Bosch Appliances D9412GV3 manual CC# Supervised, CC# Enhanced Command Center, CC# Area Assign

Page 51

D9412GV3/D7412GV3 Program Entry Guide 2.0 Panel and Area Wide Parameters

EN 51

CC# Supervised

Default:

Refer to the program record sheet

Selection:

Yes or No

Yes

Only one keypad can be installed for this

 

CC SDI address.

 

 

No

More than one keypad can be installed

 

using this CC SDI address with the same

 

address DIP switch setting.

 

 

 

Supervise this SDI address and generate Trouble SDI Reports and local trouble annunciation if a problem occurs with this keypad or the SDI bus.

To meet UL 864 requirements, set CC# Supervised to Yes for the fire annunciation keypad.

Keypads that share the same address setting display the same text and emit the same tones, regardless of which keypad’s keys are pressed.

Trouble SDI # Reports are always reported as Area 1, Account 1 Events regardless of the area the SDI device is assigned.

When this prompt is Yes, you cannot have duplicate DIP switch settings.

CC# Enhanced Command Center

Default:

No

Selection:

Yes or No

Yes

This keypad is a D1260 Series

 

Keypad.

 

 

No

This keypad is not a D1260 Series

 

Keypad.

 

 

When a D1260 Series Keypad is installed at this keypad address, this item must be set to Yes.

Keypad Programming of CC# EnhancCMDCTR

D1255

1.Refer to Figure 1 on page 7 to access Keypad Programming and navigate to the COMMAND CENTER option.

2.Press [ENT]. The CC NUM 1 – 16 option shows.

3.Enter the keypad number you wish to configure and press [ENT]. The keypad reads CC# SCOPE, and then the current configuration (for example, PANEL WIDE).

4.Press [NEXT]. The current keypad type shows (for example, CC - 1 TYPE ENHANCED: YES).

5.Press [ENT] to change the keypad’s type.

6.Press [NEXT] or [PREV] to toggle to No to indicate that the D1255 is not an enhanced keypad, and then press [ENT] to save the changes.

When the keypad reads PARAMETER SAVED, your selection has been configured.

D1260

1.Refer to Figure 2 on page 8 to access Keypad Programming and navigate to the Command Center option.

2.Press [ENTER]. The CC Num 1 – 16 option shows.

3.Enter the keypad number you wish to configure and press [ENTER]. The keypad reads CC# Scope, and then the current configuration (for example, Panel Wide).

4.Press the Type softkey. The current keypad type shows (for example, CC (1) Type Enhanced: Yes).

5.Press the Edit softkey to change the keypad’s type.

6.Press the Yes or No softkey, and then press the Save softkey to save the changes.

When the keypad reads Parameter Saved, your selection has been configured.

Reboot the system to enable a D1260 Series Keypad.

To reboot the system, close and open the reset switch, labeled “S1 RESET,” located in the upper right corner of the control panel.

CC# Area Assign

Default: 1

Selection: 1 to 32 on D9412GV3 1 to 8 on D7412GV3

Enter the area number where you are installing this keypad or keypads with this address and the same DIP switch settings.

Bosch Security Systems, Inc. 10/11 F01U170807-02

Image 51
Contents D9412GV3/D7412GV3 v8.11 and Higher Type Styles Used in this Manual System RequirementsTable of Contents Tables 147Programming Prompts Directory 148 Document Name Part Number Using this Program Entry GuideDifferences between the D9412GV3 and D7412GV3 Features Literature ReferencedGuide to Programming Options D1255 Keypad Programming Menu and Page References D1260 Keypad Programming Menu and Page References Guide to UL 864 Programming Requirements D9412GV3/D7412GV3 Program Entry Guide 1.0 Introduction For Ground Fault Enable Switch UL 864 Programming Recommendations Prompt Possible SettingsRecommendation For SIA CP-01 Compliance Call Waiting Disable PhonePhone # D1260 D1255Phone # Format Default Modem IIIa2 Selection Modem IIIa2 or Contact IDDefault Yes Selection Yes or No Phone ParametersDtmf Dialing D6000 User IDs and ZonesModem IIIa2 Communication Format Data Point Numbers Two Phone Lines Alarm On FailPhone Supv Time Buzz on FailRoute Number Groups Which Has the Highest Priority? Default Selection Yes or NoExpand Test Report Called Party DisconnectRouting Destination Communication Failures Programming Primary and Backup DestinationsEnhanced Routing Programming a Duplicate Report# Primary Device Route GRP 1 4 optionRoute Group 1 4 option # Backup Device Burglar Reports Fire ReportsBurglar Reports Fire Reports Selections DescriptionSending Test Reports User ReportsTest Reports User Reports Selections DescriptionTest Reports Selections Description Diagnostics ReportsReport Selections Description Diagnostic ReportsRelay Reports Selections Report DescriptionRPS Reports Selections Report Description Auto Function ReportsRPS Reports Auto-Function Reports Selections Report DescriptionUser Change Reports Selections Description Point ReportsUser Chng Reports Point Reports Selections DescriptionAccess Reports Access Reports Selections Report DescriptionEvent Descriptions, Priorities, and Numbers Event Descriptions, Priorities, and Numbers Power Supervision Printer Parameters ## Fire Events ## Access Event## Scope ## A1 through A# in ScopeRPS Passcode RPS Parameters## Point Event ## Usr Chng EvtDefault Selection 0 to Log % FullContact RPS if Log % Full Answer Armed Default Refer to the program record sheet SelectionRPS Call Back RPS Line MonitorRPS Modem Speed Default Blank Selection Blank or up to 24 charactersDefault Selection 300, 1200 RPS Phone #Area Parameters MiscellaneousArea# Account Number # Force Arm/Bypass MaxArea On to Yes # Auto Watch # Delay Restorals# Exit Tone # Exit Dly Time# Duress Enable # Duress Enable must be set to YesVerify Time to 60 sec # Area Type Shared Area Arming Sequence Shared-Area Characteristics Arming a Shared AreaAccess Control Readers Assigned to the Shared Area Disarming a Shared Area# Burg Pattern # Fire Time# Fire Pattern # Burg Time# Single Ring # Bell TestRing # Account O/C # Fail to Open # Disable O/C in Window# Area O/C # Auto CloseExit Dly Time  If Disable O/C in Window is# Fail to Close # Restrictd O/C# Latest Close Time Default Selection 0000 toArming Features # Perimeter O/CD1255 Keypad Parameter Setup RequirementTo Early Ambush Timer on # Early Ambush# Exit Warning must be set to Yes # Exit Restart# Arm No Exit # Exit Warning# Entry Warning must be set to Yes Keypad Command Center# Entry Warning Cmd CenterCC# Area Assign CC# Enhanced Command CenterDefault Selection 1 to 32 on D9412GV3 1 to 8 on D7412GV3 CC# SupervisedCC# Scope CC# A1 through A# in ScopeSame A# Account Number, CC# Enter Key Relay CC# Enter Key Cycle DoorCC# Assign Door Trouble Tone to Yes CC# Trouble ToneCC# Entry Tone CC# Exit Tone## Passcode Arm CC# Arm Now WarningCC# Close Door CC# Passcode Follows ScopeCC# Abort Display CC# Cancel DisplayCC# Scroll Lock CC# Menu Key LockArea# Account Is On Area# Is OnArea# Not Ready Area# Is OffSee .9.2 Area Text on Custom FunctionCF### Text CF### Key StrokesExample User InterfaceMaster Arm Delay Master Arm InstantPerimeter Instant View Area Stat Perimeter DelayWatch Mode Perimeter PartialDoor Control Access Ctl LevelView Point Status Walk TestExtend Close Change Time/DateChange Passcode Del UserUnbypass a Point Bypass a PointPrint Log User CmdRemote Program Reset SensorsService Walk Change RelayFunction 128 through Default TextChange Skeds Invisible Walk Test## Disarm Default Selection 1 toDefault Refer to the program record sheet Selection Or E Authority Level## Master Arm Instant ## Master Arm Delay## Perimeter Delay ## Watch Mode## Fire Test ## View Memory## View Point Status ## Walk Test## Unlock Door ## Send Report## Door Control ## Cycle Door## Change Passcode ## Access Control Level## Change Display ## Change Time/Date## View Log ## Add User## Del User ## Extend Close## Change Relay ## Reset Sensors## Service Walk ## Bypass a Point## Default Text ## Change Skeds## Invisible Walk Test ## Area O/C ## C Function 128 through## Force Arm ## Passcode ArmDefault Refer to the program record sheet Selection C, or ## Disarm Level## Function Level Function List Menu Item## Function ## CC Address 1 through Relay ParametersArea Relays # Alarm Bell# Reset Sensors # Fire Bell# Force Armed # Fail to Close # Watch Mode# Area Fault # Area ArmedAC Failure # Perimeter Fault# Silent Alarm # Duress RelayPasscode or Token Worksheet User Group Window User GroupsPasscodes Passcode TamperUser passcode User token or card Reporting and Logging### User Group Default Selection 0, 1 toUser ### ### Passcode### SU1 through SU3 Site ### Name### Mstr Site ### Mstr Crd DataPoint Index Point Index## Type ## Type Description On next Program Point Response as Disarmed is YesApplications for Point Responses 9, D, and E Point ResponsesExample of Controlled point ## Entry Delay## Pt Response Hour Points## Audible After 2 Failures ## Ring Until Restored## Entry Tone Off ## Silent Bell## Invisible Point Regardless of the armed state . The buzz ## Buzz On FaultKeypad for any fault condition while the point Point Response## Local While Disarmed ## Watch Point## Relay Response Type ## Display as Device## Disable Restorals ## Local While Armed## Force Arm Returnable ## Bypass Returnable ## BypassableA# Auto Close prompt ## Cross Point ## Swinger Bypass## Report Bypass at Occurrence ## Defer Bypass Report## Alarm Verify ## Resettable## Fire Point Parameter Abort Window ## Alarm AbortPoint Number ### Point Index### Debounce ### Area Assign### Relay ### Point Text### Relay Codes/Relays CMD9 Relay CMD7 Point IndexCMD7 Relay CMD9 Point IndexWindows Window# Sunday # Thursday # Monday# Tuesday # Wednesday# Open Window Stop Default Selection Hhmm hours and minutesDisable O/C in Window is programmed Yes # Open Window StartProgramming to Link Two Days over Midnight # Close Early Begin# Close Window Stop # Close Window StartHoliday Indexes for O/C Windows # Xept Holiday# Holiday # Area 1 throughNormal Store Hours Opening and Closing Windows WorksheetMonthly Auditor’s Schedule User Windows #UW# User Group Delivery ScheduleUW# Monday UW# Group EnableUW# Group Disable UW# SundaySchedules Skeds Bypass Max setting ## Area 1through ### Point Number ## Relay Number prompt defines ## Relay NumberSelections Blank To 128 for D9412GV3 To 64 for D7412GV3Report ## Defer Test## Hourly Report If Expand Test Report in Phone## Cmd Center Cmd Center and Custom Func## Custom Func Sound Watch Tone at Command Center Keypad ThisAccess Control Level On This ## Access Ctl Level ### Door 1 through Default Selection To 24, 28 Access Control Level OffAccess Authority Events Unlock Door This functionDefault Selection To 24, 28 Access Authority Events No Entry Events OnNo Entry Events Off D9412GV3/D7412GV3 Program Entry Guide 4.0 Schedules Skeds ## Tuesday ## Time## Date ## MondayHoliday Index # Holiday Indexes## Holiday # DateSDI Automation Enable SDI AutoIntroduction RPS RequirementsStatus Rate SDI RPS ParametersEntered in RPS IP Address Configuration for RPS Over NetworkAnswer RPS Over Network RPS Address VerificationCommand 43, Remote Program Command 43 Flow Chart D1265 Default Selection 0.0.0.0 to RPS IP Address #RPS Port Number Enhanced Comm Path # IP AddressPath # Port Number  Path # Poll Rate is set to 120 sec Default Selection 0, 5 to 65535 secPath # Poll Rate Example of HeartbeatD1260 Poll Rate Timeline Path # Retry Count SDI RPS/Enhanced Communications ConfigurationDefault Selection 5 sec to 65535 sec Path # Ack WaitRoute Group Parameters Supervise SDIRG# Same Network Receiver Fire Supervision Restoral Type Early Ambush TimerFire Summary Sustain Secondary Ambush CodeRemote Warning Crystal Time AdjustPasscode Length Swinger CountEarly Armed Relay Default Disabled Selection Disabled or US CalendarCross Point Parameters Perimeter Relay# Entry Area # Door ProfileCross Point Time Door ## Door Point Default Selection To 127, 129 to 2470 to 75 on D7412GV3#CC#Scope # Custom Function# Interlock Point # Auto Door?# Fire Unlock? # Strike Time Strike Profile# Disarm on Open? # Card Type# RTE Shunt Only? # Buzz Time# Extend Time # Deactivate On Open?# No Entry? # Access Granted?Event Profile # REXShunt Only?# Exit Request? # Enter Request?Programming the Control Panels for SIA CP--01 Compliance SIA CP-01 Quick ReferenceRouting Power SupervisionPhone Phone ParametersKeypad Command Center Assignment50 Area Relays 101 Command 7 and Command 104140 145 143Bosch Security Systems, Inc Perinton Parkway Fairport, NY
Related manuals
Manual 76 pages 25.33 Kb

D9412GV3 specifications

The Bosch Appliances D9412GV3 is a perfect blend of functionality and innovation, designed to meet the needs of modern households. This dishwasher is part of Bosch's reputation for creating high-quality, energy-efficient home appliances. With a sleek design and advanced technology, the D9412GV3 stands out in the crowded market of dishwashers.

One of the main features of the D9412GV3 is its remarkable efficiency. With an Energy Star rating, this model is designed to minimize water and energy consumption while still delivering exceptional cleaning performance. The EcoSense technology optimizes water usage, ensuring every wash cycle is both effective and economical, making it a responsible choice for energy-conscious consumers.

The dishwasher offers a spacious interior, capable of accommodating large loads. Its flexible rack system includes adjustable tines and folding platforms, making it easy to fit various dish sizes, from pots and pans to delicate glassware. Additionally, the third rack feature provides extra space for utensils and smaller items, enhancing its capacity and versatility.

In terms of cleaning power, the D9412GV3 is equipped with the PrecisionWash system. This cutting-edge technology features intelligent sensors that continuously scan and check the load, adjusting the wash cycle as needed for optimal results. Coupled with the 40 dBA noise level, it ensures that the dishwasher operates quietly in the background, so you can enjoy your home without disruptive sounds.

Another standout characteristic is the PureDry technology, an integrated drying system that uses a condensation process to gently dry dishes without the need for extra heat. This not only protects sensitive items but also saves energy, further enhancing the appliance's eco-friendly nature.

Ease of use is a priority for Bosch, as seen in the D9412GV3's user-friendly controls. The intuitive interface allows for selecting various wash cycles and options, including Heavy, Auto, and Quick options, catering to different cleaning needs. Additionally, the Time Delay feature provides the flexibility to set the dishwasher to run at a later time, great for aligning with your schedule.

In summary, the Bosch D9412GV3 combines innovative technologies with a user-centered design to deliver a top-tier dishwasher experience. Its energy-efficient operation, spacious interior, and advanced cleaning features make it an excellent choice for any kitchen, ensuring spotless dishes with minimal effort. With Bosch's commitment to quality, the D9412GV3 stands as a reliable and stylish addition to any modern home.