Specifications
Input Specifications
Table C-2: Input Specifications
|
| Default | Available |
| |
|
| Settings |
| ||
| Utility Voltage | Settings | Power Cord | ||
UPS Model | Nominal | ||||
Frequency (Hz) | Utility Voltage | Supplied | |||
| Voltage | ||||
|
| (VAC) |
| ||
|
| (VAC) |
| ||
|
|
|
| ||
|
|
|
|
| |
R1500 XR NA | 50/60 | 120 | 110, 120, 1271 | ||
|
|
|
| power cord with | |
|
|
|
| NEMA | |
|
|
|
|
| |
R1500 XR JPN | 50/60 | 100 | 1002 | ||
|
|
|
| power cord with | |
|
|
|
| NEMA | |
|
|
|
|
| |
R1500 XR H INT’L | 50/60 | 230 | 220, 230, 240 | Input power | |
|
|
|
| receptacle | |
|
|
|
|
Note: 1 120 on battery
2110 on battery
Before connecting devices, verify that the UPS will not overload by checking that the rating of the devices does not exceed the capacity of the UPS. Evenly distribute connected devices throughout all load segments. Do not exceed the rating of individual receptacles. Connect devices according to shutdown preference.
After checking that the UPS will not overload, connect the power cords from the devices to the appropriate output receptacles of the UPS.
WARNING: To prevent risk of personal injury from electric shock, the
UPS R1500 XR H INT’L model is not suitable for installation where the total earth (ground) conductor leakage current for all connected devices exceeds 3.5 mA. Use RackBuilder Pro (obtainable at www.hp.com) to find the total system leakage current.
HP Uninterruptible Power System R1500 XR Models User Guide |