HP Performance Optimized Data Center (POD) 40c manual Fire protection system, EPO modes

Page 18

Item

Component

Indicator color

Description

 

 

 

 

7

EPO mode

Key control

Enables you to select the EPO mode:

 

 

 

Armed

 

 

 

Test

 

 

 

Bypass

 

 

 

For more information, see "EPO modes (on

 

 

 

page 18)."

 

 

 

 

8

EPO reset

White button

Resets the EPO system when pressed

EPO modes

The EPO system has three operating modes:

Armed—The EPO system is armed and operational.

Test—The EPO system is in test mode and does not initiate during events that normally trigger an EPO.

Bypass—The EPO system is non-operational and does not initiate during events that normally trigger an EPO.

EPO accidental activation

To help prevent accidentally pressing the EPO button and activating the EPO system, each EPO button is covered with a clear Lexan cover.

Battery backup during an EPO event

The following components are equipped with a UPS to ensure that service is not interrupted during a loss of power to the HP POD 40c G2:

ECS system

VESDA air sampling smoke detection system

Optional fire suppression system

Emergency lighting in the HP POD 40c G2

Fire protection system

Each HP POD 40c G2 is equipped with a fire alarm panel that is integrated with the fire detection system and the optional fire suppression system.

The fire system is designed as a stand-alone system, but can also interface with customer site fire alarm systems. Customer site connections are the responsibility of the customer. Consult with HP for connection locations.

The fire protection system includes:

Manual fire pulls (on page 19)

Fire alarm indicators (on page 19)

VESDA air sampling smoke detection system (on page 19)

(Optional) Fire suppression system (on page 20)

Life safety systems 18

Image 18
Contents HP Performance Optimized Datacenter 40c G2 User Guide Part Number August EditionPage Contents Fire protection system Humidifier Controlled access HP POD 40c G2 lightingNetworking Connection portals Demarcation box Fire box Regulatory compliance notices Before you contact HP HP contact informationOverview Operator safetyComponent safety Before you beginFire detection and suppression Environmental considerationsComponent identification Structural component identificationParts and part number identification Life safety component identification Internal life safety componentsTop view shown Component Description Electrical power component identification Front view shown Component DescriptionComponent Description Internal panel labelsFront view shown Electrical safety label Description Control cabinet component identification HP POD 40c G2 racksHP POD 40c G2 contains a total of 20 IT racks Component identification Life safety systems Life safety overviewEPO system ECS touchscreen and EPO indicators Fire protection system Battery backup during an EPO eventComponent Indicator color Description EPO modesFire alarm indicators Manual fire pullsVesda air sampling smoke detection system Optional Fire suppression system Fire system operator panelEmergency egress Fire suppression sequence of operationsSite electrical system Power, electrical, and controlsPower safety GroundingLightning protection Capacities Power feedersFeature Specification Electrical and mechanical cooling capacitiesElectrical panels Arc flash safety Power distribution Electrical busway systemWire color code Panel schedulesControl cabinet power components Electrical buswaysPower, electrical, and controls Drop boxes Power configurations Rack powerHP POD 40c G2 lighting Power, electrical, and controls Using the ECS Environmental control systemEnvironmental control system overview Satellite control boxes SensorsTop view shown Sensor Quantity Description Connecting to the ECS Facility connections to ECSConfiguring the ECS Managing the ECS from the HP POD 40c G2Environmental control system Logging in remotely to the ECS Locating the ECS IP addresses Click ConnectPassword protection Navigating the ECS interfaceController Settings screen on Icon name DescriptionOverview screen Information Description Basic System Configuration screen Status Overview screenConfiguring the cold aisle temperature alarm parameters Configuring the hot aisle temperature alarm parameters Current temperature parameters appear on the related buttons Advanced System Configuration screen Setting the dimensions of the ECSEnvironmental control system Calibrating the flowmeter Enable/disable power management Controller Settings screen ECS alarms 40c G2 Maintenance and Service Guide orSafety and security alarms Fire alarm sequence of operationsAlarm Meaning Solution Water supply temperature Cooling systemHP POD 40c G2 cooling system theory of operation Water quality requirements and specifications Cooling system components Fans Side view shown Component DescriptionCondensation management DrainsLeak detection IT networking and communications NetworkingConnection portals Demarcation box Fire boxConnection portal Connection point Quantity Diameter IT networking and communications Controlled access Optional componentsHumidifier Standard power up checklist Power up procedureStandard HP POD 40c G2 power up procedure Standard power up procedureSite chilled water Cold weather HP POD 40c G2 power up procedureSite electrical ECS and EPOCold weather power up checklist Cold weather power up procedurePOD heating procedure Power down procedure Electrical specifications SpecificationsGeneral HP POD 40c G2 specifications Features SpecificationsWater specifications Rack specificationsEnvironmental specifications Standard HP POD 40c G2 racks AT978A Feature Specification29ºC to 54ºC -20ºF to 130ºF Maintenance Periodic maintenanceSample HP POD 40c G2 maintenance schedule Contacting HP Before you contact HPHP contact information Safety and NEC compliance Regulatory compliance noticesHP POD 40c G2 regulatory compliance Modifications Regulatory compliance identification numbersFederal Communications Commission notice CablesRegulatory requirements for Exit signs Glossary Enclosure of sufficient size to enable entry of personnel Programmable logic controllerPersonal protective equipment Uninterruptible power system Documentation feedback ECS, configuring ECS, logging in to IndexWater quality 57 water temperature 56 wire color code
Related manuals
Manual 41 pages 46.35 Kb

Performance Optimized Data Center (POD) 40c specifications

The HP Performance Optimized Data Center (POD) 40c is a state-of-the-art data center solution designed to meet the increasing demands for efficiency, scalability, and flexibility in enterprise environments. Aimed at delivering high-performance computing with minimal environmental impact, the POD 40c integrates innovative technologies and features to optimize operations.

One of the standout characteristics of the POD 40c is its modular design, allowing for easy deployment and scalability. Customers can configure their data center according to specific requirements, enabling rapid expansion as business needs evolve. The POD can house up to 240 servers, providing ample capacity to support intensive workloads while ensuring that users can quickly adapt to changing technological landscapes.

The energy efficiency of the POD 40c is a significant highlight. By employing advanced cooling technologies, including hot aisle/cold aisle containment and direct expansion cooling, it minimizes energy consumption while maintaining optimal temperatures for hardware components. This focus on efficiency also extends to power management, with redundant power supplies and the integration of high-efficiency power distribution units (PDUs) that help reduce operational costs.

In terms of connectivity, the HP POD 40c is equipped with comprehensive networking capabilities. The design includes integrated cabling systems that ensure organized and efficient routing of power and data. This dedication to streamlined connectivity facilitates faster data transfer rates and decreases latency, enhancing overall system performance.

Moreover, security is a paramount consideration in the POD 40c design. The unit incorporates various security features, including access controls, environmental monitoring, and surveillance options, which provide peace of mind for data-sensitive businesses. These elements work together to ensure that critical data remains protected from unauthorized access and environmental threats.

Sustainability is another key aspect, as the POD 40c is designed to be environmentally friendly. The system's effective cooling mechanisms and efficient power usage contribute to reduced carbon emissions, aligning with corporate sustainability goals and industry regulations.

In conclusion, the HP Performance Optimized Data Center (POD) 40c represents a cutting-edge solution for modern data center requirements. Its modularity, energy efficiency, robust connectivity, enhanced security, and sustainability make it an attractive option for organizations aiming to optimize their IT infrastructure while maintaining agility in a rapidly evolving digital landscape. The POD 40c exemplifies HP's commitment to providing innovative and performance-driven data center solutions, positioning it as a transformative asset for businesses seeking to thrive in a data-driven world.