HP Performance Optimized Data Center (POD) 40c manual Cooling system, Water supply temperature

Page 56

Cooling system

HP POD 40c G2 cooling system theory of operation

CAUTION: Using contaminated supply water can cause decreased cooling capacity or disruption in service. The supply water must meet the guidelines stated in the HP Performance Optimized Datacenter 40c G2 Site Preparation and Requirements Guide. Damage caused by contaminated supply water is not covered by the warranty.

The HP POD 40c G2 has 12 heat exchangers configured into 6 zones that maintain temperature and cool the equipment installed in the HP POD 40c G2. The HP POD 40c G2 receives chilled water from your facility, cycles the water through the heat exchangers to cool the air, and then the fans circulate the cool air throughout the HP POD 40c G2.

A predetermined differential pressure setpoint between the hot aisle and the cold aisle is factory set. Do not alter the setpoint without consulting HP. The fan speeds are regulated to maintain the differential pressure between the hot and cold aisle and hot aisle temperature. For more information, see "Fans (on page 59)."

The HP POD 40c G2 chilled water flow rate is regulated by the ECS Flow Control Valve that is installed on the POD chilled water return header. The ECS system opens and closes this valve to maintain the differential temperature between the POD supply and return chilled water header temperature.

For more information on the cooling system, see the HP Performance Optimized Datacenter 40c G2 Maintenance and Service Guide.

Water supply temperature

The temperature of the water supplied to the HP POD 40c G2 must be 13ºC to 24ºC (55ºF to 75ºF). Freezing water can cause a blockage and damage to the POD.

Cooling system 56

Image 56
Contents HP Performance Optimized Datacenter 40c G2 User Guide Part Number August EditionPage Contents Networking Connection portals Demarcation box Fire box Fire protection system Humidifier Controlled accessHP POD 40c G2 lighting Regulatory compliance notices Before you contact HP HP contact informationOperator safety Component safetyOverview Before you beginFire detection and suppression Environmental considerationsParts and part number identification Component identificationStructural component identification Life safety component identification Internal life safety componentsTop view shown Component Description Electrical power component identification Front view shown Component DescriptionComponent Description Internal panel labelsFront view shown Electrical safety label Description HP POD 40c G2 contains a total of 20 IT racks Control cabinet component identificationHP POD 40c G2 racks Component identification EPO system Life safety systemsLife safety overview ECS touchscreen and EPO indicators Battery backup during an EPO event Component Indicator color DescriptionFire protection system EPO modesVesda air sampling smoke detection system Fire alarm indicatorsManual fire pulls Optional Fire suppression system Fire system operator panelEmergency egress Fire suppression sequence of operationsPower, electrical, and controls Power safetySite electrical system GroundingLightning protection Power feeders Feature SpecificationCapacities Electrical and mechanical cooling capacitiesElectrical panels Arc flash safety Power distribution Electrical busway systemWire color code Panel schedulesControl cabinet power components Electrical buswaysPower, electrical, and controls Drop boxes HP POD 40c G2 lighting Power configurationsRack power Power, electrical, and controls Environmental control system overview Using the ECSEnvironmental control system Satellite control boxes SensorsTop view shown Sensor Quantity Description Connecting to the ECS Facility connections to ECSConfiguring the ECS Managing the ECS from the HP POD 40c G2Environmental control system Logging in remotely to the ECS Locating the ECS IP addresses Click ConnectPassword protection Navigating the ECS interfaceController Settings screen on Icon name DescriptionOverview screen Information Description Basic System Configuration screen Status Overview screenConfiguring the cold aisle temperature alarm parameters Configuring the hot aisle temperature alarm parameters Current temperature parameters appear on the related buttons Advanced System Configuration screen Setting the dimensions of the ECSEnvironmental control system Calibrating the flowmeter Enable/disable power management Controller Settings screen ECS alarms 40c G2 Maintenance and Service Guide orAlarm Meaning Solution Safety and security alarmsFire alarm sequence of operations HP POD 40c G2 cooling system theory of operation Water supply temperatureCooling system Water quality requirements and specifications Cooling system components Fans Side view shown Component DescriptionCondensation management DrainsLeak detection Connection portals IT networking and communicationsNetworking Connection portal Connection point Quantity Diameter Demarcation boxFire box IT networking and communications Humidifier Controlled accessOptional components Power up procedure Standard HP POD 40c G2 power up procedureStandard power up checklist Standard power up procedureCold weather HP POD 40c G2 power up procedure Site electricalSite chilled water ECS and EPOCold weather power up checklist Cold weather power up procedurePOD heating procedure Power down procedure Specifications General HP POD 40c G2 specificationsElectrical specifications Features SpecificationsRack specifications Environmental specificationsWater specifications Standard HP POD 40c G2 racks AT978A Feature Specification29ºC to 54ºC -20ºF to 130ºF Sample HP POD 40c G2 maintenance schedule MaintenancePeriodic maintenance HP contact information Contacting HPBefore you contact HP HP POD 40c G2 regulatory compliance Safety and NEC complianceRegulatory compliance notices Regulatory compliance identification numbers Federal Communications Commission noticeModifications CablesRegulatory requirements for Exit signs Glossary Personal protective equipment Enclosure of sufficient size to enable entry of personnelProgrammable logic controller Uninterruptible power system Documentation feedback ECS, configuring ECS, logging in to IndexWater quality 57 water temperature 56 wire color code
Related manuals
Manual 41 pages 46.35 Kb

Performance Optimized Data Center (POD) 40c specifications

The HP Performance Optimized Data Center (POD) 40c is a state-of-the-art data center solution designed to meet the increasing demands for efficiency, scalability, and flexibility in enterprise environments. Aimed at delivering high-performance computing with minimal environmental impact, the POD 40c integrates innovative technologies and features to optimize operations.

One of the standout characteristics of the POD 40c is its modular design, allowing for easy deployment and scalability. Customers can configure their data center according to specific requirements, enabling rapid expansion as business needs evolve. The POD can house up to 240 servers, providing ample capacity to support intensive workloads while ensuring that users can quickly adapt to changing technological landscapes.

The energy efficiency of the POD 40c is a significant highlight. By employing advanced cooling technologies, including hot aisle/cold aisle containment and direct expansion cooling, it minimizes energy consumption while maintaining optimal temperatures for hardware components. This focus on efficiency also extends to power management, with redundant power supplies and the integration of high-efficiency power distribution units (PDUs) that help reduce operational costs.

In terms of connectivity, the HP POD 40c is equipped with comprehensive networking capabilities. The design includes integrated cabling systems that ensure organized and efficient routing of power and data. This dedication to streamlined connectivity facilitates faster data transfer rates and decreases latency, enhancing overall system performance.

Moreover, security is a paramount consideration in the POD 40c design. The unit incorporates various security features, including access controls, environmental monitoring, and surveillance options, which provide peace of mind for data-sensitive businesses. These elements work together to ensure that critical data remains protected from unauthorized access and environmental threats.

Sustainability is another key aspect, as the POD 40c is designed to be environmentally friendly. The system's effective cooling mechanisms and efficient power usage contribute to reduced carbon emissions, aligning with corporate sustainability goals and industry regulations.

In conclusion, the HP Performance Optimized Data Center (POD) 40c represents a cutting-edge solution for modern data center requirements. Its modularity, energy efficiency, robust connectivity, enhanced security, and sustainability make it an attractive option for organizations aiming to optimize their IT infrastructure while maintaining agility in a rapidly evolving digital landscape. The POD 40c exemplifies HP's commitment to providing innovative and performance-driven data center solutions, positioning it as a transformative asset for businesses seeking to thrive in a data-driven world.