SECTION 14: OPERATION

14.1.1 Heater Lockout Indicator by Connector

A 230 V signal is provided which enables the ROBERTS GORDON® controller, BMS system, etc. to indicate the heater that has failed. An additional wire has to be installed from the heater lockout indicator connector to the monitoring computer. See Page 57, Section 13.5.

Description

Part Number

Connector male - Lockout Indicator

91324000

Connector female - Lockout Indicator

91324001

Wire Blue 12"

91300011

Wire Brown 12"

91300012

14.1.2Heater Lockout Indicator by Volt Free Connector

Avolt free contact relay is closed which enables the ROBERTS GORDON® controller, BMS system, etc. to indicate the heater that has failed. An additional wire has to be installed from the heater volt free connector to the monitoring computer. See Page 57, Section 13.5.

Description

Part Number

Connector male - Volt Free

91324000

Connector female - Volt Free

91324001

Wire Blue 7"

91300004

Wire Brown 7"

91300005

Wire Yellow 12"

91300003

Screw #8 x 3/8 Hex Wshr PHH Type 23

94961406

Base relay P2RF05E

C1050B

Relay G2R1-SN IMO 220 V 10 A

C1049B

14.2 Testing

Establish that a satisfactory purged gas supply and an electrical supply is available to the heater. Ensure that all time clocks and thermostats are set to call for heat.

With the gas supply cut off at the appliance isolating cock and the electrical supply isolated by switching off at the local switch and removing the appliance inlet plug, open the control chamber secured by the two screws. Loosen the sealing screw from the pressure test point and remove the cover cap from the governor.

Turn on the gas supply and connect appliance electrical plug. Ensure that the timer or thermostat, if fitted, are set to call for full gas rate. Switch on at the local switch. The sequence as described should take place. If not, refer to detailed fault finding sequence. When flame is established, check the gas pressure reading and adjust if necessary. Refer to burner data label.

Check the gas pressure at the outlet of the gas valve. See Page 74, Section 18.9.1 or See Page 75, Section 18.9.2 for pressure settings or refer to the data plate.

Switch off the electrical supply (shutting down the heater), remove pressure gauge - tighten pressure test point screw, ensuring a tight gas seal. Replace governor cover cap. Close burner side cover.

14.3 Commissioning (Multiburner)

1.Establish that a satisfactory purged gas supply and an electrical supply is available to the heater.

2.ENSURE that all the dampers are in the fully open position.

3.With the gas supply off at each of the burners and the electrical supply isolated, open the control chamber secured by two self tapping screws.

4.Ensure that all time clocks and thermostats are set to call for heat.

5.Switch on the electrical supply at the main isolator. This will start the exhaust fan.

6.Balancing Cold Vacuum

Check each burner vacuum by connecting an inclined pressure gauge to the tee on the pressure switch inlet side in the burner. Adjust the damper so that the vacuum is 1.9 mbar. Repeat for each burner.

7.Starting at the end burner (furthest from the exhaust fan), with the inclined pressure gauge connected as described above. Turn on the gas supply and con- nect appliance electrical plug, reset the pressure switch by removing vacuum from the inlet side of the pressure switch waiting several seconds and recon- necting. The start up sequence described on Page 58, Section 14 should take place. If not, refer to detailed fault finding sequence. When flame is established, check the gas pressure reading and adjust if necessary. See data label.

Check the gas pressure at the outlet of the gas

valve. See Page 74, Section 18.9.1 or See Page 75, Section 18.9.2 for pressure settings or refer to the data plate.

Switch off the electrical supply (shutting down the heater), remove pressure gauge - refit pressure test- point screw, ensuring a tight gas seal. Replace gov- ernor cover cap.

Repeat this procedure for each burner in the sys- tem.

Close the control chamber and secure with two sheet metal screws.

8.Balancing Hot Vacuum

Reconnect all the burners on the system and allow them to reach full operating temperature (approxi- mately 20 minutes). Return to each burner and recheck the hot vacuum at the tee on the inlet to the pressure switch. Readjust the damper so that the hot vacuum of 1.5 mbar (2.0 mbar for BH40EF) is achieved and lock the damper in position.

14.4 System Checks

Switch on again at the local switch to ensure smooth ignition. Carry out the following system checks:

When running, turn off the gas supply at the appliance. The heater will immediately shut down followed by three ignition attempts followed by lockout.

Linear and Double Linear only:

When running, disconnect the fan plug from the burner. The unit should shut down within three seconds, proving operation of the pressure switch.

14.5 User Instructions

After satisfactory testing, ensure that the client is fully

aware of the operation of the system. Bring this manual to

59 of 75

Image 65
Contents Owner If you smell gasPage Roberts-Gordon LLC Table of ContentsPage Linear & Double Linear, One Side Reflector Table of FiguresPage Product Approval Safety Labels and Their Placement Heater SafetyManpower Requirements Top Panel Label Placement National Standards and Applicable Codes Installer ResponsibilityLow Level User Instructions Clearances to Combustibles BH45ST/EF BH40ST/EFBH15ST BH30DL BH20ST BH40DLBH35ST/EF BH70DL/EF BH55STBH20UT Clearance Data -U TubeBH15UT 200 1530 1650 560 200 1370 1500 560250 1630 1860 560 250 1780 1960 560Major Component Descriptions General Suspension Details Typical Suspension Details Description Linear & Double Linear Heater InstallationLinear Standard Parts List Burner Tube ClipsWeld Spot BH20ST f BH15ST fBH35ST/EF f BH45ST/EFBH50ST/EF f BH55ST fDouble Linear Standard Parts List Burner Tube Reflector Support Tube and Reflector Clips Assembly CouplingReflector Overlap approx RepeatedSide Coupling and Tube Assembly Burner Tube InstallationOpen ClosedTighten slide bar as shown below 1 Coupling and Tube Assembly2 Coupling and Tube Assembly Tube Clamp Package Installation 02750303 Option a Option BFan Tube Fan Tube Weld Spot Coupling TeeTube Standard Parts List Tube Heater Installation94320812 200 mm Tube Assembly Overview690 mm BH35UT/EF gReflector Overlap 1780 mm Burner Tube and Fan Tube Installation U-Tube Hanger PlacementU-Tube Support Bracket Assembly Installation 1 Tube Clamp Package InstallationBolt Nut Torque 13.56 Nm Lock Washer Tube ClampOrient coupling so that Impact block is Tube Support Bracket Assembly Coupling Tube InstallationU-Tube Installation Reflector 02750303 Reflector Support Strap 03050000 Screw #8 x 3/4 3.9 x 19mm Damper Flange Multiburner Configuration & InstallationFan Tube Weld Spot Install Fully open position Mm Manifold Damper Typical Cross Typical Fan Arrangement Mm Hanger CrossMm Manifold Max 1000 3000 mm Tee ID/ID Sleeve Mm Hanger ReducerFan Assembly Burner & FAN InstallationBurner Installation Tighten securely until tube Double Linear Fan InstallationCannot be removed Tee Tighten securely until tube Cannot be removedUse 1 x ¾ reducer 1 Double Linear Fan InstallationNot supplied Non-Return ValveCondensate Drain Assembly Optional Heater Accessories She et Met al Screw 2 Side Reflector InstallationPer reflector Use additional supports High air movement Use six #8 sheet metal screws to attach the joint piece Tube Cover InstallationStep 2 Frame Shield Installation Decorative Grille Installation .3.1 Grille Installation3 Grille Installation 2 Grille End Cap Installation2 Fastener Installation Sports Hall Guard Installation1 Grille Installation 3 Mesh Guard ConnectionAdjust Undershield Height Undershield Installation 10.6.1 Hanger InstallationUndershield Installation Wall Mounting Hardware InstallationLinear Venting End of Tube Fan Tube Outside Combustion Air SupplyAir Supply Requirements Common Duct Fresh Air Intake SpigotGAS Piping Gas Supply Pipe Connector 545 mm Minimum BurnerShut-Off Valve Supplied by Roberts-Gordon 1000 mm Long Typical External Wiring Diagram Double Linear Option WiringTypical External Wiring Diagram Linear or U-Tube Typical External Wiring Diagram Multiburner Internal Wiring Diagram Operation Operation and serviceTubing may still be hot Heater Lockout Indication OptionalHeater Lockout Indicator by Volt Free Connector Heater Lockout Indicator by ConnectorTesting Commissioning MultiburnerECA Approved Systems Multiburner only Servicing Instructions Automatic Flame Control Unit Pressure SwitchNeons Vehicles and Other ObjectsGas Line TubesBurner Observation WindowTroubleshooting U-Tube Troubleshooting Flow Chart Linear, Double LinearTroubleshoot Ends Troubleshooting Flow Chart Linear, Double Linear and U-TubeTroubleshooting Flow Chart Multiburner Re-establish continuity Purge Lines Troubleshooting Flow Chart MultiburnerWhile burner is running. See Manifold Gas Pressure SettingGovernor orifice pressure Replacement Parts Item Description Specifications Tube Heater Linear HeaterDouble Linear Heater Standard Burner SpecificationsBH15 BH20 BH25 BH30 BH35 BH40 BH45 BH50 BH55 Burner Airplate ID Number Jet Numbers #30 #19 Natural G20BH25/EF BH30/EF BH35/EF BH40/EF BH45/EF BH50/EF EF Burner SpecificationsPage Page F r a r e d H e a t i n g