HP Performance Optimized Data Center (POD) 40c manual

Page 48

To configure the low differential pressure parameters:

1.Select Difference Pressure Low Alarm. A keypad appears.

2.Enter a differential pressure alarm parameter.

3.Select Save to store the new parameters in the system configuration file.

To configure the high differential pressure parameters:

1.Select Difference Pressure High Alarm. A keypad appears.

2.Enter a differential pressure alarm parameter.

3.Select Save to store the new parameters in the system configuration file.

Configuring the chilled water supply pressure alarm parameters

The current differential pressure parameters appear on the related buttons.

To configure the chilled water supply pressure low alarm parameters:

1.Select Chilled Water Supply Pressure Low Alarm. A keypad appears.

2.Enter a differential pressure alarm parameter.

3.Select Save to store the new parameters in the system configuration file.

To configure the chilled water supply pressure high alarm parameters:

1.Select Chilled Water Supply Pressure High Alarm. A keypad appears.

2.Enter a differential pressure alarm parameter.

3.Select Save to store the new parameters in the system configuration file.

Configuring the chilled water supply pressure alarm parameters

The current chilled water return pressure alarm parameters appear on the related buttons. To configure the chilled water return pressure low alarm parameters:

1.Select Chilled Water Return Pressure Low Alarm. A keypad appears.

2.Enter a chilled water return pressure alarm parameter.

3.Select Save to store the new parameters in the system configuration file.

To configure the chilled water return pressure high alarm parameters:

1.Select Chilled Water Return Pressure High Alarm. A keypad appears.

2.Enter a chilled water return pressure alarm parameter.

3.Select Save to store the new parameters in the system configuration file.

Configuring the chilled water supply temperature alarm parameters

The current temperature parameters appear on the related buttons.

Environmental control system 48

Image 48
Contents HP Performance Optimized Datacenter 40c G2 User Guide Part Number August EditionPage Contents Fire protection system Humidifier Controlled access HP POD 40c G2 lightingNetworking Connection portals Demarcation box Fire box Regulatory compliance notices Before you contact HP HP contact informationOperator safety Component safetyOverview Before you beginFire detection and suppression Environmental considerationsComponent identification Structural component identificationParts and part number identification Life safety component identification Internal life safety componentsTop view shown Component Description Electrical power component identification Front view shown Component DescriptionComponent Description Internal panel labelsFront view shown Electrical safety label Description Control cabinet component identification HP POD 40c G2 racksHP POD 40c G2 contains a total of 20 IT racks Component identification Life safety systems Life safety overviewEPO system ECS touchscreen and EPO indicators Battery backup during an EPO event Component Indicator color DescriptionFire protection system EPO modesFire alarm indicators Manual fire pullsVesda air sampling smoke detection system Optional Fire suppression system Fire system operator panelEmergency egress Fire suppression sequence of operationsPower, electrical, and controls Power safetySite electrical system GroundingLightning protection Power feeders Feature SpecificationCapacities Electrical and mechanical cooling capacitiesElectrical panels Arc flash safety Power distribution Electrical busway systemWire color code Panel schedulesControl cabinet power components Electrical buswaysPower, electrical, and controls Drop boxes Power configurations Rack powerHP POD 40c G2 lighting Power, electrical, and controls Using the ECS Environmental control systemEnvironmental control system overview Satellite control boxes SensorsTop view shown Sensor Quantity Description Connecting to the ECS Facility connections to ECSConfiguring the ECS Managing the ECS from the HP POD 40c G2Environmental control system Logging in remotely to the ECS Locating the ECS IP addresses Click ConnectPassword protection Navigating the ECS interfaceController Settings screen on Icon name DescriptionOverview screen Information Description Basic System Configuration screen Status Overview screenConfiguring the cold aisle temperature alarm parameters Configuring the hot aisle temperature alarm parameters Current temperature parameters appear on the related buttons Advanced System Configuration screen Setting the dimensions of the ECSEnvironmental control system Calibrating the flowmeter Enable/disable power management Controller Settings screen ECS alarms 40c G2 Maintenance and Service Guide orSafety and security alarms Fire alarm sequence of operationsAlarm Meaning Solution Water supply temperature Cooling systemHP POD 40c G2 cooling system theory of operation Water quality requirements and specifications Cooling system components Fans Side view shown Component DescriptionCondensation management DrainsLeak detection IT networking and communications NetworkingConnection portals Demarcation box Fire boxConnection portal Connection point Quantity Diameter IT networking and communications Controlled access Optional componentsHumidifier Power up procedure Standard HP POD 40c G2 power up procedureStandard power up checklist Standard power up procedureCold weather HP POD 40c G2 power up procedure Site electricalSite chilled water ECS and EPOCold weather power up checklist Cold weather power up procedurePOD heating procedure Power down procedure Specifications General HP POD 40c G2 specificationsElectrical specifications Features SpecificationsRack specifications Environmental specificationsWater specifications Standard HP POD 40c G2 racks AT978A Feature Specification29ºC to 54ºC -20ºF to 130ºF Maintenance Periodic maintenanceSample HP POD 40c G2 maintenance schedule Contacting HP Before you contact HPHP contact information Safety and NEC compliance Regulatory compliance noticesHP POD 40c G2 regulatory compliance Regulatory compliance identification numbers Federal Communications Commission noticeModifications CablesRegulatory requirements for Exit signs Glossary Enclosure of sufficient size to enable entry of personnel Programmable logic controllerPersonal protective equipment Uninterruptible power system Documentation feedback ECS, configuring ECS, logging in to IndexWater quality 57 water temperature 56 wire color code