SECTION 6: VENTING
Figure 12: Separated Combustion Heater - Vertical and Horizontal Vent Termination
12" (31 cm) Minimum from air inlet to vent termination (may be horizontal or vertical clearance).
NOTE: Vent supports not shown.
4" (10 cm) Diameter Air Intake
Vertical
Option
12" (31 cm)
Minimum from wall to vent termination.
4"
(10 cm) Diameter Vent
Listed Thimble
through
Combustible Wall
4" (10 cm)
Diameter Vent
4" (10 cm) Diameter
Air Intake
12" (31 cm)
Minimum from wall to vent termination.
Vent
Termination
Air Intake Termination
12" (31 cm)
Model | Air Intake & Vent Diameter | Part Number | Horizontal |
UHA[X]S 30 - 125 | 4" (10 cm) | 90502102 | |
|
|
| Option |
|
|
|
Minimum from air inlet to vent termination (may be horizontal or vertical clearance).
Figure 13: Concentric Vent Box
|
|
| of | 4" | (10 | cm) |
| piece | Model | ||||
|
| |||||
One |
|
| ||||
|
|
|
| |||
| .Selkirk |
| ||||
| ent |
|
|
|
| |
| v |
|
|
|
|
|
type
|
|
|
| (6 | cm) | airspace |
|
| 1/4" | others) | |||
|
|
| ||||
|
| .(By |
| |||
diameter, iv |
|
|
| |||
| qu | alent |
|
| ||
Vor | e |
|
|
|
|
|
R |
|
|
|
|
|
|
“B” |
Seal joint between single wall
and Type B vent with silicone sealant.
Combustion Air |
|
to Heater | Use 3 sheetmetal |
Concentric
Vent Box
Toward
Outside
6" (15 cm) Single Wall Inlet Air Pipe (By Others)
Exhaust | screws equally |
spaced around joint. |
from Heater
4" (10 cm) Single Wall Vent Pipe (By Others)
Use 3 sheetmetal screws equally spaced around collar.
19