Roberts Gorden UHA[X][S] 60 MAJOR COMPONENTS 5.1 General, Shelf Mounting and Suspension

Page 16
SECTION 5: MAJOR COMPONENTS 5.1 General

UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 5: MAJOR COMPONENTS 5.1 General

Heaters are designed for installation above 6'

(1.8 m). These heaters must be installed within the heated space. Duct delivery systems are not permitted with axial fan units. When handling or supporting the heater from below, ensure that the weight is taken at the support points.

The gas or electrical supply lines must not be used to support the heater.

Do not locate the gas or electrical supply lines directly over the path of the flue products from the heater.

The heater must be installed in accordance with clearances to combustibles as indicated on the wall tag and this manual.

5.2 Shelf Mounting and Suspension

5.2 Shelf Mounting and Suspension WARNING

Crush Hazard

Use 3/8" threaded rod minimum.

Failure to follow these instructions can result in death, injury or property damage.

Four suspension points (3/8" nuts) are located on the top of the heater. Drop rods must be 3/8" diameter mild steel.

When handling or supporting the heater from below, ensure that the weight is taken at the support points. For typical suspension, See Page 11, Figure 5.

For typical shelf mounting on existing shelf, See Page 11, Figure 6

5.3 Wall Mounting

For typical suspension, See Page 12, Figure 7. Wall mounted heaters blowing parallel to the wall can only be installed with the service door away from the wall.

The wall mounting brackets must be attached to a suitable wall using all mounting holes. Screw sizes less than 3/8" may not be used. In order for the wall mounting brackets to adequately carry the weight of the heater, it must be installed according to best building practices.

10

Image 16
Contents Installation, Operation & Service Manual CombatUHA-Series Tubular Unit Heaters Low Profile Range Models UHAXS 30, 45, 60, 75, 100,Page 2008 Roberts-GordonLLC TABLE OF CONTENTSPrinted in U.S.A Page TABLE OF FIGURES Page 1.1 Manpower Requirements SECTION 1: HEATER SAFETY1.2 Safety Labels and Their Placement Figure 1: UHA 30 - 45 Label Placement For separated combustion units onlyFigure 2: UHA 60 - 75 Label Placement For separated combustion units onlyFigure 3: UHA 100 - 125 Label Placement For separated combustion units onlySECTION 2: INSTALLER RESPONSIBILITY 2.1 Wall Tag2.2 Corrosive Chemicals 2.3 National Standards and Applicable Codes3.4 Minimum Required Installation Clearances 3.2 Manufactured Units3.5 Clearances to Combustibles 3.6 Ventilation3.8 Electrical Supply 3.7 Gas Supply3.9 Vent 4.1 Gas Codes 4.2 Aircraft Hangars4.3 Parking Structures and Repair Garages 4.4 Electrical4.6 High Altitude SECTION 5: MAJOR COMPONENTS 5.1 General 5.2 Shelf Mounting and Suspension5.3 Wall Mounting Crush Hazard Use 3/8 threaded rod minimumFigure 6: Shelf-MountingMethods Figure 5: Suspension MethodsExisting cabinet screws must be re-used Description Part NumberWall Shelf Mounting Bracket Kit DescriptionFigure 8: Vertical Louvers Optional Push inlouver and compress spring to remove6.3 Vent Installation SECTION 6 VENTING6.1 Changing Vent and Air Intake Orientation 6.2 Venting6.4 Unvented Operation 6.3.1Standard Vented Heaters Models UHAX 30 -6.5 Horizontal Venting 6.6 Vertical Venting 6.7 Length Requirements6.7.1 Maximum Vent Lengths 6.8 Vent MaterialFigure 9: Vent and Roof Detail VerticalHorizontal OptionPage Figure 13: Concentric Vent Box Vertical OptionHorizontal OptionVent Terminal 7.1 Separated Combustion Installation 7.2 Unvented InstallationSECTION 7 AIR SUPPLY 7.3 Building Ventilation8.1 Connections SECTION 8: GAS PIPINGFigure 15: Gas Connection SECTION 9: WIRING 9.1 Positioning Thermostats9.1.1 Fan Control 9.2 Low Voltage Thermostat with One HeaterModel Relay TypeRelay Part Number UHAXS 30 -UHAXS 60 - DPST90436300 Max. Number of Heaters9.5 Internal Wiring Diagram 9.6 Ladder Wiring Diagram 9.7 Electrical Connection to the Heater SECTION 10: OPERATION AND MAINTENANCE 10.1 Pre-Start-UpChecks10.1.1 Louvers 10.1.2 Electrical ChecksFigure 16: Automatic Burner Control Sequence Figure 17: Gas Valve for Models UHAXS 30 -Required Incoming Signals Signals Output By Control10.2.3 Pressure Switch Figure 18: Gas Valve for Models UHAXS 60 -Check Gas Rate 10.2.4 Turning Off the Heater10.3 Complete Start-Up 10.2.5 External Controls10.3.1 Instruction to the User Reset Limit Switch - See Page 33, Section Figure 19: Manual Reset Limit SwitchSECTION 11: USER INSTRUCTIONS 11.1 User Instructions11.5 Simple Troubleshooting 11.5.1 Simple Troubleshooting Burner FaultsFigure 20: LED Diagnostic Codes 11.4.2 To Turn the Heater Off12.2 Burner Maintenance 12.3 Fan/Motor Assembly Maintenance12.4 Heat Exchanger Maintenance 12.5 Gas Valve Maintenance12.8 Maintenance Checklist 12.7 Venting and Air Intake PipeThe Vicinity of the Heater See Page 6, Sectionwhen installed Combustion Air IntakePipe Heat ExchangerSECTION 13: TROUBLESHOOTING 13.1 General STARTSECTION 13: TROUBLESHOOTING 13.3 Troubleshooting for Flame Supervision System 13.4Troubleshooting for Gas Valves 13.5Troubleshooting for Flue BlowerCorrect power STARTBurner Components SECTION 14 REPLACEMENT PARTS14.1 Gas Valve 14.2 Burner Compartment 14.2.1 Burner Injectors14.3 Ignition Electrode and Flame Probe 14.4 Heat Exchanger 14.5 Louver and Louver SpringsInstall Vertical screws Horizontal14.6 Flue Blower Vertical Installation 14.9 Axial Fan/Guard/Motor Assembly 14.7 Pressure Switch14.8 Ignition Control 14.9.1 Fan Removal and Replacement 14.9.2 To Replace the Fan Assembly14.10 Limit Switches 14.10.1 Removal and ReplacementSECTION 15: SPECIFICATIONS 15.1 Dimension Data TOP VIEWSIDE VIEW REAR VIEW15.2 General Technical Data Table All Models 15.3 Technical Data Table All ModelsWARRANTY IS VOID IF ROBERTS GORDON WILL PAY FORROBERTS GORDON WILL NOT PAY FOR Roberts-GordonPage OWNER WARRANTY REGISTRATION CARD About the InstallerPurchased From if different than installer Type of Installation check onePage Page Installation Clearances Fire Hazardclose to heater injury or property damage