York YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4 Start-Up, Chiller Operation

Page 31

START-UP

1.If the chilled water pump is manually operated, start the pump. The Control Center will not allow the chiller to start unless chilled liquid flow is es- tablished through the unit. (A field supplied chilled water flow switch is required.) If the chilled liquid pump is wired to the MicroComputer Control Cen- ter the pump will automatically start, therefore, this step is not necessary.

2.To start the chiller, press the COMPRESSOR START switch. This switch will automatically spring return to the RUN position. (If the unit was previ- ously started, press the STOP/RESET side of the COMPRESSOR switch and then press the START side of the switch to start the chiller.) When the start switch is energized, the Control Center is placed in an operating mode and any malfunction will be noted by messages on the 40 character alphanumeric display. (See Fig. 3.)

NOTE: Any malfunctions which occur during STOP/RESET are also displayed.

When the chiller is shut down, the prerotation vanes will close automatically to prevent loading the com- pressor on start-up. When the prerotation vanes are fully closed the “Display” will read

SYSTEM READY TO START – VANES CLOSED when in SERVICE mode.

When the chiller starts to operate, the following auto- matic sequences are initiated: (Refer to Fig. 15, “Chiller Starting & Shutdown Sequence Chart”.)

1.The MicroComputer Control center alphanumeric display message will read

START SEQUENCE INITIATED

for the first 50 seconds of the starting sequence, (3 minutes if Micro Board JP6 removed).

2.The compressor vent line solenoid valve will open after the first 5.83 minutes of operation. The sole- noid will close automatically after the compressor shuts down.

3.The 1R-1 contacts of the 1R start relay will re- main open for the first 50 seconds of oil pump operation. These contacts will close, starting the compressor motor and the condenser water pump at the end of the 50 second period.

4.The oil pump will start to circulate oil for a 50 second pre-run to establish oil flow and adequate lubrication to all bearings, gears, and rotating sur- faces within the compressor.

FORM 160.49-O2

The high and low oil pressure transducers (OP) and the oil temperature sensor (RT3) will sense any malfunction in the lubrication system and ac- tivate one of the following display messages:

DAY 10:30 AM – LOW OIL PRESSURE

DAY 10:30 AM – HIGH OIL TEMPERATURE

DAY 10:30 AM – LOW OIL TEMP – AUTOSTART

DAY 11:30 AM – OIL PRESSURE TRANSDUCER

5.The anti-recycle timer software function will oper- ate after the 50 seconds of pre-run time. At this time, the timer will be initiated and will run for 30 minutes after the compressor starts. If the chiller shuts down during this period of time, it cannot be started until the timer completes the 30 minute cycle.

6.The chilled liquid pump contacts will close start- ing the chilled liquid pump to allow liquid flow through the cooler when the COMPRESSOR start switch is energized.

7.After the first 50 seconds of operation, the com- pressor will start and the Control Center display message will read

SYSTEM RUN – CURRENT LIMIT IN EFFECT while the motor is accelerating to full speed. When the mo- tor reaches full speed and the current falls below 100% FLA the message will read

SYSTEM RUN – LEAVING TEMP. CONTROL

8.For additional display messages and information pertaining to the operation of the MicroComputer Control Center, refer to “Section 2”.

9.Low Oil Temp. Differential.

CHILLER OPERATION

After the compressor reaches its operating speed, the Prerotation Vanes will begin to open under the control of the Microprocessor Board which senses the leaving chilled liquid temperature. The unit capacity will vary to maintain the leaving CHILLED LIQUID TEMPERA- TURE setpoint. The Prerotation Vanes are modulated by an actuator under the control of the Microprocessor Board. The vane control routine employs proportional plus derivative (rate) control action. A drop in chilled liquid temperature will cause the actuator to close the Prerotation Vanes to decrease chiller capacity. When the chilled liquid temperature rises, the actuator will open the Prerotation Vanes to increase the capacity of the chiller.

YORK INTERNATIONAL

31

Image 31
Contents With Microcomputer Control Center Centrifugal Liquid ChillersTable of Contents Nomenclature Description of System and Fundamentals of Operation SectionSystem Operation Description See Fig Capacity Control Detail a Compressor Prerotation VanesMicrocomputer Control Center and Keypad Section Microcomputer Control CenterCondenser Refrigerant Level IntroductionOperation Control CenterDisplaying System Parameters To Display OIL Pressure To Display Chilled Liquid TemperaturesPsid = HOP LP Offset Pressure To Display Operating Hours and Starts Counter To Display Motor CurrentSystem Setpoints See Programming System Setpoints, Displaying System Setpoints To Display Undervoltage setpoints Programming System Setpoints Press Access Code keyProgramming Microcomputer Control CenterSolid State Starter, refer to Fig Electro-Mechanical Starter, refer to FigSetpoint Keypad Programming Pull Down Demand SetpointKeypad Programming Daily Schedule Setpoint Keypad Programming Holiday PRE-ROTATION Vanes Keys Service KeysPulldn Level = XXX% Setp = XXX% Actual = XXX% Other Service KeysOperating Modes Display Messages Compressor SwitchSystem RUN Auto Vanes System Shutdown Messages When Control Center is in Remote mode MON Xxxx AM Evap Trans or Probe Error Then Function Jumper PositionTherefore MON Xxxx AM High Line Voltage MON Xxxx AM High Speed Drain Temp Reservoir System Operating ProceduresSTART-UP Procedure OIL Heaters Checking the OIL Level in the OILChiller Operation START-UPChiller Starting Sequence & Shutdown Sequence Condenser Water Temperature ControlOperating LOG Sheet EcwtLchwt Checking OperationQuarterly Operating Inspections See SectionDaily WeeklyCycling Shutdowns Need for Maintenance or ServiceNormal and Safety System Shutdowns Safety ShutdownsSTART-UP After Prolonged Shutdown Prolonged ShutdownSystem Components System Components DescriptionSpeed Increasing Gears GeneralCompressor Compressor Lubrication System See FigSchematic Drawing YK Compressor Lubrication System Refrigerant Flow Control OIL HeaterMotor Driveline Heat ExchangersSolid State Starter Optional Microcomputer Control Center See SectionVariable Speed Drive Optional OIL Return System Operational MaintenanceChanging the Dehydrator OIL Charge OIL Charging ProcedureRise TroubleshootingLEP Operating Setpoints System After Service Symptom no OIL Pressure When System Start Button Pushed Operating Analysis ChartSymptom Abnormally LOW Suction Pressure Symptom High Cooler PressureOIL Pressure display key Symptom OIL Pump Vibrates or is NoisySymptom OIL Pump Fails to Deliver OIL Pressure Symptom Reduced OIL Pump CapacityLeak Testing During Operation MaintenanceConducting R-22 Pressure Test System Pressures Vacuum TestingOperation Vacuum DehydrationChecking the Refrigerant Charge During Unit Shutdown Refrigerant ChargingRefrigerant Charge Megging the Motor Handling Refrigerant for Dismantling and RepairsMotor Stator Temperature and Insulation Resistances Condensers and Coolers Testing for Cooler and Condenser Tube Leaks Electrical Controls CompressorCooler and Condenser Preventive MaintenancePressure Testing Compressor MotorElectrical Controls ALL Rights Reserved

YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4, YK M3 M3 G4 specifications

The York YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, and YK LB LB G4 THRU YK SE SC J4 represent a sophisticated line of HVAC systems engineered for modern commercial applications. These models are celebrated for their innovative designs, energy efficiency, and advanced features, making them a preferred choice among facility managers and building owners.

One of the standout characteristics of the York YK series is its modular construction, which provides unparalleled flexibility in system configuration. This design allows for easy upgrades and expansions as building demands evolve. The YK M3 series, in particular, is equipped with advanced controls that enhance system performance while minimizing energy consumption. With features like variable speed drives and sophisticated control algorithms, these units optimize airflow and refrigerant use, significantly reducing operational costs.

Another notable aspect of the YK M3 M3 G4 is its robust refrigeration technology. Utilizing high-efficiency scroll compressors, these chillers deliver impressive cooling capacities while maintaining high energy efficiency ratings. Integrated with low GWP (Global Warming Potential) refrigerants, they meet modern environmental standards, ensuring compliance with regulations while promoting sustainability.

The YK LB LB G4 and YK SE SC J4 models further enhance York’s portfolio with their compact designs and lower installation footprints. These chillers are ideal for applications where space is at a premium. Additional features include advanced noise reduction technology, allowing for quieter operation compared to traditional HVAC systems, making them suitable for urban environments or buildings where noise control is a priority.

Furthermore, York's commitment to continuous innovation is evident in the incorporation of smart technology across its chiller series. Features such as connectivity options for monitoring and diagnostics through mobile apps or web interfaces empower users to maintain optimal system performance proactively. This connectivity aids in predictive maintenance, enabling timely interventions that extend equipment life and reliability.

Finally, all these high-efficiency chillers are backed by York's renowned service support network, ensuring that customers have access to expert assistance and maintenance services whenever needed. With their exceptional features, modern technologies, and commitment to sustainability, the York YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, and YK LB LB G4 THRU YK SE SC J4 models stand out as leaders in the commercial HVAC market, setting new standards for performance and efficiency.