HP Performance Optimized Data Center (POD) 40c manual Specifications, Electrical specifications

Page 71

Specifications

General HP POD 40c G2 specifications

Features

Specifications

 

 

Overall dimensions

Height—3.66 m (12 ft)

 

Length—12.19 m (40 ft)

 

Width—2.43 m (7.97 ft)

 

 

Weight1

Empty—16,783 kg (37,000 lb)

 

Maximum fully loaded—46,266 kg (102,000 lb)

Maximum power2

600 kW HP POD 40c G2

Power input voltage

380 VAC to 415 VAC

Power distribution3

8 x 200 A electrical busways

Maximum rack quantity

20 racks

Rack Units (RU) per rack

50 RU

Rack Units (RU) total

1000 RU

Average capacity per rack (kW)

30 kW

Peak rack capacity

69 kW

 

 

Voltage to rack

200 VAC to 240 VAC

Minimum quantity of PDUs per HP POD 40c G2

20 (one per rack)

Maximum quantity of PDUs per HP POD 40c G2

40 (two per rack)

Maximum power per PDU

30A = 17 kW; 60A = 34 kW

Network supported

Bulk cable pass-through-fiber

 

Bulk cable pass-through-copper

 

(Optional) External rated DEMARC box

 

 

1The Empty weight includes the HP POD 40c G2 structure, empty racks, PDUs, and drop boxes. It does not include IT equipment.

2The maximum power depends on the exact installation and power configuration in your POD. The HP POD 40c G2 is electrically limited to 600 kW.

3The HP POD 40c G2 can be configured for redundancy or non-redundancy.

Electrical specifications

Electrical busway system information

Feature

Specification

 

 

Number of busways

8

Frequency

60 Hz

Amps (per busway)

200 A

Voltage (per busway)

380 to 415 V

Grounding

Copper

Busway configuration

3-phase + neutral + equipment ground

Specifications 71

Image 71
Contents Part Number August Edition HP Performance Optimized Datacenter 40c G2 User GuidePage Contents Networking Connection portals Demarcation box Fire box Fire protection system Humidifier Controlled accessHP POD 40c G2 lighting Before you contact HP HP contact information Regulatory compliance noticesBefore you begin Operator safetyComponent safety OverviewEnvironmental considerations Fire detection and suppressionParts and part number identification Component identificationStructural component identification Internal life safety components Life safety component identificationTop view shown Component Description Front view shown Component Description Electrical power component identificationInternal panel labels Component DescriptionFront view shown Electrical safety label Description HP POD 40c G2 contains a total of 20 IT racks Control cabinet component identificationHP POD 40c G2 racks Component identification EPO system Life safety systemsLife safety overview ECS touchscreen and EPO indicators EPO modes Battery backup during an EPO eventComponent Indicator color Description Fire protection systemVesda air sampling smoke detection system Fire alarm indicatorsManual fire pulls Fire system operator panel Optional Fire suppression systemFire suppression sequence of operations Emergency egressGrounding Power, electrical, and controlsPower safety Site electrical systemLightning protection Electrical and mechanical cooling capacities Power feedersFeature Specification CapacitiesElectrical panels Power distribution Electrical busway system Arc flash safetyPanel schedules Wire color codeElectrical busways Control cabinet power componentsPower, electrical, and controls Drop boxes HP POD 40c G2 lighting Power configurationsRack power Power, electrical, and controls Environmental control system overview Using the ECSEnvironmental control system Sensors Satellite control boxesTop view shown Sensor Quantity Description Facility connections to ECS Connecting to the ECSManaging the ECS from the HP POD 40c G2 Configuring the ECSEnvironmental control system Logging in remotely to the ECS Click Connect Locating the ECS IP addressesNavigating the ECS interface Password protectionIcon name Description Controller Settings screen onOverview screen Information Description Status Overview screen Basic System Configuration screenConfiguring the cold aisle temperature alarm parameters Configuring the hot aisle temperature alarm parameters Current temperature parameters appear on the related buttons Setting the dimensions of the ECS Advanced System Configuration screenEnvironmental control system Calibrating the flowmeter Enable/disable power management Controller Settings screen 40c G2 Maintenance and Service Guide or ECS alarmsAlarm Meaning Solution Safety and security alarmsFire alarm sequence of operations HP POD 40c G2 cooling system theory of operation Water supply temperatureCooling system Water quality requirements and specifications Cooling system components Side view shown Component Description FansDrains Condensation managementLeak detection Connection portals IT networking and communicationsNetworking Connection portal Connection point Quantity Diameter Demarcation boxFire box IT networking and communications Humidifier Controlled accessOptional components Standard power up procedure Power up procedureStandard HP POD 40c G2 power up procedure Standard power up checklistECS and EPO Cold weather HP POD 40c G2 power up procedureSite electrical Site chilled waterCold weather power up procedure Cold weather power up checklistPOD heating procedure Power down procedure Features Specifications SpecificationsGeneral HP POD 40c G2 specifications Electrical specificationsStandard HP POD 40c G2 racks AT978A Feature Specification Rack specificationsEnvironmental specifications Water specifications29ºC to 54ºC -20ºF to 130ºF Sample HP POD 40c G2 maintenance schedule MaintenancePeriodic maintenance HP contact information Contacting HPBefore you contact HP HP POD 40c G2 regulatory compliance Safety and NEC complianceRegulatory compliance notices Cables Regulatory compliance identification numbersFederal Communications Commission notice ModificationsRegulatory requirements for Exit signs Glossary Personal protective equipment Enclosure of sufficient size to enable entry of personnelProgrammable logic controller Uninterruptible power system Documentation feedback Index ECS, configuring ECS, logging in toWater quality 57 water temperature 56 wire color code
Related manuals
Manual 41 pages 46.35 Kb

Performance Optimized Data Center (POD) 40c specifications

The HP Performance Optimized Data Center (POD) 40c is a state-of-the-art data center solution designed to meet the increasing demands for efficiency, scalability, and flexibility in enterprise environments. Aimed at delivering high-performance computing with minimal environmental impact, the POD 40c integrates innovative technologies and features to optimize operations.

One of the standout characteristics of the POD 40c is its modular design, allowing for easy deployment and scalability. Customers can configure their data center according to specific requirements, enabling rapid expansion as business needs evolve. The POD can house up to 240 servers, providing ample capacity to support intensive workloads while ensuring that users can quickly adapt to changing technological landscapes.

The energy efficiency of the POD 40c is a significant highlight. By employing advanced cooling technologies, including hot aisle/cold aisle containment and direct expansion cooling, it minimizes energy consumption while maintaining optimal temperatures for hardware components. This focus on efficiency also extends to power management, with redundant power supplies and the integration of high-efficiency power distribution units (PDUs) that help reduce operational costs.

In terms of connectivity, the HP POD 40c is equipped with comprehensive networking capabilities. The design includes integrated cabling systems that ensure organized and efficient routing of power and data. This dedication to streamlined connectivity facilitates faster data transfer rates and decreases latency, enhancing overall system performance.

Moreover, security is a paramount consideration in the POD 40c design. The unit incorporates various security features, including access controls, environmental monitoring, and surveillance options, which provide peace of mind for data-sensitive businesses. These elements work together to ensure that critical data remains protected from unauthorized access and environmental threats.

Sustainability is another key aspect, as the POD 40c is designed to be environmentally friendly. The system's effective cooling mechanisms and efficient power usage contribute to reduced carbon emissions, aligning with corporate sustainability goals and industry regulations.

In conclusion, the HP Performance Optimized Data Center (POD) 40c represents a cutting-edge solution for modern data center requirements. Its modularity, energy efficiency, robust connectivity, enhanced security, and sustainability make it an attractive option for organizations aiming to optimize their IT infrastructure while maintaining agility in a rapidly evolving digital landscape. The POD 40c exemplifies HP's commitment to providing innovative and performance-driven data center solutions, positioning it as a transformative asset for businesses seeking to thrive in a data-driven world.