HP Performance Optimized Data Center (POD) 40c manual Power down procedure

Page 70

Power down procedure

1.Power down all IT equipment.

2.Open all POD power drop box breakers.

3.Monitor the system parameters and allow the POD to cool to an acceptable temperature. Be sure that the cold aisle temperature does not fall below 10°C (50°F.)

4.Close the POD return chilled water isolation valve.

5.Close the POD supply chilled water isolation valve.

6.Open the POD main power feed breakers.

7.Unlock the POD power cabinets A and B.

8.Open all breakers in the POD power cabinets A and B.

The HP POD 40c G2 is now powered down and all breakers are ready for standard or cold weather power up.

Power up procedure 70

Image 70
Contents HP Performance Optimized Datacenter 40c G2 User Guide Part Number August EditionPage Contents HP POD 40c G2 lighting Fire protection system Humidifier Controlled accessNetworking Connection portals Demarcation box Fire box Regulatory compliance notices Before you contact HP HP contact informationOverview Operator safetyComponent safety Before you beginFire detection and suppression Environmental considerationsStructural component identification Component identificationParts and part number identification Life safety component identification Internal life safety componentsTop view shown Component Description Electrical power component identification Front view shown Component DescriptionComponent Description Internal panel labelsFront view shown Electrical safety label Description HP POD 40c G2 racks Control cabinet component identificationHP POD 40c G2 contains a total of 20 IT racks Component identification Life safety overview Life safety systemsEPO system ECS touchscreen and EPO indicators Fire protection system Battery backup during an EPO eventComponent Indicator color Description EPO modesManual fire pulls Fire alarm indicatorsVesda air sampling smoke detection system Optional Fire suppression system Fire system operator panelEmergency egress Fire suppression sequence of operationsSite electrical system Power, electrical, and controlsPower safety GroundingLightning protection Capacities Power feedersFeature Specification Electrical and mechanical cooling capacitiesElectrical panels Arc flash safety Power distribution Electrical busway systemWire color code Panel schedulesControl cabinet power components Electrical buswaysPower, electrical, and controls Drop boxes Rack power Power configurationsHP POD 40c G2 lighting Power, electrical, and controls Environmental control system Using the ECSEnvironmental control system overview Satellite control boxes SensorsTop view shown Sensor Quantity Description Connecting to the ECS Facility connections to ECSConfiguring the ECS Managing the ECS from the HP POD 40c G2Environmental control system Logging in remotely to the ECS Locating the ECS IP addresses Click ConnectPassword protection Navigating the ECS interfaceController Settings screen on Icon name DescriptionOverview screen Information Description Basic System Configuration screen Status Overview screenConfiguring the cold aisle temperature alarm parameters Configuring the hot aisle temperature alarm parameters Current temperature parameters appear on the related buttons Advanced System Configuration screen Setting the dimensions of the ECSEnvironmental control system Calibrating the flowmeter Enable/disable power management Controller Settings screen ECS alarms 40c G2 Maintenance and Service Guide orFire alarm sequence of operations Safety and security alarmsAlarm Meaning Solution Cooling system Water supply temperatureHP POD 40c G2 cooling system theory of operation Water quality requirements and specifications Cooling system components Fans Side view shown Component DescriptionCondensation management DrainsLeak detection Networking IT networking and communicationsConnection portals Fire box Demarcation boxConnection portal Connection point Quantity Diameter IT networking and communications Optional components Controlled accessHumidifier Standard power up checklist Power up procedureStandard HP POD 40c G2 power up procedure Standard power up procedureSite chilled water Cold weather HP POD 40c G2 power up procedureSite electrical ECS and EPOCold weather power up checklist Cold weather power up procedurePOD heating procedure Power down procedure Electrical specifications SpecificationsGeneral HP POD 40c G2 specifications Features SpecificationsWater specifications Rack specificationsEnvironmental specifications Standard HP POD 40c G2 racks AT978A Feature Specification29ºC to 54ºC -20ºF to 130ºF Periodic maintenance MaintenanceSample HP POD 40c G2 maintenance schedule Before you contact HP Contacting HPHP contact information Regulatory compliance notices Safety and NEC complianceHP POD 40c G2 regulatory compliance Modifications Regulatory compliance identification numbersFederal Communications Commission notice CablesRegulatory requirements for Exit signs Glossary Programmable logic controller Enclosure of sufficient size to enable entry of personnelPersonal protective equipment Uninterruptible power system Documentation feedback ECS, configuring ECS, logging in to IndexWater quality 57 water temperature 56 wire color code
Related manuals
Manual 41 pages 46.35 Kb

Performance Optimized Data Center (POD) 40c specifications

The HP Performance Optimized Data Center (POD) 40c is a state-of-the-art data center solution designed to meet the increasing demands for efficiency, scalability, and flexibility in enterprise environments. Aimed at delivering high-performance computing with minimal environmental impact, the POD 40c integrates innovative technologies and features to optimize operations.

One of the standout characteristics of the POD 40c is its modular design, allowing for easy deployment and scalability. Customers can configure their data center according to specific requirements, enabling rapid expansion as business needs evolve. The POD can house up to 240 servers, providing ample capacity to support intensive workloads while ensuring that users can quickly adapt to changing technological landscapes.

The energy efficiency of the POD 40c is a significant highlight. By employing advanced cooling technologies, including hot aisle/cold aisle containment and direct expansion cooling, it minimizes energy consumption while maintaining optimal temperatures for hardware components. This focus on efficiency also extends to power management, with redundant power supplies and the integration of high-efficiency power distribution units (PDUs) that help reduce operational costs.

In terms of connectivity, the HP POD 40c is equipped with comprehensive networking capabilities. The design includes integrated cabling systems that ensure organized and efficient routing of power and data. This dedication to streamlined connectivity facilitates faster data transfer rates and decreases latency, enhancing overall system performance.

Moreover, security is a paramount consideration in the POD 40c design. The unit incorporates various security features, including access controls, environmental monitoring, and surveillance options, which provide peace of mind for data-sensitive businesses. These elements work together to ensure that critical data remains protected from unauthorized access and environmental threats.

Sustainability is another key aspect, as the POD 40c is designed to be environmentally friendly. The system's effective cooling mechanisms and efficient power usage contribute to reduced carbon emissions, aligning with corporate sustainability goals and industry regulations.

In conclusion, the HP Performance Optimized Data Center (POD) 40c represents a cutting-edge solution for modern data center requirements. Its modularity, energy efficiency, robust connectivity, enhanced security, and sustainability make it an attractive option for organizations aiming to optimize their IT infrastructure while maintaining agility in a rapidly evolving digital landscape. The POD 40c exemplifies HP's commitment to providing innovative and performance-driven data center solutions, positioning it as a transformative asset for businesses seeking to thrive in a data-driven world.