York YK M3 M3 G4 System Operating Procedures, OIL Heaters Checking the OIL Level in the OIL

Page 30

SECTION 3

SYSTEM OPERATING PROCEDURES

WARNING

OIL HEATERS

CHECKING THE OIL LEVEL IN THE OIL

If the oil heater is de-energized during a shut-

RESERVOIR

 

down period, they must be energized for 12 hours

Proper operating oil level – the middle of the up-

prior to starting compressor, or remove all oil and

per sight glass.

recharge compressor with new oil. (See “Charg-

 

ing Unit With Oil”, page 43.)

If the oil is excessively high after start-up, the

 

NOTE: The oil heater is thermostatically controlled

excess oil may be drained from the oil filter drain

valve while the compressor is running.

and remains energized as long as the

 

fused disconnect switch to the starter or

If oil level is low, oil should be added to the com-

turbo-modulator is energized.

pressor. (See “Charging Unit With Oil”, page 43.)

 

 

START-UP PROCEDURE

PRE-STARTING

Prior to starting the chiller, observe the MicroCom- puter Control Center. Make sure the display reads

SYSTEM READY TO START .

To pre-start the chiller, use the following procedure:

1.Oil Heater – The oil heater must be energized for 12 hours prior to starting the chiller. The unit will not start if the oil is less than 71°F. If not possible the compressor oil should be drained and new oil must be charged into the oil sump. (See “Charging Unit With Oil”, page 43.)

2.Oil Pump – To check, press and release the MANUAL OIL PUMP key under Service on the Control Center. The oil pump will run for 10 min- utes and shut down. Press and release the MANUAL OIL PUMP key to stop the operation of the oil pump for less than 10 minutes of operation.

3.Pre-Rotation Vanes – To perform this test the starter interlock terminals 3 and 4 must be jumpered to allow vanes to open (remove the jumper after test). Make sure the Control Center is in the SERVICE mode, then press the prerotation vanes OPEN and CLOSE keys to observe the operation of the prerotation vanes. The Control Center supplies a signal to operate the prerotation vanes. The movement of the vanes will be dis-

played on the Control Center. The display readout is active whenever power is supplied to the Con- trol Center. Return from the SERVICE mode to LOCAL, PROGRAM, or REMOTE mode to suit the method of operation selected for the chiller application. Refer to “Section 2”.

4.% Current Limit – Press the % CURRENT LIMIT setpoint key on the Control Center. The “Display”

should read CURRENT LIMIT = 100% FLA on (Solid State Starter units only, the display is

CURRENT LIMIT = 100% FLA, MTR CUR = XXXX FLA )

if the Control Center was not programmed. If the setpoint is not 100% and was predetermined for the job application the Control Center should be programmed to that specification. To program, re- fer to “Section 2”.

5.All Control Center setpoints should be programmed before the chiller is started. (Refer to “Section 2”.) Prior to start, the clock must be programmed for the proper day and time. Any setpoints which are desired to be changed may be programmed. If not programmed the “default” value setpoints are as follows:

LCWT = 45°F

%Current Limit = 100% FLA Pulldown Demand = None Clock = Sun 12:00 A.M. Daily Schedule = None Holiday = None

Remote Reset Temp. Range = 20°F Data Logger = No operation

30

YORK INTERNATIONAL

Image 30
Contents Centrifugal Liquid Chillers With Microcomputer Control CenterTable of Contents Nomenclature Section Description of System and Fundamentals of OperationSystem Operation Description See Fig Detail a Compressor Prerotation Vanes Capacity ControlSection Microcomputer Control Center Microcomputer Control Center and KeypadIntroduction Condenser Refrigerant LevelControl Center OperationDisplaying System Parameters To Display Chilled Liquid Temperatures To Display OIL PressurePsid = HOP LP Offset Pressure To Display Motor Current To Display Operating Hours and Starts CounterSystem Setpoints See Programming System Setpoints, Displaying System Setpoints To Display Undervoltage setpoints Microcomputer Control Center Press Access Code keyProgramming Programming System SetpointsElectro-Mechanical Starter, refer to Fig Solid State Starter, refer to FigKeypad Programming Pull Down Demand Setpoint SetpointKeypad Programming Daily Schedule Setpoint Keypad Programming Holiday Service Keys PRE-ROTATION Vanes KeysOther Service Keys Pulldn Level = XXX% Setp = XXX% Actual = XXX%Operating Modes Compressor Switch Display MessagesSystem RUN Auto Vanes System Shutdown Messages When Control Center is in Remote mode MON Xxxx AM Evap Trans or Probe Error Function Jumper Position ThenTherefore MON Xxxx AM High Line Voltage MON Xxxx AM High Speed Drain Temp OIL Heaters Checking the OIL Level in the OIL System Operating ProceduresSTART-UP Procedure ReservoirSTART-UP Chiller OperationCondenser Water Temperature Control Chiller Starting Sequence & Shutdown SequenceChecking Operation EcwtLchwt Operating LOG SheetWeekly Operating Inspections See SectionDaily QuarterlySafety Shutdowns Need for Maintenance or ServiceNormal and Safety System Shutdowns Cycling ShutdownsProlonged Shutdown START-UP After Prolonged ShutdownSystem Components Description System ComponentsCompressor Lubrication System See Fig GeneralCompressor Speed Increasing GearsSchematic Drawing YK Compressor Lubrication System Heat Exchangers OIL HeaterMotor Driveline Refrigerant Flow ControlMicrocomputer Control Center See Section Solid State Starter OptionalVariable Speed Drive Optional Operational Maintenance OIL Return SystemChanging the Dehydrator OIL Charging Procedure OIL ChargeTroubleshooting RiseLEP Operating Setpoints System After Service Symptom High Cooler Pressure Operating Analysis ChartSymptom Abnormally LOW Suction Pressure Symptom no OIL Pressure When System Start Button PushedSymptom Reduced OIL Pump Capacity Symptom OIL Pump Vibrates or is NoisySymptom OIL Pump Fails to Deliver OIL Pressure OIL Pressure display keyMaintenance Leak Testing During OperationConducting R-22 Pressure Test Vacuum Testing System PressuresVacuum Dehydration OperationRefrigerant Charging Checking the Refrigerant Charge During Unit ShutdownRefrigerant Charge Handling Refrigerant for Dismantling and Repairs Megging the MotorMotor Stator Temperature and Insulation Resistances Condensers and Coolers Testing for Cooler and Condenser Tube Leaks Compressor Electrical ControlsCompressor Motor Preventive MaintenancePressure Testing Cooler and CondenserElectrical Controls ALL Rights Reserved

YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4, YK M3 M3 G4 specifications

The York YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, and YK LB LB G4 THRU YK SE SC J4 represent a sophisticated line of HVAC systems engineered for modern commercial applications. These models are celebrated for their innovative designs, energy efficiency, and advanced features, making them a preferred choice among facility managers and building owners.

One of the standout characteristics of the York YK series is its modular construction, which provides unparalleled flexibility in system configuration. This design allows for easy upgrades and expansions as building demands evolve. The YK M3 series, in particular, is equipped with advanced controls that enhance system performance while minimizing energy consumption. With features like variable speed drives and sophisticated control algorithms, these units optimize airflow and refrigerant use, significantly reducing operational costs.

Another notable aspect of the YK M3 M3 G4 is its robust refrigeration technology. Utilizing high-efficiency scroll compressors, these chillers deliver impressive cooling capacities while maintaining high energy efficiency ratings. Integrated with low GWP (Global Warming Potential) refrigerants, they meet modern environmental standards, ensuring compliance with regulations while promoting sustainability.

The YK LB LB G4 and YK SE SC J4 models further enhance York’s portfolio with their compact designs and lower installation footprints. These chillers are ideal for applications where space is at a premium. Additional features include advanced noise reduction technology, allowing for quieter operation compared to traditional HVAC systems, making them suitable for urban environments or buildings where noise control is a priority.

Furthermore, York's commitment to continuous innovation is evident in the incorporation of smart technology across its chiller series. Features such as connectivity options for monitoring and diagnostics through mobile apps or web interfaces empower users to maintain optimal system performance proactively. This connectivity aids in predictive maintenance, enabling timely interventions that extend equipment life and reliability.

Finally, all these high-efficiency chillers are backed by York's renowned service support network, ensuring that customers have access to expert assistance and maintenance services whenever needed. With their exceptional features, modern technologies, and commitment to sustainability, the York YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, and YK LB LB G4 THRU YK SE SC J4 models stand out as leaders in the commercial HVAC market, setting new standards for performance and efficiency.