UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

Figure 14: Concentric Vertical and Horizontal Vent Termination - Separated Combustion Heater

 

 

Vent Terminal

NOTE: Vent supports not

4" (10 cm)

 

 

shown.

 

with Baffle Plate

 

 

Type B-1

 

 

 

 

Vent

Storm Collar (By Others)

 

 

6" (16 cm)

(Attach with 3 sheet metal screws.)

 

Diameter

 

 

 

 

Single Wall

 

 

 

 

 

Combustion

 

 

 

Air Terminal

 

 

 

 

Flashing

 

 

 

 

(By Others)

 

 

Concentric

 

 

 

 

Vent Box

 

 

 

 

4" (10 cm) Diameter

 

 

6" (16 cm)

 

 

 

Minimum

 

Air Intake

 

 

 

4" (10 cm)

 

12" (31 cm)

 

Vertical

 

 

Diameter

 

Maximum

 

Option

Vent

 

 

 

10' (3 m)

 

 

4"(10

Vent Terminal

Maximum

 

 

 

 

cm)

 

4" (10 cm)

 

with Baffle Plate

 

Horizontal

Type

 

 

Diameter

B-1

 

 

Option

 

 

Vent

 

Vent

 

 

4" (10 cm)

Concentric

 

Diameter

 

Vent Box

 

Vent

 

 

Description

Part Number

Qty.

Concentric Vent Kit

UHVK1

 

Concentric Vent Box Top & Side Assembly

90504113

1

Concentric Vent Box Bottom Assembly

90504112

1

Screw #6 x 3/8 Self Drilling

91119100

14

4" (10 cm) Vent Terminal with Baffle Plate

90502102R

1

6" (16 cm) Combustion Air Terminal

90502103

1

Combustion

Storm Collar (By Others)

(Attach with 3

Air Terminal

sheet metal screws.)

20

Image 26
Contents UHA-Series Tubular Unit Heaters Low Profile Range Installation, Operation & Service ManualCombat Models UHAXS 30, 45, 60, 75, 100,Page Printed in U.S.A TABLE OF CONTENTS2008 Roberts-GordonLLC Page TABLE OF FIGURES Page 1.2 Safety Labels and Their Placement SECTION 1: HEATER SAFETY1.1 Manpower Requirements Figure 1: UHA 30 - 45 Label Placement For separated combustion units onlyFigure 2: UHA 60 - 75 Label Placement For separated combustion units onlyFigure 3: UHA 100 - 125 Label Placement For separated combustion units only2.2 Corrosive Chemicals SECTION 2: INSTALLER RESPONSIBILITY2.1 Wall Tag 2.3 National Standards and Applicable Codes3.5 Clearances to Combustibles 3.4 Minimum Required Installation Clearances3.2 Manufactured Units 3.6 Ventilation3.9 Vent 3.7 Gas Supply3.8 Electrical Supply 4.3 Parking Structures and Repair Garages 4.1 Gas Codes4.2 Aircraft Hangars 4.4 Electrical4.6 High Altitude 5.3 Wall Mounting SECTION 5: MAJOR COMPONENTS 5.1 General5.2 Shelf Mounting and Suspension Crush Hazard Use 3/8 threaded rod minimumExisting cabinet screws must be re-used Figure 5: Suspension MethodsFigure 6: Shelf-MountingMethods Wall Shelf Mounting Bracket Kit DescriptionPart Number Descriptionlouver and compress Figure 8: Vertical Louvers OptionalPush in spring to remove6.1 Changing Vent and Air Intake Orientation 6.3 Vent InstallationSECTION 6 VENTING 6.2 Venting6.5 Horizontal Venting 6.3.1Standard Vented Heaters Models UHAX 30 -6.4 Unvented Operation 6.7.1 Maximum Vent Lengths 6.6 Vertical Venting6.7 Length Requirements 6.8 Vent MaterialHorizontal Figure 9: Vent and Roof DetailVertical OptionPage Horizontal Figure 13: Concentric Vent BoxVertical Option OptionVent Terminal SECTION 7 AIR SUPPLY 7.1 Separated Combustion Installation7.2 Unvented Installation 7.3 Building VentilationFigure 15: Gas Connection SECTION 8: GAS PIPING8.1 Connections 9.1.1 Fan Control SECTION 9: WIRING9.1 Positioning Thermostats 9.2 Low Voltage Thermostat with One HeaterRelay Part Number ModelRelay Type UHAXS 30 -90436300 UHAXS 60 -DPST Max. Number of Heaters9.5 Internal Wiring Diagram 9.6 Ladder Wiring Diagram 9.7 Electrical Connection to the Heater 10.1.1 Louvers SECTION 10: OPERATION AND MAINTENANCE10.1 Pre-Start-UpChecks 10.1.2 Electrical ChecksRequired Incoming Signals Figure 16: Automatic Burner Control SequenceFigure 17: Gas Valve for Models UHAXS 30 - Signals Output By ControlCheck Gas Rate 10.2.3 Pressure SwitchFigure 18: Gas Valve for Models UHAXS 60 - 10.2.4 Turning Off the Heater10.3.1 Instruction to the User 10.2.5 External Controls10.3 Complete Start-Up SECTION 11: USER INSTRUCTIONS Reset Limit Switch - See Page 33, SectionFigure 19: Manual Reset Limit Switch 11.1 User InstructionsFigure 20: LED Diagnostic Codes 11.5 Simple Troubleshooting11.5.1 Simple Troubleshooting Burner Faults 11.4.2 To Turn the Heater Off12.4 Heat Exchanger Maintenance 12.2 Burner Maintenance12.3 Fan/Motor Assembly Maintenance 12.5 Gas Valve MaintenanceThe Vicinity of the Heater 12.8 Maintenance Checklist12.7 Venting and Air Intake Pipe See Page 6, SectionPipe when installedCombustion Air Intake Heat ExchangerSECTION 13: TROUBLESHOOTING 13.1 General STARTSECTION 13: TROUBLESHOOTING 13.3 Troubleshooting for Flame Supervision System Correct power 13.4Troubleshooting for Gas Valves13.5Troubleshooting for Flue Blower START14.1 Gas Valve SECTION 14 REPLACEMENT PARTSBurner Components 14.2 Burner Compartment 14.2.1 Burner Injectors14.3 Ignition Electrode and Flame Probe Install Vertical screws 14.4 Heat Exchanger14.5 Louver and Louver Springs Horizontal14.6 Flue Blower Vertical Installation 14.8 Ignition Control 14.7 Pressure Switch14.9 Axial Fan/Guard/Motor Assembly 14.10 Limit Switches 14.9.1 Fan Removal and Replacement14.9.2 To Replace the Fan Assembly 14.10.1 Removal and ReplacementSIDE VIEW SECTION 15: SPECIFICATIONS 15.1 Dimension DataTOP VIEW REAR VIEW15.2 General Technical Data Table All Models 15.3 Technical Data Table All ModelsROBERTS GORDON WILL NOT PAY FOR WARRANTY IS VOID IFROBERTS GORDON WILL PAY FOR Roberts-GordonPage Purchased From if different than installer OWNER WARRANTY REGISTRATION CARDAbout the Installer Type of Installation check onePage Page close to heater Installation ClearancesFire Hazard injury or property damage