Bosch Appliances D9412GV3 manual # Interlock Point, # Auto Door?, # Fire Unlock?

Page 142

D9412GV3/D7412GV3 Program Entry Guide 6.0 ACCESS CONTROL

EN 142

Door points must be programmed as Perimeter points. If a 24-hour point type is required for the Door point, you can use a Perimeter point type with a point response of 9 to C. Also, the debounce count must be set to 4 in Point Assignments.

When assigning Points 1 to 8 (control panel zones), the end-of-line (EOL) resistors must be removed from the control panel.

Also, do not enable any POPIT points (or OctoPOPIT points) sharing the same point number as the Door point. Failure to do so results in extra point trouble conditions upon reboot.

D# Interlock Point

Default:

Blank

Selection:

0 to 127, 129 to 247

 

(0 to 75 on the D7412GV3)

1 to 127,

The point number assigned to the

129 to 247

Interlock point. Points 128 and 248

 

are reserved by the control panel for

 

internal use.

0No point number is assigned to the Interlock point.

Enter the interlock point number. This point, when faulted, prevents the door controller from allowing access upon a valid ID read or door request.

Do not assign this point to another D# Door Point. You can, however, assign it to another controller to prevent multiple controllers from activating.

Door points must be programmed as Perimeter points. If a 24-hour point type is required for the Door point, you can use a Perimeter point type with a Point Response of 9 to C. Also, the debounce count must be set to 4 in Point Assignments.

The Interlock point is considered in a normal state if it is bypassed, swinger bypassed, or forced armed. This results in normal access even if the door remains open.

D# Auto Door?

Default:

No

Selection:

Yes or No

Yes

When the area assigned in D# Entry

 

Area # is disarmed, the door is in

 

the unlocked state. When that area

 

is armed, the door returns to the

 

locked state.

No

Door state is not affected by the

 

armed state of the area.

 

 

Use this program item to automatically unlock the door (latched, shunt, and strike) when the entry area is disarmed. The door re-locks upon Master or Perimeter Arming the area.

The unlocked state cannot be overridden manually.

D# Fire Unlock?

Default:

 

No

Selection:

 

Yes or No

Yes

 

Relay activates and shunt is applied

 

 

for the door contact automatically

 

 

upon a Fire Alarm.

 

 

Door remains in its current mode

No

 

 

 

upon a Fire Alarm.

 

 

 

Use this program item to activate the relay for the door strike and shunt the door zone automatically upon a Fire Alarm. This feature overrides a Secure Door state, Locked Door state, Auto Door, and an Interlock Faulted point. The relay activates for all doors with this prompt programmed as Yes when a Fire Alarm occurs in any area. Relays that are activated by Fire Unlock can be returned to normal only through the keypad using the Door Control function.

Doors that are activated by Fire Unlock must be returned to normal using the Door Control function on the keypad.

Bosch Security Systems, Inc. 10/11 F01U170807-02

Image 142
Contents D9412GV3/D7412GV3 v8.11 and Higher System Requirements Type Styles Used in this ManualTable of Contents 147 TablesProgramming Prompts Directory 148 Literature Referenced Using this Program Entry GuideDifferences between the D9412GV3 and D7412GV3 Features Document Name Part NumberGuide to Programming Options D1255 Keypad Programming Menu and Page References D1260 Keypad Programming Menu and Page References Guide to UL 864 Programming Requirements D9412GV3/D7412GV3 Program Entry Guide 1.0 Introduction UL 864 Programming Recommendations Prompt Possible Settings For Ground Fault Enable SwitchRecommendation Phone For SIA CP-01 Compliance Call Waiting DisablePhone # D1255 D1260Phone Parameters Default Modem IIIa2 Selection Modem IIIa2 or Contact IDDefault Yes Selection Yes or No Phone # FormatD6000 User IDs and Zones Dtmf DialingModem IIIa2 Communication Format Data Point Numbers Buzz on Fail Alarm On FailPhone Supv Time Two Phone LinesCalled Party Disconnect Default Selection Yes or NoExpand Test Report Route Number Groups Which Has the Highest Priority?Programming a Duplicate Report Programming Primary and Backup DestinationsEnhanced Routing Routing Destination Communication FailuresRoute GRP 1 4 option # Primary DeviceRoute Group 1 4 option # Backup Device Fire Reports Selections Description Fire ReportsBurglar Reports Burglar ReportsUser Reports Selections Description User ReportsTest Reports Sending Test ReportsDiagnostics Reports Test Reports Selections DescriptionSelections Report Description Diagnostic ReportsRelay Reports Report Selections DescriptionAuto-Function Reports Selections Report Description Auto Function ReportsRPS Reports RPS Reports Selections Report DescriptionPoint Reports Selections Description Point ReportsUser Chng Reports User Change Reports Selections DescriptionAccess Reports Selections Report Description Access ReportsEvent Descriptions, Priorities, and Numbers Event Descriptions, Priorities, and Numbers Power Supervision Printer Parameters ## A1 through A# in Scope ## Access Event## Scope ## Fire Events## Usr Chng Evt RPS Parameters## Point Event RPS PasscodeLog % Full Default Selection 0 toContact RPS if Log % Full RPS Line Monitor Default Refer to the program record sheet SelectionRPS Call Back Answer ArmedRPS Phone # Default Blank Selection Blank or up to 24 charactersDefault Selection 300, 1200 RPS Modem SpeedMiscellaneous Area Parameters# Force Arm/Bypass Max Area# Account NumberArea On to Yes # Exit Dly Time # Delay Restorals# Exit Tone # Auto Watch# Duress Enable must be set to Yes # Duress EnableVerify Time to 60 sec # Area Type Disarming a Shared Area Shared-Area Characteristics Arming a Shared AreaAccess Control Readers Assigned to the Shared Area Shared Area Arming Sequence# Burg Time # Fire Time# Fire Pattern # Burg Pattern# Bell Test # Single RingRing # Account O/C # Auto Close # Disable O/C in Window# Area O/C # Fail to Open# Restrictd O/C  If Disable O/C in Window is# Fail to Close Exit Dly Time# Perimeter O/C Default Selection 0000 toArming Features # Latest Close Time# Early Ambush Parameter Setup RequirementTo Early Ambush Timer on D1255 Keypad# Exit Warning # Exit Restart# Arm No Exit # Exit Warning must be set to YesCmd Center Keypad Command Center# Entry Warning # Entry Warning must be set to YesCC# Supervised CC# Enhanced Command CenterDefault Selection 1 to 32 on D9412GV3 1 to 8 on D7412GV3 CC# Area AssignCC# A1 through A# in Scope CC# ScopeSame A# Account Number, CC# Enter Key Cycle Door CC# Enter Key RelayCC# Assign Door CC# Exit Tone CC# Trouble ToneCC# Entry Tone Trouble Tone to YesCC# Passcode Follows Scope CC# Arm Now WarningCC# Close Door ## Passcode ArmCC# Menu Key Lock CC# Cancel DisplayCC# Scroll Lock CC# Abort DisplayArea# Is Off Area# Is OnArea# Not Ready Area# Account Is OnCF### Key Strokes Custom FunctionCF### Text See .9.2 Area Text onUser Interface ExampleMaster Arm Instant Master Arm DelayPerimeter Instant Perimeter Partial Perimeter DelayWatch Mode View Area StatWalk Test Access Ctl LevelView Point Status Door ControlDel User Change Time/DateChange Passcode Extend CloseUser Cmd Bypass a PointPrint Log Unbypass a PointChange Relay Reset SensorsService Walk Remote ProgramInvisible Walk Test Default TextChange Skeds Function 128 throughAuthority Level Default Selection 1 toDefault Refer to the program record sheet Selection Or E ## Disarm## Watch Mode ## Master Arm Delay## Perimeter Delay ## Master Arm Instant## Walk Test ## View Memory## View Point Status ## Fire Test## Cycle Door ## Send Report## Door Control ## Unlock Door## Change Time/Date ## Access Control Level## Change Display ## Change Passcode## Extend Close ## Add User## Del User ## View Log## Bypass a Point ## Reset Sensors## Service Walk ## Change Relay## Change Skeds ## Default Text## Invisible Walk Test ## Passcode Arm ## C Function 128 through## Force Arm ## Area O/C## Disarm Level Default Refer to the program record sheet Selection C, or## Function Level Menu Item Function List## Function Relay Parameters ## CC Address 1 through# Fire Bell # Alarm Bell# Reset Sensors Area Relays# Area Armed # Fail to Close # Watch Mode# Area Fault # Force Armed# Duress Relay # Perimeter Fault# Silent Alarm AC FailurePasscode or Token Worksheet Passcode Tamper User GroupsPasscodes User Group WindowReporting and Logging User passcode User token or card### Passcode Default Selection 0, 1 toUser ### ### User Group### Mstr Crd Data ### Name### Mstr Site ### SU1 through SU3 SitePoint Index Point Index## Type ## Type Description On next Disarmed is Yes Program Point Response asPoint Responses Applications for Point Responses 9, D, and EHour Points ## Entry Delay## Pt Response Example of Controlled point## Silent Bell ## Ring Until Restored## Entry Tone Off ## Audible After 2 Failures## Invisible Point Point Response ## Buzz On FaultKeypad for any fault condition while the point Regardless of the armed state . The buzz## Display as Device ## Watch Point## Relay Response Type ## Local While Disarmed## Local While Armed ## Disable Restorals## Force Arm Returnable ## Bypassable ## Bypass ReturnableA# Auto Close prompt ## Defer Bypass Report ## Swinger Bypass## Report Bypass at Occurrence ## Cross Point## Resettable ## Alarm Verify## Fire Point ### Point Index ## Alarm AbortPoint Number Parameter Abort Window### Area Assign ### Debounce### Point Text ### Relay### Relay Codes/Relays CMD9 Point Index CMD7 Point IndexCMD7 Relay CMD9 RelayWindow Windows# Sunday # Wednesday # Monday# Tuesday # Thursday# Open Window Start Default Selection Hhmm hours and minutesDisable O/C in Window is programmed Yes # Open Window Stop# Close Early Begin Programming to Link Two Days over Midnight# Close Window Start # Close Window Stop# Area 1 through # Xept Holiday# Holiday Holiday Indexes for O/C WindowsOpening and Closing Windows Worksheet Normal Store HoursDelivery Schedule User Windows #UW# User Group Monthly Auditor’s ScheduleUW# Sunday UW# Group EnableUW# Group Disable UW# MondaySchedules Skeds ## Area 1through # Bypass Max setting## Point Number To 128 for D9412GV3 To 64 for D7412GV3 ## Relay NumberSelections Blank ## Relay Number prompt definesIf Expand Test Report in Phone ## Defer Test## Hourly Report ReportCmd Center and Custom Func ## Cmd Center## Custom Func ## Access Ctl Level # Command Center Keypad ThisAccess Control Level On This Sound Watch Tone atUnlock Door This function Default Selection To 24, 28 Access Control Level OffAccess Authority Events ## Door 1 throughNo Entry Events On Default Selection To 24, 28 Access Authority EventsNo Entry Events Off D9412GV3/D7412GV3 Program Entry Guide 4.0 Schedules Skeds ## Monday ## Time## Date ## TuesdayDate Holiday Indexes## Holiday # Holiday Index #RPS Requirements Enable SDI AutoIntroduction SDI AutomationSDI RPS Parameters Status RateRPS Address Verification Configuration for RPS Over NetworkAnswer RPS Over Network Entered in RPS IP AddressCommand 43, Remote Program Command 43 Flow Chart D1265 RPS IP Address # Default Selection 0.0.0.0 toRPS Port Number Path # IP Address Enhanced CommPath # Port Number Example of Heartbeat Default Selection 0, 5 to 65535 secPath # Poll Rate  Path # Poll Rate is set to 120 secD1260 Poll Rate Timeline Path # Ack Wait SDI RPS/Enhanced Communications ConfigurationDefault Selection 5 sec to 65535 sec Path # Retry CountSupervise SDI Route Group ParametersRG# Same Network Receiver Secondary Ambush Code Early Ambush TimerFire Summary Sustain Fire Supervision Restoral TypeSwinger Count Crystal Time AdjustPasscode Length Remote WarningPerimeter Relay Default Disabled Selection Disabled or US CalendarCross Point Parameters Early Armed RelayDoor # Door ProfileCross Point Time # Entry Area ## Custom Function Default Selection To 127, 129 to 2470 to 75 on D7412GV3#CC#Scope # Door Point# Auto Door? # Interlock Point# Fire Unlock? # Card Type Strike Profile# Disarm on Open? # Strike Time# Deactivate On Open? # Buzz Time# Extend Time # RTE Shunt Only?# REXShunt Only? # Access Granted?Event Profile # No Entry?# Enter Request? # Exit Request?SIA CP-01 Quick Reference Programming the Control Panels for SIA CP--01 CompliancePhone Parameters Power SupervisionPhone RoutingKeypad Command Center Assignment50 Area Relays Command 7 and Command 104 101140 143 145Bosch Security Systems, Inc Perinton Parkway Fairport, NY
Related manuals
Manual 76 pages 25.33 Kb

D9412GV3 specifications

The Bosch Appliances D9412GV3 is a perfect blend of functionality and innovation, designed to meet the needs of modern households. This dishwasher is part of Bosch's reputation for creating high-quality, energy-efficient home appliances. With a sleek design and advanced technology, the D9412GV3 stands out in the crowded market of dishwashers.

One of the main features of the D9412GV3 is its remarkable efficiency. With an Energy Star rating, this model is designed to minimize water and energy consumption while still delivering exceptional cleaning performance. The EcoSense technology optimizes water usage, ensuring every wash cycle is both effective and economical, making it a responsible choice for energy-conscious consumers.

The dishwasher offers a spacious interior, capable of accommodating large loads. Its flexible rack system includes adjustable tines and folding platforms, making it easy to fit various dish sizes, from pots and pans to delicate glassware. Additionally, the third rack feature provides extra space for utensils and smaller items, enhancing its capacity and versatility.

In terms of cleaning power, the D9412GV3 is equipped with the PrecisionWash system. This cutting-edge technology features intelligent sensors that continuously scan and check the load, adjusting the wash cycle as needed for optimal results. Coupled with the 40 dBA noise level, it ensures that the dishwasher operates quietly in the background, so you can enjoy your home without disruptive sounds.

Another standout characteristic is the PureDry technology, an integrated drying system that uses a condensation process to gently dry dishes without the need for extra heat. This not only protects sensitive items but also saves energy, further enhancing the appliance's eco-friendly nature.

Ease of use is a priority for Bosch, as seen in the D9412GV3's user-friendly controls. The intuitive interface allows for selecting various wash cycles and options, including Heavy, Auto, and Quick options, catering to different cleaning needs. Additionally, the Time Delay feature provides the flexibility to set the dishwasher to run at a later time, great for aligning with your schedule.

In summary, the Bosch D9412GV3 combines innovative technologies with a user-centered design to deliver a top-tier dishwasher experience. Its energy-efficient operation, spacious interior, and advanced cleaning features make it an excellent choice for any kitchen, ensuring spotless dishes with minimal effort. With Bosch's commitment to quality, the D9412GV3 stands as a reliable and stylish addition to any modern home.