York YK M3 M3 G4 operation manual Testing for Cooler and Condenser Tube Leaks

Page 56

recommends the use of this type of organization. The Dow Industries Service Division of the Dow Chemical Company, Tulsa, Oklahoma, with branches in principal cities is one of the most reliable of these companies.

TESTING FOR COOLER AND CONDENSER TUBE LEAKS

Cooler and condenser tube leaks in R-22 or R-134a systems may result in refrigerant leaking into the wa- ter circuit, or water leaking into the shell depending on the pressure levels. If refrigerant is leaking into the water, it can be detected at the liquid head vents after a period of shutdown. If water is leaking into the refrig- erant, system capacity and efficiency will drop off sharply. If a tube is leaking and water has entered the system, the cooler and condenser should be valved off from the rest of the water circuit and drained imme- diately to prevent severe rusting and corrosion. If a tube leak is indicated, the exact location of the leak may be determined as follows:

1.Remove the heads and listen at each section of tubes for a hissing sound that would indicate gas leakage. This will assist in locating the section of tubes to be further investigated. If the probable lo- cation of the leaky tubes has been determined, treat that section in the following manner (if the location is not definite, all the tubes will require investiga- tions).

2.Wash off both tube heads and the ends of all tubes with water.

NOTE: Do not use carbon tetrachloride for this pur- pose since its fumes give the same flame discoloration that the refrigerant does.

3.With nitrogen or dry air, blow out the tubes to clear them of traces of refrigerant laden moisture from the circulation water. As soon as the tubes are clear, a cork should be driven into each end of the tube. Repeat this with all of the other tubes in the sus- pected section or if necessary, with all the tubes in the cooler or condenser. Allow the cooler or con- denser to remain corked up to 12 to 24 hours be- fore proceeding. Depending upon the amount of leak- age, the corks may blow from the end of a tube, indicating the location of the leakage. If not, if will be necessary to make a very thorough test with the leak detector.

4.After the tubes have been corked for 12 to 24 hours, it is recommended that two men working at both ends of the cooler carefully test each tube – one man removing corks at one end and the other at the opposite end to remove corks and handle the leak detector. Start with the top row of tubes in the section being investigated, remove the corks at the ends of one tube simultaneously and insert the ex- ploring tube for 5 seconds – this should be long enough to draw into the detector any refrigerant gas that might have leaked through the tube walls. A fan placed at the end of the cooler opposite the detector will assure that any leakage will travel through the tube to the detector.

5.Mark any leaking tubes for later identification.

6.If any of the tube sheet joints are leaking, the leak should be indicated by the detector. If a tube sheet leak is suspected, its exact location may be found by using a soap solution. A continuous buildup of bubbles around a tube indicates a tube sheet leak.

56

YORK INTERNATIONAL

Image 56
Contents Centrifugal Liquid Chillers With Microcomputer Control CenterTable of Contents Nomenclature System Operation Description See Fig SectionDescription of System and Fundamentals of Operation Detail a Compressor Prerotation Vanes Capacity ControlSection Microcomputer Control Center Microcomputer Control Center and KeypadIntroduction Condenser Refrigerant LevelDisplaying System Parameters Control CenterOperation Psid = HOP LP Offset Pressure To Display Chilled Liquid TemperaturesTo Display OIL Pressure System Setpoints To Display Motor CurrentTo Display Operating Hours and Starts Counter See Programming System Setpoints, Displaying System Setpoints To Display Undervoltage setpoints Press Access Code key ProgrammingMicrocomputer Control Center Programming System SetpointsElectro-Mechanical Starter, refer to Fig Solid State Starter, refer to FigKeypad Programming Pull Down Demand Setpoint SetpointKeypad Programming Daily Schedule Setpoint Keypad Programming Holiday Service Keys PRE-ROTATION Vanes KeysOther Service Keys Pulldn Level = XXX% Setp = XXX% Actual = XXX%Operating Modes Compressor Switch Display MessagesSystem RUN Auto Vanes System Shutdown Messages When Control Center is in Remote mode MON Xxxx AM Evap Trans or Probe Error Therefore Function Jumper PositionThen MON Xxxx AM High Line Voltage MON Xxxx AM High Speed Drain Temp System Operating Procedures START-UP ProcedureOIL Heaters Checking the OIL Level in the OIL ReservoirSTART-UP Chiller OperationCondenser Water Temperature Control Chiller Starting Sequence & Shutdown SequenceEcwt LchwtChecking Operation Operating LOG SheetOperating Inspections See Section DailyWeekly QuarterlyNeed for Maintenance or Service Normal and Safety System ShutdownsSafety Shutdowns Cycling ShutdownsProlonged Shutdown START-UP After Prolonged ShutdownSystem Components Description System ComponentsGeneral CompressorCompressor Lubrication System See Fig Speed Increasing GearsSchematic Drawing YK Compressor Lubrication System OIL Heater Motor DrivelineHeat Exchangers Refrigerant Flow ControlVariable Speed Drive Optional Microcomputer Control Center See SectionSolid State Starter Optional Changing the Dehydrator Operational MaintenanceOIL Return System OIL Charging Procedure OIL ChargeTroubleshooting RiseLEP Operating Setpoints System After Service Operating Analysis Chart Symptom Abnormally LOW Suction PressureSymptom High Cooler Pressure Symptom no OIL Pressure When System Start Button PushedSymptom OIL Pump Vibrates or is Noisy Symptom OIL Pump Fails to Deliver OIL PressureSymptom Reduced OIL Pump Capacity OIL Pressure display keyConducting R-22 Pressure Test MaintenanceLeak Testing During Operation Vacuum Testing System PressuresVacuum Dehydration OperationRefrigerant Charge Refrigerant ChargingChecking the Refrigerant Charge During Unit Shutdown Handling Refrigerant for Dismantling and Repairs Megging the MotorMotor Stator Temperature and Insulation Resistances Condensers and Coolers Testing for Cooler and Condenser Tube Leaks Compressor Electrical ControlsPreventive Maintenance Pressure TestingCompressor Motor Cooler and CondenserElectrical Controls ALL Rights Reserved

YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4, YK M3 M3 G4 specifications

The York YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, and YK LB LB G4 THRU YK SE SC J4 represent a sophisticated line of HVAC systems engineered for modern commercial applications. These models are celebrated for their innovative designs, energy efficiency, and advanced features, making them a preferred choice among facility managers and building owners.

One of the standout characteristics of the York YK series is its modular construction, which provides unparalleled flexibility in system configuration. This design allows for easy upgrades and expansions as building demands evolve. The YK M3 series, in particular, is equipped with advanced controls that enhance system performance while minimizing energy consumption. With features like variable speed drives and sophisticated control algorithms, these units optimize airflow and refrigerant use, significantly reducing operational costs.

Another notable aspect of the YK M3 M3 G4 is its robust refrigeration technology. Utilizing high-efficiency scroll compressors, these chillers deliver impressive cooling capacities while maintaining high energy efficiency ratings. Integrated with low GWP (Global Warming Potential) refrigerants, they meet modern environmental standards, ensuring compliance with regulations while promoting sustainability.

The YK LB LB G4 and YK SE SC J4 models further enhance York’s portfolio with their compact designs and lower installation footprints. These chillers are ideal for applications where space is at a premium. Additional features include advanced noise reduction technology, allowing for quieter operation compared to traditional HVAC systems, making them suitable for urban environments or buildings where noise control is a priority.

Furthermore, York's commitment to continuous innovation is evident in the incorporation of smart technology across its chiller series. Features such as connectivity options for monitoring and diagnostics through mobile apps or web interfaces empower users to maintain optimal system performance proactively. This connectivity aids in predictive maintenance, enabling timely interventions that extend equipment life and reliability.

Finally, all these high-efficiency chillers are backed by York's renowned service support network, ensuring that customers have access to expert assistance and maintenance services whenever needed. With their exceptional features, modern technologies, and commitment to sustainability, the York YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, and YK LB LB G4 THRU YK SE SC J4 models stand out as leaders in the commercial HVAC market, setting new standards for performance and efficiency.