HP Performance Optimized Data Center (POD) 40c Cold weather HP POD 40c G2 power up procedure

Page 67

Site electrical

Close all POD site power feeder breakers and monitor for any effects that are not standard.

Site chilled water

1.Open the POD supply chilled water isolation valve.

2.If necessary, vent the air from the chilled water return header.

3.Open the POD return chilled water isolation valve.

4.Verify that audible flow noises are present.

ECS and EPO

Verify the following on using the ECS touchscreen and EPO indicators:

The ECS panel is operational and displays the user interface.

The POD lighting is operational.

The EPO system is set to Armed (White) or Bypass (Green).

POD operation

1.On the ECS touchscreen, verify that all system components are operational (green) and no alarm conditions exist.

2.On the ECS touchscreen, verify that all system parameters are operating normally.

3.On the ECS touchscreen, verify that the POD chilled water flow rate is established on the flow rate indicator.

4.In the hot aisle, close the power drop box breakers for each rack and ensure that the IT equipment is operating.

5.In the cold aisle, monitor the flow control position, chilled water flow, and POD temperatures.

6.Wait 5 minutes to allow the system to stabilize.

The HP POD 40c G2 is now fully operational and the control system automatically controls the fan and the flow control valve position.

Cold weather HP POD 40c G2 power up procedure

This procedure is for your reference only and assumes that the POD was fully commissioned and powered up by HP before being turned over to you.

Before beginning the power up procedures in this section, verify that the POD is not in operation and that the internal ambient temperature of the POD is less than 10ºC (50ºF). If the internal ambient temperature of the POD is greater than 10ºC (50ºF), see "Standard HP POD 40c G2 power up procedure (on page 66)."

IMPORTANT: The minimum acceptable inlet temperature for IT equipment is 10ºC (50ºF).

Follow the same checks and startup procedures as described in "Standard HP POD 40c G2 power up procedure (on page 66)." However, the POD has internal and outdoor ambient temperatures that are below the minimum operational temperatures for servers. The additional steps required are contained in this procedure.

Power up procedure 67

Image 67
Contents Part Number August Edition HP Performance Optimized Datacenter 40c G2 User GuidePage Contents HP POD 40c G2 lighting Fire protection system Humidifier Controlled accessNetworking Connection portals Demarcation box Fire box Before you contact HP HP contact information Regulatory compliance noticesBefore you begin Operator safetyComponent safety OverviewEnvironmental considerations Fire detection and suppressionStructural component identification Component identificationParts and part number identification Internal life safety components Life safety component identificationTop view shown Component Description Front view shown Component Description Electrical power component identificationInternal panel labels Component DescriptionFront view shown Electrical safety label Description HP POD 40c G2 racks Control cabinet component identificationHP POD 40c G2 contains a total of 20 IT racks Component identification Life safety overview Life safety systemsEPO system ECS touchscreen and EPO indicators EPO modes Battery backup during an EPO eventComponent Indicator color Description Fire protection systemManual fire pulls Fire alarm indicatorsVesda air sampling smoke detection system Fire system operator panel Optional Fire suppression systemFire suppression sequence of operations Emergency egressGrounding Power, electrical, and controlsPower safety Site electrical systemLightning protection Electrical and mechanical cooling capacities Power feedersFeature Specification CapacitiesElectrical panels Power distribution Electrical busway system Arc flash safetyPanel schedules Wire color codeElectrical busways Control cabinet power componentsPower, electrical, and controls Drop boxes Rack power Power configurationsHP POD 40c G2 lighting Power, electrical, and controls Environmental control system Using the ECSEnvironmental control system overview Sensors Satellite control boxesTop view shown Sensor Quantity Description Facility connections to ECS Connecting to the ECSManaging the ECS from the HP POD 40c G2 Configuring the ECSEnvironmental control system Logging in remotely to the ECS Click Connect Locating the ECS IP addressesNavigating the ECS interface Password protectionIcon name Description Controller Settings screen onOverview screen Information Description Status Overview screen Basic System Configuration screenConfiguring the cold aisle temperature alarm parameters Configuring the hot aisle temperature alarm parameters Current temperature parameters appear on the related buttons Setting the dimensions of the ECS Advanced System Configuration screenEnvironmental control system Calibrating the flowmeter Enable/disable power management Controller Settings screen 40c G2 Maintenance and Service Guide or ECS alarmsFire alarm sequence of operations Safety and security alarmsAlarm Meaning Solution Cooling system Water supply temperatureHP POD 40c G2 cooling system theory of operation Water quality requirements and specifications Cooling system components Side view shown Component Description FansDrains Condensation managementLeak detection Networking IT networking and communicationsConnection portals Fire box Demarcation boxConnection portal Connection point Quantity Diameter IT networking and communications Optional components Controlled accessHumidifier Standard power up procedure Power up procedureStandard HP POD 40c G2 power up procedure Standard power up checklistECS and EPO Cold weather HP POD 40c G2 power up procedureSite electrical Site chilled waterCold weather power up procedure Cold weather power up checklistPOD heating procedure Power down procedure Features Specifications SpecificationsGeneral HP POD 40c G2 specifications Electrical specificationsStandard HP POD 40c G2 racks AT978A Feature Specification Rack specificationsEnvironmental specifications Water specifications29ºC to 54ºC -20ºF to 130ºF Periodic maintenance MaintenanceSample HP POD 40c G2 maintenance schedule Before you contact HP Contacting HPHP contact information Regulatory compliance notices Safety and NEC complianceHP POD 40c G2 regulatory compliance Cables Regulatory compliance identification numbersFederal Communications Commission notice ModificationsRegulatory requirements for Exit signs Glossary Programmable logic controller Enclosure of sufficient size to enable entry of personnelPersonal protective equipment Uninterruptible power system Documentation feedback Index ECS, configuring ECS, logging in toWater quality 57 water temperature 56 wire color code
Related manuals
Manual 41 pages 46.35 Kb

Performance Optimized Data Center (POD) 40c specifications

The HP Performance Optimized Data Center (POD) 40c is a state-of-the-art data center solution designed to meet the increasing demands for efficiency, scalability, and flexibility in enterprise environments. Aimed at delivering high-performance computing with minimal environmental impact, the POD 40c integrates innovative technologies and features to optimize operations.

One of the standout characteristics of the POD 40c is its modular design, allowing for easy deployment and scalability. Customers can configure their data center according to specific requirements, enabling rapid expansion as business needs evolve. The POD can house up to 240 servers, providing ample capacity to support intensive workloads while ensuring that users can quickly adapt to changing technological landscapes.

The energy efficiency of the POD 40c is a significant highlight. By employing advanced cooling technologies, including hot aisle/cold aisle containment and direct expansion cooling, it minimizes energy consumption while maintaining optimal temperatures for hardware components. This focus on efficiency also extends to power management, with redundant power supplies and the integration of high-efficiency power distribution units (PDUs) that help reduce operational costs.

In terms of connectivity, the HP POD 40c is equipped with comprehensive networking capabilities. The design includes integrated cabling systems that ensure organized and efficient routing of power and data. This dedication to streamlined connectivity facilitates faster data transfer rates and decreases latency, enhancing overall system performance.

Moreover, security is a paramount consideration in the POD 40c design. The unit incorporates various security features, including access controls, environmental monitoring, and surveillance options, which provide peace of mind for data-sensitive businesses. These elements work together to ensure that critical data remains protected from unauthorized access and environmental threats.

Sustainability is another key aspect, as the POD 40c is designed to be environmentally friendly. The system's effective cooling mechanisms and efficient power usage contribute to reduced carbon emissions, aligning with corporate sustainability goals and industry regulations.

In conclusion, the HP Performance Optimized Data Center (POD) 40c represents a cutting-edge solution for modern data center requirements. Its modularity, energy efficiency, robust connectivity, enhanced security, and sustainability make it an attractive option for organizations aiming to optimize their IT infrastructure while maintaining agility in a rapidly evolving digital landscape. The POD 40c exemplifies HP's commitment to providing innovative and performance-driven data center solutions, positioning it as a transformative asset for businesses seeking to thrive in a data-driven world.