profile# Card Type # Strike Time# Extend Time # Buzz Time# Deactivate On Open? # RTE Shunt Only?Event Profile # Access Granted?# REXShunt Only? # No Entry?# Exit Request? # Enter Request?Programming the Control Panels for SIA CP--01 Compliance SIA CP-01 Quick ReferencePhone Power SupervisionPhone Parameters RoutingKeypad Command Center Assignment50 Area Relays 101 Command 7 and Command 104140 145 143Bosch Security Systems, Inc Perinton Parkway Fairport, NY
Related manuals
Manual 76 pages 25.33 Kb

D9412GV3 specifications

The Bosch Appliances D9412GV3 is a perfect blend of functionality and innovation, designed to meet the needs of modern households. This dishwasher is part of Bosch's reputation for creating high-quality, energy-efficient home appliances. With a sleek design and advanced technology, the D9412GV3 stands out in the crowded market of dishwashers.

One of the main features of the D9412GV3 is its remarkable efficiency. With an Energy Star rating, this model is designed to minimize water and energy consumption while still delivering exceptional cleaning performance. The EcoSense technology optimizes water usage, ensuring every wash cycle is both effective and economical, making it a responsible choice for energy-conscious consumers.

The dishwasher offers a spacious interior, capable of accommodating large loads. Its flexible rack system includes adjustable tines and folding platforms, making it easy to fit various dish sizes, from pots and pans to delicate glassware. Additionally, the third rack feature provides extra space for utensils and smaller items, enhancing its capacity and versatility.

In terms of cleaning power, the D9412GV3 is equipped with the PrecisionWash system. This cutting-edge technology features intelligent sensors that continuously scan and check the load, adjusting the wash cycle as needed for optimal results. Coupled with the 40 dBA noise level, it ensures that the dishwasher operates quietly in the background, so you can enjoy your home without disruptive sounds.

Another standout characteristic is the PureDry technology, an integrated drying system that uses a condensation process to gently dry dishes without the need for extra heat. This not only protects sensitive items but also saves energy, further enhancing the appliance's eco-friendly nature.

Ease of use is a priority for Bosch, as seen in the D9412GV3's user-friendly controls. The intuitive interface allows for selecting various wash cycles and options, including Heavy, Auto, and Quick options, catering to different cleaning needs. Additionally, the Time Delay feature provides the flexibility to set the dishwasher to run at a later time, great for aligning with your schedule.

In summary, the Bosch D9412GV3 combines innovative technologies with a user-centered design to deliver a top-tier dishwasher experience. Its energy-efficient operation, spacious interior, and advanced cleaning features make it an excellent choice for any kitchen, ensuring spotless dishes with minimal effort. With Bosch's commitment to quality, the D9412GV3 stands as a reliable and stylish addition to any modern home.