HP Performance Optimized Data Center (POD) 40c manual Enable/disable power management

Page 52

Enable/disable power management

The current power management setting appears on the Enable/disable Power Management button. To enable or disable power management in the ECS:

1.Select Enable/disable Power Management.

2.Select Save to store the new parameters in the system configuration file.

Setting the IP address for each power meter

The current, preset static IP address appears above the Change IP address button. Change the IP address of a power meter to network multiple meters together or to resolve an IP address conflict.

To configure a power meter IP address:

1.Select IP Address Management for one of the following power meters: o Smissline A

o Smissline B o Feeder A o Feeder B

A keypad appears.

2.Enter the IP address.

3.Select Save to store the new parameters in the system configuration file.

Setting the fan controls for each fan control zone

The current fan speed appears on each fan control zone.

IMPORTANT: HP recommends leaving the fans in AUTO mode during normal operation.

To configure the fan speed:

1.Select Auto/Press in the fan control zone you want to change. A keypad appears.

2.Enter the fan speed.

3.Select Save to store the new parameters in the system configuration file.

Setting the switchboard serial number

To identify the switchboard connected to the HP POD 40c G2, set the switchboard serial number in the ECS:

1.Select Switchboard S/N. A keypad appears.

2.Enter the switchboard serial number.

3.Select Save to store the new parameters in the system configuration file.

Setting the HP POD 40c G2 serial number

If multiple HP POD 40c G2 units are connected to the same facility BMS, enter each HP POD 40c G2 serial number to monitor and display each HP POD 40c G2 ECS independently through the facility BMS.

Environmental control system 52

Image 52
Contents HP Performance Optimized Datacenter 40c G2 User Guide Part Number August EditionPage Contents HP POD 40c G2 lighting Fire protection system Humidifier Controlled accessNetworking Connection portals Demarcation box Fire box Regulatory compliance notices Before you contact HP HP contact informationOperator safety Component safetyOverview Before you beginFire detection and suppression Environmental considerationsStructural component identification Component identificationParts and part number identification Life safety component identification Internal life safety componentsTop view shown Component Description Electrical power component identification Front view shown Component DescriptionComponent Description Internal panel labelsFront view shown Electrical safety label Description HP POD 40c G2 racks Control cabinet component identificationHP POD 40c G2 contains a total of 20 IT racks Component identification Life safety overview Life safety systemsEPO system ECS touchscreen and EPO indicators Battery backup during an EPO event Component Indicator color DescriptionFire protection system EPO modesManual fire pulls Fire alarm indicatorsVesda air sampling smoke detection system Optional Fire suppression system Fire system operator panelEmergency egress Fire suppression sequence of operationsPower, electrical, and controls Power safetySite electrical system GroundingLightning protection Power feeders Feature SpecificationCapacities Electrical and mechanical cooling capacitiesElectrical panels Arc flash safety Power distribution Electrical busway systemWire color code Panel schedulesControl cabinet power components Electrical buswaysPower, electrical, and controls Drop boxes Rack power Power configurationsHP POD 40c G2 lighting Power, electrical, and controls Environmental control system Using the ECSEnvironmental control system overview Satellite control boxes SensorsTop view shown Sensor Quantity Description Connecting to the ECS Facility connections to ECSConfiguring the ECS Managing the ECS from the HP POD 40c G2Environmental control system Logging in remotely to the ECS Locating the ECS IP addresses Click ConnectPassword protection Navigating the ECS interfaceController Settings screen on Icon name DescriptionOverview screen Information Description Basic System Configuration screen Status Overview screenConfiguring the cold aisle temperature alarm parameters Configuring the hot aisle temperature alarm parameters Current temperature parameters appear on the related buttons Advanced System Configuration screen Setting the dimensions of the ECSEnvironmental control system Calibrating the flowmeter Enable/disable power management Controller Settings screen ECS alarms 40c G2 Maintenance and Service Guide orFire alarm sequence of operations Safety and security alarmsAlarm Meaning Solution Cooling system Water supply temperatureHP POD 40c G2 cooling system theory of operation Water quality requirements and specifications Cooling system components Fans Side view shown Component DescriptionCondensation management DrainsLeak detection Networking IT networking and communicationsConnection portals Fire box Demarcation boxConnection portal Connection point Quantity Diameter IT networking and communications Optional components Controlled accessHumidifier Power up procedure Standard HP POD 40c G2 power up procedureStandard power up checklist Standard power up procedureCold weather HP POD 40c G2 power up procedure Site electricalSite chilled water ECS and EPOCold weather power up checklist Cold weather power up procedurePOD heating procedure Power down procedure Specifications General HP POD 40c G2 specificationsElectrical specifications Features SpecificationsRack specifications Environmental specificationsWater specifications Standard HP POD 40c G2 racks AT978A Feature Specification29ºC to 54ºC -20ºF to 130ºF Periodic maintenance MaintenanceSample HP POD 40c G2 maintenance schedule Before you contact HP Contacting HPHP contact information Regulatory compliance notices Safety and NEC complianceHP POD 40c G2 regulatory compliance Regulatory compliance identification numbers Federal Communications Commission noticeModifications CablesRegulatory requirements for Exit signs Glossary Programmable logic controller Enclosure of sufficient size to enable entry of personnelPersonal protective equipment Uninterruptible power system Documentation feedback ECS, configuring ECS, logging in to IndexWater quality 57 water temperature 56 wire color code
Related manuals
Manual 41 pages 46.35 Kb