6.3.1Standard Vented Heaters (Models UHA[X] 30 - 125)

SECTION 6: VENTING

Vents and air intakes must be adequately supported so that the heater does not bear the weight of the pipes.

For vent termination See Page 17, Figure 9 through Page 20, Figure 14.

6.3.1Standard Vented Heaters (Models UHA[X] 30 - 125)

The vent must be fitted with a low resistance terminal. See Page 17, Figure 9 through Page 17, Figure 10. Standard vented heaters do not allow outdoor air intake for combustion air.

6.3.2Separated Combustion Heaters (Models UHA[X]S 30 - 125)

The heaters are designed to be installed as separated combustion heaters. The vent and air intake are run as separate pipes to the wall or roof terminals. See Page 19, Figure 12. As an option, the vent and air intake are run as separate pipes to a concentric vent box and a concentric vent/air intake pipe penetrates the wall or roof. See Page 19, Figure 13 and Page 20, Figure 14.

For seperated combustion installation, the vent and air intake must be fitted with an individual and correctly sized sealed system and the vent and air intake must terminate at approved wall and roof terminals.

Seperated combustion units may not be common vented. See Page 14, Section 6

6.4 Unvented Operation

6.4 Unvented Operation WARNING

Carbon Monoxide Hazard

Heaters may be installed vented or unvented.

Vented heaters must be vented outdoors.

Unvented heaters must be installed in buildings with ventilation rates as per section 6.4.

Failure to follow these instructions can result in death or injury.

The heater must be vented when installed in residential buildings.

For unvented operation in commercial installations, sufficient ventilation must be provided in the amount of 4 cfm per 1000 Btu/h firing rate (United States); 3

cfm per 1000 Btu/h firing rate (Canada).

WARNING: Combustion by-products contain a chemical known to the State of California to cause cancer and birth defects or other reproductive harm.

6.5 Horizontal Venting

Horizontally vented heaters must be individually vented.

Vent pipe must be sloped ¼" (.6 cm) for every 1' (.3 m). For vent lengths greater than 5' (1.5 m), condensation will form. Insulation is recommended and condensation drains may be desired.

In noncombustible walls only, vent terminal (P/N 02537801-1P) may be used.

For 4'' (10 cm) vents in either combustible or noncombustible walls, use vent terminal (P/N 90502100) or equivalent insulated vent terminal. Follow the manufacturer's instructions for proper installation.

Instead of an insulated vent terminal, a listed thimble (with 2" (5 cm) air gap) may be used with a 4" (10 cm) vent cap (P/N 90502102).

In the State of Massachusetts, the following regulations apply to horizontally-vented heaters certified for installation in structures used in whole or in part for residential purposes (UHA 30-75 only) and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches:

Installation of Carbon Monoxide Detectors: At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back- up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back- up may be installed on the next adjacent floor level.

15

Image 21
Contents Combat Installation, Operation & Service ManualUHA-Series Tubular Unit Heaters Low Profile Range Models UHAXS 30, 45, 60, 75, 100,Page TABLE OF CONTENTS 2008 Roberts-GordonLLCPrinted in U.S.A Page TABLE OF FIGURES Page SECTION 1: HEATER SAFETY 1.1 Manpower Requirements1.2 Safety Labels and Their Placement For separated combustion units only Figure 1: UHA 30 - 45 Label PlacementFor separated combustion units only Figure 2: UHA 60 - 75 Label PlacementFor separated combustion units only Figure 3: UHA 100 - 125 Label Placement2.1 Wall Tag SECTION 2: INSTALLER RESPONSIBILITY2.2 Corrosive Chemicals 2.3 National Standards and Applicable Codes3.2 Manufactured Units 3.4 Minimum Required Installation Clearances3.5 Clearances to Combustibles 3.6 Ventilation3.7 Gas Supply 3.8 Electrical Supply3.9 Vent 4.2 Aircraft Hangars 4.1 Gas Codes4.3 Parking Structures and Repair Garages 4.4 Electrical4.6 High Altitude 5.2 Shelf Mounting and Suspension SECTION 5: MAJOR COMPONENTS 5.1 General5.3 Wall Mounting Crush Hazard Use 3/8 threaded rod minimumFigure 5: Suspension Methods Figure 6: Shelf-MountingMethodsExisting cabinet screws must be re-used Part Number DescriptionWall Shelf Mounting Bracket Kit DescriptionPush in Figure 8: Vertical Louvers Optionallouver and compress spring to removeSECTION 6 VENTING 6.3 Vent Installation6.1 Changing Vent and Air Intake Orientation 6.2 Venting6.3.1Standard Vented Heaters Models UHAX 30 - 6.4 Unvented Operation6.5 Horizontal Venting 6.7 Length Requirements 6.6 Vertical Venting6.7.1 Maximum Vent Lengths 6.8 Vent MaterialVertical Figure 9: Vent and Roof DetailHorizontal OptionPage Vertical Option Figure 13: Concentric Vent BoxHorizontal OptionVent Terminal 7.2 Unvented Installation 7.1 Separated Combustion InstallationSECTION 7 AIR SUPPLY 7.3 Building VentilationSECTION 8: GAS PIPING 8.1 ConnectionsFigure 15: Gas Connection 9.1 Positioning Thermostats SECTION 9: WIRING9.1.1 Fan Control 9.2 Low Voltage Thermostat with One HeaterRelay Type ModelRelay Part Number UHAXS 30 -DPST UHAXS 60 -90436300 Max. Number of Heaters9.5 Internal Wiring Diagram 9.6 Ladder Wiring Diagram 9.7 Electrical Connection to the Heater 10.1 Pre-Start-UpChecks SECTION 10: OPERATION AND MAINTENANCE10.1.1 Louvers 10.1.2 Electrical ChecksFigure 17: Gas Valve for Models UHAXS 30 - Figure 16: Automatic Burner Control SequenceRequired Incoming Signals Signals Output By ControlFigure 18: Gas Valve for Models UHAXS 60 - 10.2.3 Pressure SwitchCheck Gas Rate 10.2.4 Turning Off the Heater10.2.5 External Controls 10.3 Complete Start-Up10.3.1 Instruction to the User Figure 19: Manual Reset Limit Switch Reset Limit Switch - See Page 33, SectionSECTION 11: USER INSTRUCTIONS 11.1 User Instructions11.5.1 Simple Troubleshooting Burner Faults 11.5 Simple TroubleshootingFigure 20: LED Diagnostic Codes 11.4.2 To Turn the Heater Off12.3 Fan/Motor Assembly Maintenance 12.2 Burner Maintenance12.4 Heat Exchanger Maintenance 12.5 Gas Valve Maintenance12.7 Venting and Air Intake Pipe 12.8 Maintenance ChecklistThe Vicinity of the Heater See Page 6, SectionCombustion Air Intake when installedPipe Heat ExchangerSTART SECTION 13: TROUBLESHOOTING 13.1 GeneralSECTION 13: TROUBLESHOOTING 13.3 Troubleshooting for Flame Supervision System 13.5Troubleshooting for Flue Blower 13.4Troubleshooting for Gas ValvesCorrect power STARTSECTION 14 REPLACEMENT PARTS Burner Components14.1 Gas Valve 14.2.1 Burner Injectors 14.2 Burner Compartment14.3 Ignition Electrode and Flame Probe 14.5 Louver and Louver Springs 14.4 Heat ExchangerInstall Vertical screws Horizontal14.6 Flue Blower Vertical Installation 14.7 Pressure Switch 14.9 Axial Fan/Guard/Motor Assembly14.8 Ignition Control 14.9.2 To Replace the Fan Assembly 14.9.1 Fan Removal and Replacement14.10 Limit Switches 14.10.1 Removal and ReplacementTOP VIEW SECTION 15: SPECIFICATIONS 15.1 Dimension DataSIDE VIEW REAR VIEW15.3 Technical Data Table All Models 15.2 General Technical Data Table All ModelsROBERTS GORDON WILL PAY FOR WARRANTY IS VOID IFROBERTS GORDON WILL NOT PAY FOR Roberts-GordonPage About the Installer OWNER WARRANTY REGISTRATION CARDPurchased From if different than installer Type of Installation check onePage Page Fire Hazard Installation Clearancesclose to heater injury or property damage