Roberts Gorden UHA[X][S] 125, UHA[X][S] 45, UHA[X][S] 30 TROUBLESHOOTING 13.1 General, Start

Page 44
SECTION 13: TROUBLESHOOTING 13.1 General

UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 13: TROUBLESHOOTING 13.1 General

START

Are gas & electrical

No

Turn on supplies.

supplies on?

 

 

STARTWARNING

Explosion Hazard

Installation, service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.

Turn off gas and electrical supplies before performing service or maintenance.

Failure to follow these instructions can result in death, injury or property damage.

Yes

Is ignition control showing a

"4 flashes" LED code?

Noo

Is ignition control showing a

"2 flashes" LED code?

No

Does the flue

blower run?

 

UHA 30 - 75: Press in reset

 

button on manual reset limit

 

switch. UHA 100 - 125: Wait

Yes

10 - 15 minutes for limit Yes

 

switch to cool. Does fan

 

stop running?

 

No

 

Replace temperature

 

limit switch.

 

Burner has locked out due

Yes

to ignition failure. Use

Troubleshooting for

 

 

Automatic Ignition Burner

 

Systems section to test

 

burner.

No

Use Troubleshooting for

Flue Blower section to test

 

fan.

Fan and limit switch are operating normally.

Yess

With external controls (i.e.

 

Has burner “Locked Out”? No

thermostat) on, does the No

burner continue through the

 

 

heating cycle?

 

 

 

 

Yes

 

 

Use Troubleshooting for

 

 

Automatic Ignition Burner

 

 

Systems section to test burner.

Yes

 

 

Heater Operating

 

If problems persist, contact

No

Roberts-Gordon LLC at

TROUBLESHOOT ENDS.

www.rg-inc.com

 

The limit switch has

 

tripped. See Manual Reset No

Replace limit switch.

Limit Switch Figure.

 

Yes

Ensure proper air flow clearance for axial fan. Open louvers slightly.

Replace axial fan if it does

not operate.

38

Image 44
Contents Installation, Operation & Service Manual CombatUHA-Series Tubular Unit Heaters Low Profile Range Models UHAXS 30, 45, 60, 75, 100,Page Printed in U.S.A TABLE OF CONTENTS2008 Roberts-GordonLLC Page TABLE OF FIGURES Page 1.2 Safety Labels and Their Placement SECTION 1: HEATER SAFETY1.1 Manpower Requirements Figure 1: UHA 30 - 45 Label Placement For separated combustion units onlyFigure 2: UHA 60 - 75 Label Placement For separated combustion units onlyFigure 3: UHA 100 - 125 Label Placement For separated combustion units onlySECTION 2: INSTALLER RESPONSIBILITY 2.1 Wall Tag2.2 Corrosive Chemicals 2.3 National Standards and Applicable Codes3.4 Minimum Required Installation Clearances 3.2 Manufactured Units3.5 Clearances to Combustibles 3.6 Ventilation3.9 Vent 3.7 Gas Supply3.8 Electrical Supply 4.1 Gas Codes 4.2 Aircraft Hangars4.3 Parking Structures and Repair Garages 4.4 Electrical4.6 High Altitude SECTION 5: MAJOR COMPONENTS 5.1 General 5.2 Shelf Mounting and Suspension5.3 Wall Mounting Crush Hazard Use 3/8 threaded rod minimumExisting cabinet screws must be re-used Figure 5: Suspension MethodsFigure 6: Shelf-MountingMethods Description Part NumberWall Shelf Mounting Bracket Kit DescriptionFigure 8: Vertical Louvers Optional Push inlouver and compress spring to remove6.3 Vent Installation SECTION 6 VENTING6.1 Changing Vent and Air Intake Orientation 6.2 Venting6.5 Horizontal Venting 6.3.1Standard Vented Heaters Models UHAX 30 -6.4 Unvented Operation 6.6 Vertical Venting 6.7 Length Requirements6.7.1 Maximum Vent Lengths 6.8 Vent MaterialFigure 9: Vent and Roof Detail VerticalHorizontal OptionPage Figure 13: Concentric Vent Box Vertical OptionHorizontal OptionVent Terminal 7.1 Separated Combustion Installation 7.2 Unvented InstallationSECTION 7 AIR SUPPLY 7.3 Building VentilationFigure 15: Gas Connection SECTION 8: GAS PIPING8.1 Connections SECTION 9: WIRING 9.1 Positioning Thermostats9.1.1 Fan Control 9.2 Low Voltage Thermostat with One HeaterModel Relay TypeRelay Part Number UHAXS 30 -UHAXS 60 - DPST90436300 Max. Number of Heaters9.5 Internal Wiring Diagram 9.6 Ladder Wiring Diagram 9.7 Electrical Connection to the Heater SECTION 10: OPERATION AND MAINTENANCE 10.1 Pre-Start-UpChecks10.1.1 Louvers 10.1.2 Electrical ChecksFigure 16: Automatic Burner Control Sequence Figure 17: Gas Valve for Models UHAXS 30 -Required Incoming Signals Signals Output By Control10.2.3 Pressure Switch Figure 18: Gas Valve for Models UHAXS 60 -Check Gas Rate 10.2.4 Turning Off the Heater10.3.1 Instruction to the User 10.2.5 External Controls10.3 Complete Start-Up Reset Limit Switch - See Page 33, Section Figure 19: Manual Reset Limit SwitchSECTION 11: USER INSTRUCTIONS 11.1 User Instructions11.5 Simple Troubleshooting 11.5.1 Simple Troubleshooting Burner FaultsFigure 20: LED Diagnostic Codes 11.4.2 To Turn the Heater Off12.2 Burner Maintenance 12.3 Fan/Motor Assembly Maintenance12.4 Heat Exchanger Maintenance 12.5 Gas Valve Maintenance12.8 Maintenance Checklist 12.7 Venting and Air Intake PipeThe Vicinity of the Heater See Page 6, Sectionwhen installed Combustion Air IntakePipe Heat ExchangerSECTION 13: TROUBLESHOOTING 13.1 General STARTSECTION 13: TROUBLESHOOTING 13.3 Troubleshooting for Flame Supervision System 13.4Troubleshooting for Gas Valves 13.5Troubleshooting for Flue BlowerCorrect power START14.1 Gas Valve SECTION 14 REPLACEMENT PARTSBurner Components 14.2 Burner Compartment 14.2.1 Burner Injectors14.3 Ignition Electrode and Flame Probe 14.4 Heat Exchanger 14.5 Louver and Louver SpringsInstall Vertical screws Horizontal14.6 Flue Blower Vertical Installation 14.8 Ignition Control 14.7 Pressure Switch14.9 Axial Fan/Guard/Motor Assembly 14.9.1 Fan Removal and Replacement 14.9.2 To Replace the Fan Assembly14.10 Limit Switches 14.10.1 Removal and ReplacementSECTION 15: SPECIFICATIONS 15.1 Dimension Data TOP VIEWSIDE VIEW REAR VIEW15.2 General Technical Data Table All Models 15.3 Technical Data Table All ModelsWARRANTY IS VOID IF ROBERTS GORDON WILL PAY FORROBERTS GORDON WILL NOT PAY FOR Roberts-GordonPage OWNER WARRANTY REGISTRATION CARD About the InstallerPurchased From if different than installer Type of Installation check onePage Page Installation Clearances Fire Hazardclose to heater injury or property damage