HP 9000 800t s Z7634-96002 manual Replacement Power Supply, DC Power Specifications Data

Page 24

Addendum to D Class Enterprise Servers System Installation Guide

DC Power Supply

Specifications

Table 1-3

DC Power Specifications

 

 

 

 

 

Specification

Data

 

 

 

 

Input

-48V, 20A max under full load

 

 

-60V

 

 

 

 

Shutdown Thresholds

-72V (input over-voltage)

 

 

-40V (input under-voltage)

 

 

 

 

Power

650W

 

 

 

 

Outputs (* = remote sense provided)

3.3V*, 25A (maximum)

 

 

5V*, 55A (maximum)

 

 

12.V, 10A (maximum)

 

 

Aux5V, 55A (maximum)

 

 

 

 

Temperature Ranges:

5° to 40° C (41° to 104° F)

 

Operating:

 

 

 

-40° to 45°C (-40° to 113°F)

 

Non-operating:

 

 

 

-5° to 50°C (23° to 122°F)

 

Short-term Operating:

 

 

 

 

 

Remote (switched ground) RESET signal:

-48V, 50mA (minimum)

 

 

500mA (maximum)

 

 

 

 

Alarm signals:

Dry relay contact closure

 

Input out of tolerance

for all alarms

 

Output out of tolerance

 

 

 

 

 

Fused circuits:

(Not field replaceable)

 

Power Input

30A

 

 

 

Replacement Power Supply

To order a replacement DC Power Supply, order replacement part number Z7634-67003.

24

Chapter 1

Image 24
Contents Addendum to D Class Enterprise Servers Third EditionPage Printing History Printing HistoryAbout This Manual Contents Contents Addendum to D Class Contents Purpose of this Addendum Tools NeededSeismic Rack Kit Seismic Rack Kit Site Hazard Considerations Installation Seismic Rack Installation Installation Installation Attach cable retractor item 26, -3 to right main bracket as Tray Seismic Rack Installation Installation DC Power Supply ConnectionsDC Power Cable Pinouts Function Color Pin No Power supply cable is used as the main disconnect deviceFor this equipment. The key switch on front of SPU does not Safety Grounding Procedures DC Power Cable Pin DiagramSpecifications Replacement Power SupplyDC Power Specifications Data Regulatory/Safety Statements FCC Statement USA Only IEC Statement WorldwideInternational Product Noise Declaration Germany Only Acoustic Noise EmissionsGeräuschemission Safety EMC RegulatoryEMC Certification EMC LabelsConforms to the following Product Specifications SafetyAccording to ISO/IEC Guide 22 and EN Manufacturer’s Name