BLACKHEAT® INSTALLATION OPERATION AND SERVICE MANUAL
SECTION 18: SPECIFICATIONS
18.1 Material Specifications
18.1.1 Combustion and Tubes
100 mm dia. 16 gauge heat treated aluminised mild steel.
18.1.2 Reflectors
NS3 H14 aluminium or 1.4016 2R stainless steel (option).
18.2 Heater Specifications
18.2.1 Sequence Controller
Fully automatic, three try, direct spark, 100% shut off ignition flame rectification module.
18.2.2 Electrical
Rating: 230V, 50 Hz, 1 Ø, 1 A
Connection: 3 pin moulded plug
18.2.3 Gas Supply
Connection: Rc1/2 (1/2" BSP int)
Natural G20:
Minimum - Inlet 15 mbar (6 in wg)
Maximum - Inlet 50 mbar (20 in wg)
Natural G25:
Minimum - Inlet 17.5 mbar (7 in wg)
Maximum - Inlet 50 mbar (20 in wg)
LP Gas (Propane or Butane):
Minimum - Inlet 32.5 mbar (13 in wg)
Maximum - Inlet 50 mbar (20 in wg)
18.3 Venting Specifications
18.3.1 Fans
Model: Torin DSF | |
| |
Model: Torin DSA | |
| |
50 EF, | Model: Magnetek JF1G |
BH30DL, 40DL, BH50DL/EF, | |
60DL/EF, 70DL/EF | Model: Magnetek JF1G |
Multiburner | Model: Airflow 83 BTLW |
.................. | Model: Airflow 90 BTLW |
Consult the manufacturer for availability of alternate fans.
18.3.2 Flue
When fitted, the flue must be 100 mm, or greater in diameter, and must conform to National Codes. The flue must be self supporting. Inlet must be 100 mm diameter.
Multiburner - Flue must be 150 mm diameter and will be sized to suit arrangement and will connect to the fan. Flue material must conform to National Codes. The flue must be self supporting.
18.4 Suspension Specifications
Hang heater with materials with a minimum working load of 33 kg.
18.5 Controls Specifications
Time switches, thermostats, etc. can be wired into the electrical supply. External controls supplied as an optional extra.