Battery Maintenance

Installing a New Battery Pack

To install a new battery pack, reverse the steps in “Removing the Battery Pack,” in this chapter.

Testing the New Battery Pack

After installing the new battery pack, press the Test/Alarm Reset button. For information on initiating a self-test, refer to the section, “Initiating a Self-Test,” in Chapter 2.

IMPORTANT: The UPS will not execute a self-test until the batteries are 90 percent charged.

If the installation has been successful, the Bad Battery/Low Battery LED is not illuminated.

If the installation has not been successful, the Bad Battery/Low Battery LED illuminates red. If this occurs, remove and reinstall the battery pack, and check the battery terminal connections. If the Bad Battery/Low Battery LED is still red, refer to Chapter 5, “Troubleshooting.”

IMPORTANT: The batteries charge to 90 percent of their capacity within less than 3 hours. Allow the batteries to charge for 24 hours before using the UPS to supply backup power to devices. The load may not be fully protected for 24 hours.

Disposing of Used Batteries

The spare battery kit includes the instructions and packaging required to return used batteries to the appropriate location for disposal.

Do not dispose of used batteries with general office or household waste. Return the used pack for proper disposal to either:

HP, authorized HP Partners, or their agents

A recycling center that meets all local environmental standards

4-6

HP Uninterruptible Power System R1500 XR Models User Guide

Image 34
Contents HP Uninterruptible Power System R1500 XR Models User Guide Page Contents Chapter Troubleshooting Appendix B Electrostatic Discharge Page About This Guide Important Safety InformationSymbols on Equipment Audience AssumptionsRack Stability Symbols in TextRelated Documents Technical Support Getting HelpReader’s Comments HP Website Authorized ResellerOverview Standard UPS FeaturesCommunications Port Overcurrent Protection UPS R1500 XR ModelsNetwork Transient Protector UPS R1500 XR ModelsFront panel configuration Front PanelRear Panels Rear panel of R1500 XR NARear panel of R1500 XR JPN Rear panel of R1500 XR H INT’L Hardware Options Power Management SoftwareUPS Hardware Options Option Part Number$25,000 Computer Load Protection Guarantee Remote Emergency Power Off PortWarranties Pre-Failure Battery Warranty Operation Front Panel Controls and LED IndicatorsDescription Meaning/Function Modes of Operation LEDPlacing the UPS in Operate Mode Charging the BatteriesReturning to Standby Mode Placing the UPS in Standby modeTest/Alarm Reset button Initiating a Self-TestSilencing an Audible Alarm Audible AlarmsShutting Down the System Configuration Placing the UPS in Configure ModeConfiguration Parameters Configuration ParametersParameter LED Parameter Name Explanation when illuminated Changing Configuration Parameters Available Voltage SettingsConfiguration Precautions Battery MaintenanceCharging Batteries Determining When to Replace Batteries Obtaining New BatteriesReplacing Batteries Removing the Battery PackPreparing the UPS Remove the two screws to obtain access to the battery pack Disconnecting the battery cable from the circuit board Testing the New Battery Pack Installing a New Battery PackDisposing of Used Batteries Care and Storage of Batteries Troubleshooting TroubleshootingTroubleshooting Symptom Possible Cause Suggested ActionTroubleshooting Troubleshooting Repairing the UPS Federal Communications Commission Notice Regulatory Compliance NoticesRegulatory Compliance Identification Numbers Class a EquipmentClass B Equipment ModificationsEuropean Union Notice Canadian Notice Avis CanadienCables Japanese Notice China Taiwan Notice Battery Replacement Notice Electrostatic Discharge Grounding MethodsTable C-1 Physical Specifications SpecificationsPhysical Specifications Feature MetricInput Specifications Table C-2 Input SpecificationsTable C-3 Output Specifications Output SpecificationsTable C-4 Output Specifications Table C-5 Battery Specifications Battery SpecificationsEnvironmental Specifications Table C-6 Environmental SpecificationsIndex Index-2 Index-3