York YK Chiller Manual and Troubleshooting Resources

Page 19

FORM 160.49-O2

SERVICE KEYS

LD00963

FIG. 13 – KEYPAD – SERVICE KEYS LOCATION

The Service keys are provided for the service techni- cian’s use when performing routine maintenance or when troubleshooting the system.The WARNING RESET and PRE-ROTATION VANES keys are enabled in SERVICE mode only. The remainder of the Service keys are en- abled in SERVICE, LOCAL or REMOTE mode.

PRE-ROTATION VANES KEYS

If chiller is equipped with the REFRIGERANT LEVEL CONTROL (and EPROM version C.02F(T).13 or later), the pre-rotation vanes keys can be used to manually control the refrigerant level variable orifice or the pre- rotation vanes. The procedure to select either manual vane or manual variable orifice control is contained in “Special Setpoints and Programming Procedures” sec- tion of Service manual, Form 160.49-M3 and must be performed by a qualified service technician only.

OPEN – Press and release this key to drive the pre- rotation vanes open. If the chiller is running,

SYSTEM RUN – VANES OPENING is displayed. If chiller is not running, SYS READY TO START – VANES OPENING is displayed. The vanes will continue to open until the CLOSE, HOLD, or AUTO (if temperature error requires it) keys are pressed and released.

HOLD – Press and release this key to hold the pre- rotation vanes in their present position. If the chiller is

running,

SYSTEM RUN – VANES HOLDING

 

is displayed.

If chiller is not running,

 

 

SYS READY TO START – VANES HOLDING

 

is displayed. The

 

 

 

 

 

vanes will remain stationary until the OPEN, HOLD, or AUTO keys are pressed and released.

AUTO – Press and release this key to put the pre-rota- tion vanes under LCWT control as long as the current limit setpoint is not reached, which causes the current limit function to override the LCWT control. If system is

running, SYSTEM RUN – AUTO VANES is displayed. The

actual opening and closing of the vanes is indicated on the display. When the vanes are opening,

SYSTEM RUN – VANES OPENING is displayed. If the vanes

are closing, SYSTEM RUN – VANES CLOSING is displayed. Whenever the Control Center is in LOCAL, REMOTE or PROGRAM mode, the vane control circuitry is automati- cally placed in AUTO mode and the vanes operate to control the leaving chilled water temperature to the pro- grammed setpoint.

CLOSE – Press and release this key to drive the pre- rotation vanes closed. If the chiller is running,

SYSTEM RUN – VANES CLOSING

 

is displayed. If chiller is

not running,

 

 

 

is

SYS READY TO

START – VANES CLOSING

displayed. When the vanes are full closed,

 

SYS READY TO START – VANES CLOSED is displayed. The vanes will continue to close until the OPEN, HOLD, or AUTO keys are pressed.

YORK INTERNATIONAL

19

Image 19
Contents With Microcomputer Control Center Centrifugal Liquid ChillersTable of Contents Nomenclature Description of System and Fundamentals of Operation SectionSystem Operation Description See Fig Capacity Control Detail a Compressor Prerotation VanesMicrocomputer Control Center and Keypad Section Microcomputer Control CenterCondenser Refrigerant Level IntroductionOperation Control CenterDisplaying System Parameters To Display OIL Pressure To Display Chilled Liquid TemperaturesPsid = HOP LP Offset Pressure To Display Operating Hours and Starts Counter To Display Motor CurrentSystem Setpoints See Programming System Setpoints, Displaying System Setpoints To Display Undervoltage setpoints Programming System Setpoints Press Access Code keyProgramming Microcomputer Control CenterSolid State Starter, refer to Fig Electro-Mechanical Starter, refer to FigSetpoint Keypad Programming Pull Down Demand SetpointKeypad Programming Daily Schedule Setpoint Keypad Programming Holiday PRE-ROTATION Vanes Keys Service KeysPulldn Level = XXX% Setp = XXX% Actual = XXX% Other Service KeysOperating Modes Display Messages Compressor SwitchSystem RUN Auto Vanes System Shutdown Messages When Control Center is in Remote mode MON Xxxx AM Evap Trans or Probe Error Then Function Jumper PositionTherefore MON Xxxx AM High Line Voltage MON Xxxx AM High Speed Drain Temp Reservoir System Operating ProceduresSTART-UP Procedure OIL Heaters Checking the OIL Level in the OILChiller Operation START-UPChiller Starting Sequence & Shutdown Sequence Condenser Water Temperature ControlOperating LOG Sheet EcwtLchwt Checking OperationQuarterly Operating Inspections See SectionDaily WeeklyCycling Shutdowns Need for Maintenance or ServiceNormal and Safety System Shutdowns Safety ShutdownsSTART-UP After Prolonged Shutdown Prolonged ShutdownSystem Components System Components DescriptionSpeed Increasing Gears GeneralCompressor Compressor Lubrication System See FigSchematic Drawing YK Compressor Lubrication System Refrigerant Flow Control OIL HeaterMotor Driveline Heat ExchangersSolid State Starter Optional Microcomputer Control Center See SectionVariable Speed Drive Optional OIL Return System Operational MaintenanceChanging the Dehydrator OIL Charge OIL Charging ProcedureRise TroubleshootingLEP Operating Setpoints System After Service Symptom no OIL Pressure When System Start Button Pushed Operating Analysis ChartSymptom Abnormally LOW Suction Pressure Symptom High Cooler PressureOIL Pressure display key Symptom OIL Pump Vibrates or is NoisySymptom OIL Pump Fails to Deliver OIL Pressure Symptom Reduced OIL Pump CapacityLeak Testing During Operation MaintenanceConducting R-22 Pressure Test System Pressures Vacuum TestingOperation Vacuum DehydrationChecking the Refrigerant Charge During Unit Shutdown Refrigerant ChargingRefrigerant Charge Megging the Motor Handling Refrigerant for Dismantling and RepairsMotor Stator Temperature and Insulation Resistances Condensers and Coolers Testing for Cooler and Condenser Tube Leaks Electrical Controls CompressorCooler and Condenser Preventive MaintenancePressure Testing Compressor MotorElectrical Controls ALL Rights Reserved

YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4, YK M3 M3 G4 specifications

The York YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, and YK LB LB G4 THRU YK SE SC J4 represent a sophisticated line of HVAC systems engineered for modern commercial applications. These models are celebrated for their innovative designs, energy efficiency, and advanced features, making them a preferred choice among facility managers and building owners.

One of the standout characteristics of the York YK series is its modular construction, which provides unparalleled flexibility in system configuration. This design allows for easy upgrades and expansions as building demands evolve. The YK M3 series, in particular, is equipped with advanced controls that enhance system performance while minimizing energy consumption. With features like variable speed drives and sophisticated control algorithms, these units optimize airflow and refrigerant use, significantly reducing operational costs.

Another notable aspect of the YK M3 M3 G4 is its robust refrigeration technology. Utilizing high-efficiency scroll compressors, these chillers deliver impressive cooling capacities while maintaining high energy efficiency ratings. Integrated with low GWP (Global Warming Potential) refrigerants, they meet modern environmental standards, ensuring compliance with regulations while promoting sustainability.

The YK LB LB G4 and YK SE SC J4 models further enhance York’s portfolio with their compact designs and lower installation footprints. These chillers are ideal for applications where space is at a premium. Additional features include advanced noise reduction technology, allowing for quieter operation compared to traditional HVAC systems, making them suitable for urban environments or buildings where noise control is a priority.

Furthermore, York's commitment to continuous innovation is evident in the incorporation of smart technology across its chiller series. Features such as connectivity options for monitoring and diagnostics through mobile apps or web interfaces empower users to maintain optimal system performance proactively. This connectivity aids in predictive maintenance, enabling timely interventions that extend equipment life and reliability.

Finally, all these high-efficiency chillers are backed by York's renowned service support network, ensuring that customers have access to expert assistance and maintenance services whenever needed. With their exceptional features, modern technologies, and commitment to sustainability, the York YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, and YK LB LB G4 THRU YK SE SC J4 models stand out as leaders in the commercial HVAC market, setting new standards for performance and efficiency.