York YK M3 M3 G4 Preventive Maintenance, Compressor Motor, Pressure Testing, Cooler and Condenser

Page 58

SECTION 8

PREVENTIVE MAINTENANCE

It is the responsibility of the owner to provide the nec- essary daily, monthy and yearly maintenance require- ments of the system. IMPORTANT – If a unit failure occurs due to improper maintenance during the war- ranty period; YORK will not be liable for costs incurred to return the system to satisfactory operation.

In any operating system it is most important to provide a planned maintenance and inspection of its function- ing parts to keep it operating at its peak efficiency. Therefore, the following maintenance should be per- formed when prescribed.

COMPRESSOR

1.Oil Filter – The oil filter must be changed when the oil pressure drops 30% or semi-annually if not re- quired earlier.

When the oil filter is changed, it should be inspected thoroughly for any aluminum particles which would indicate possible bearing wear. If aluminum particles are found this should be brought to the attention of the nearest YORK office for their further investiga- tion and recommendations.

2.Oil Changing – The oil in the compressor must be changed annually or earlier if it becomes dark or cloudy.

COMPRESSOR MOTOR

1.Check motor mounting screws frequently to insure tightness.

2.Meg motor windings annually to check for deterio- ration of windings.

PRESSURE TESTING

The unit should be pressure tested annually. Any leaks found must be repaired immediately. Air and moisture are the worst enemies of these systems and experi- ence has shown that units which are maintained tight, are systems that provide trouble free efficient opera- tion.

COOLER AND CONDENSER

The major portion of maintenance on the condenser and cooler will deal with the maintaining the water side of the condenser and cooler in a clean condition.

The use of untreated water in cooling towers, closed water systems, etc. frequently results in one or more of the following:

1.Scale Formation.

2.Corrosion or Rusting.

3.Slime and Algae Formation.

It is therefore to the benefit of the user to provide for proper water treatment to provide for a longer and more economical life of the equipment. The following recom- mendation should be followed in determining the con- dition of the water side of the condenser and cooler tubes.

1.The condenser tubes should be cleaned annually or earlier if conditions warrant. If the temperature difference between the water off the condenser and the condenser liquid temperature is more than 4° greater than the difference recorded on a new unit, it is a good indication that the condenser tubes re- quire cleaning.They should be cleaned as instructed on pages 38 to 39 of this manual.

2.The cooler tubes under normal circumstances will not require cleaning. If however the temperature dif- ference between the refrigerant and the chilled wa- ter increases slowly over the operating season, it is an indication that the cooler tubes may be fouling or that there may be a water by-pass in the water box requiring gasket relacement or refrigerant may have leaked from the chiller.

OIL RETURN SYSTEM

1.Change the dehydrator in the oil return system semi- annually or earlier if the oil return system fails to operate.

2.When the dehydrator is changed, the nozzle of the

58

YORK INTERNATIONAL

Image 58
Contents Centrifugal Liquid Chillers With Microcomputer Control CenterTable of Contents Nomenclature Description of System and Fundamentals of Operation SectionSystem Operation Description See Fig Detail a Compressor Prerotation Vanes Capacity ControlSection Microcomputer Control Center Microcomputer Control Center and KeypadIntroduction Condenser Refrigerant LevelOperation Control CenterDisplaying System Parameters To Display OIL Pressure To Display Chilled Liquid TemperaturesPsid = HOP LP Offset Pressure To Display Operating Hours and Starts Counter To Display Motor CurrentSystem Setpoints See Programming System Setpoints, Displaying System Setpoints To Display Undervoltage setpoints Microcomputer Control Center Press Access Code keyProgramming Programming System SetpointsElectro-Mechanical Starter, refer to Fig Solid State Starter, refer to FigKeypad Programming Pull Down Demand Setpoint SetpointKeypad Programming Daily Schedule Setpoint Keypad Programming Holiday Service Keys PRE-ROTATION Vanes KeysOther Service Keys Pulldn Level = XXX% Setp = XXX% Actual = XXX%Operating Modes Compressor Switch Display MessagesSystem RUN Auto Vanes System Shutdown Messages When Control Center is in Remote mode MON Xxxx AM Evap Trans or Probe Error Then Function Jumper PositionTherefore MON Xxxx AM High Line Voltage MON Xxxx AM High Speed Drain Temp OIL Heaters Checking the OIL Level in the OIL System Operating ProceduresSTART-UP Procedure ReservoirSTART-UP Chiller OperationCondenser Water Temperature Control Chiller Starting Sequence & Shutdown SequenceChecking Operation EcwtLchwt Operating LOG SheetWeekly Operating Inspections See SectionDaily QuarterlySafety Shutdowns Need for Maintenance or ServiceNormal and Safety System Shutdowns Cycling ShutdownsProlonged Shutdown START-UP After Prolonged ShutdownSystem Components Description System ComponentsCompressor Lubrication System See Fig GeneralCompressor Speed Increasing GearsSchematic Drawing YK Compressor Lubrication System Heat Exchangers OIL HeaterMotor Driveline Refrigerant Flow ControlSolid State Starter Optional Microcomputer Control Center See SectionVariable Speed Drive Optional OIL Return System Operational MaintenanceChanging the Dehydrator OIL Charging Procedure OIL ChargeTroubleshooting RiseLEP Operating Setpoints System After Service Symptom High Cooler Pressure Operating Analysis ChartSymptom Abnormally LOW Suction Pressure Symptom no OIL Pressure When System Start Button PushedSymptom Reduced OIL Pump Capacity Symptom OIL Pump Vibrates or is NoisySymptom OIL Pump Fails to Deliver OIL Pressure OIL Pressure display keyLeak Testing During Operation MaintenanceConducting R-22 Pressure Test Vacuum Testing System PressuresVacuum Dehydration OperationChecking the Refrigerant Charge During Unit Shutdown Refrigerant ChargingRefrigerant Charge Handling Refrigerant for Dismantling and Repairs Megging the MotorMotor Stator Temperature and Insulation Resistances Condensers and Coolers Testing for Cooler and Condenser Tube Leaks Compressor Electrical ControlsCompressor Motor Preventive MaintenancePressure Testing Cooler and CondenserElectrical Controls ALL Rights Reserved

YK M3 M3 G4 THRU YK S6 S4 J2, YK LB LB G4 THRU YK SE SC J4, YK M3 M3 G4 specifications

The York YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, and YK LB LB G4 THRU YK SE SC J4 represent a sophisticated line of HVAC systems engineered for modern commercial applications. These models are celebrated for their innovative designs, energy efficiency, and advanced features, making them a preferred choice among facility managers and building owners.

One of the standout characteristics of the York YK series is its modular construction, which provides unparalleled flexibility in system configuration. This design allows for easy upgrades and expansions as building demands evolve. The YK M3 series, in particular, is equipped with advanced controls that enhance system performance while minimizing energy consumption. With features like variable speed drives and sophisticated control algorithms, these units optimize airflow and refrigerant use, significantly reducing operational costs.

Another notable aspect of the YK M3 M3 G4 is its robust refrigeration technology. Utilizing high-efficiency scroll compressors, these chillers deliver impressive cooling capacities while maintaining high energy efficiency ratings. Integrated with low GWP (Global Warming Potential) refrigerants, they meet modern environmental standards, ensuring compliance with regulations while promoting sustainability.

The YK LB LB G4 and YK SE SC J4 models further enhance York’s portfolio with their compact designs and lower installation footprints. These chillers are ideal for applications where space is at a premium. Additional features include advanced noise reduction technology, allowing for quieter operation compared to traditional HVAC systems, making them suitable for urban environments or buildings where noise control is a priority.

Furthermore, York's commitment to continuous innovation is evident in the incorporation of smart technology across its chiller series. Features such as connectivity options for monitoring and diagnostics through mobile apps or web interfaces empower users to maintain optimal system performance proactively. This connectivity aids in predictive maintenance, enabling timely interventions that extend equipment life and reliability.

Finally, all these high-efficiency chillers are backed by York's renowned service support network, ensuring that customers have access to expert assistance and maintenance services whenever needed. With their exceptional features, modern technologies, and commitment to sustainability, the York YK M3 M3 G4, YK M3 M3 G4 THRU YK S6 S4 J2, and YK LB LB G4 THRU YK SE SC J4 models stand out as leaders in the commercial HVAC market, setting new standards for performance and efficiency.