| SECTION 12: SERVICING |
|
Combustion Air Intake | Intake pipe and inlet must be intact. Look for obstructions, cracks on the pipe, | |
Pipe | gaps in the sealed areas or corrosion. | |
| The area must be free of dirt and dust. | |
| Clean and reinstall as required. | |
|
| |
Heat Exchanger | Make sure there are no cracks. | |
| Make sure there is no sagging, bending or distortion. | |
| Clean or replace as required. | |
| See Page 22, Section 8. | |
|
| |
Gas Line and | Check for gas leaks. See Page 22, Section 8. | |
Valves |
|
|
|
| |
Burner Observation | Make sure it is clean and free of cracks or holes. | |
Window | Clean and replace as required. | |
| ||
|
| |
Flue Blower Scroll, Wheel | Compressed air or a vacuum cleaner may be used to clean dust and dirt. | |
and Motor |
|
|
|
| |
Inshot Burners and | Clear obstructions (even spider webs will cause problems). | |
Orifices | Carefully remove any dust and debris from the burner. | |
| ||
|
| |
| Replace if there are cracked ceramics, excessive carbon residue, or erosion | |
| of the electrode. | |
| The electrode gap should be 1/8" (3.2 mm). | |
|
| |
Thermostat | There should be no exposed wire or damage to the device or wiring. | |
| See Page 29, Section 10. | |
|
| |
Suspension Points | Make sure the heater is hanging securely. | |
| Look for signs of wear on the suspension materials or ceiling. | |
| See Page 11, Figure 5. | |
|
| |
Silicone Tubing | Ensure tight, secure fit on all pressure fittings at pressure switch, | |
| burner partition, and blower outlet. | |
|
| |
Gas Valve | Verify that cap covering pressure regulator adjustment screw is secure and | |
| has not been tampered with. | |
| Verify all wiring connections. | |
|
| |
Condensate Drain | Flush drain and clear any obstructions. | |
(when installed) |
|
|
|
| |
Wall Tag | If wall tag is present, make sure it is legible and accurate. Please contact | |
| Roberts Gordon LLC or ROBERTS GORDON® independent distributor if you | |
| need a wall tag. See Page 5, Section 2.1. | |
|
|
|
37