York HFC-410A manual VAV Supply AIR Pressure Control, Copper-Fin Evaporator and Condenser Coil

Page 10

FORM 100.50-EG5 (108)

Application Data (continued)

VAV SUPPLY AIR PRESSURE CONTROL

Traditional packaged rooftop systems use inlet guide vanes (IGVs) for duct static pressure control. These control supply duct pressure by modulating dampers (introducing losses and inefficiencies) on the inlet of the fan, open and closed. YORK’s variable frequency drives (VFDs) offer superior fan speed control and quieter, energy efficient operation.

For VAV applications, the YORK Eco2 unit uses a VFD to modulate fan speed and maintain a constant duct static pressure. VFDs offer superior control over the operation of the unit at part load, and offer the additional benefits of quieter and more efficient operation when compared to IGV.

FIG. 1. TRADITIONAL OVERHEAD VAV AIR DELIVERY SYSTEM

HARSH ENVIRONMENTS – CONDENSER AND EVAPORATOR COIL PROTECTION

For harsh environmental conditions such as seashore applications, YORK offers three types of coil protection: copper fin material, black fin and Technicoat coatings. YORK recommends that for corrosive environments that copper fins be used to protect the evaporator and/or condenser coils. In areas where chemicals that can corrode copper are present, such as ammonia, YORK recommends that the black fin or Technicoat coating be used for maximum protection.

Copper-Fin Evaporator and Condenser Coil

– Copper fins can be used instead of aluminum for additional corrosion protection. However, it is not suitable for areas that are subject to acid rain or exposed to ammonia.

Pre-Coated Condenser Fins – Black fin coating (yellow fin for evaporator fins) is pre-coated appli- cation epoxy on aluminum fin stock to guard from corrosive agents and insulate against galvanic

potential. It is used for mild seashore or industrial locations. This can provide corrosion resistance comparable to copper fin coils in typical seashore locations.

Post-Coated Condenser Fins – Technicoat (a post-coated application of epoxy) can be used for seashore and other corrosive applications with the exception of strong alkaloides, oxidizers, wet bro- mide, chlorine and fluorine in concentrations greater than 100 ppm. Any of the above suitable options should be selected based on the particular project design parameters and related environmental fac- tors. The application should be further reviewed and approved by the consulting engineer or owner based on their knowledge of the job site conditions.

BUILDING PRESSURE CONTROL SYSTEMS

Building pressure control systems are often neces- sary when economizers are used to bring in outdoor air. Without proper building exhaust, the building may become over pressurized. The pressure control system maintains the proper building pressure by expelling the appropriate amount of air from the building.

Exhaust/relief fans – In this application, a powered exhaust fan may be suitable, however careful consid- eration of the fan type is necessary. YORK offers a centrifugal powered exhaust fan to perform this function. Some manufacturers use a propeller exhaust fan, which cannot handle the static pressure requirements.

For systems with moderate to low return static pressure, an exhaust fan is recommended. The benefit of the ex- haust fan is that it does not run all of the time, and may facilitate compliance with the ASHRAE 90.1 fan motor horsepower requirement.

The exhaust fan operates in parallel with the supply fan. In this arrangement, the supply fan handles the full static pressure requirements of the system. For normal building pressure control, the exhaust fan operates to draw air from the return plenum and exhaust it out of the building.

The exhaust fan configuration is available in two forms, modulating and non-modulating. Modulating is the most common and recommended for the majority of applica- tions, while non-modulating should be used with in only certain circumstances.

In the modulating exhaust system, the volume of airflow exhausted from the building is proportional to the enter- ing volume of outside air. Control is accomplished via either a discharge damper or a variable-frequencydrive (VFD). YORK recommends the use of a VFD to reduce energy consumption, sound levels and improved reli- ability due to fewer moving parts.

10

JOHNSON CONTROLS

Image 10
Contents Compliant MEA Ashrae90.1 231-02-ELower total cost of ownership Indoor air quality features for the indoor environ- mentIntroduction Simplicity Elite controller OptionTable of Contents Features and Benefits Outside AIR Damper Options CommunicationsFilter Options Relief SystemEvaporator Section Condenser Features and OptionsCabinet Features and Options Roof CurbsAccessories General Unit PlacementApplication Data LocationHorizontal Applications Duct ConsiderationsUnit Orientation EconomizerCopper-Fin Evaporator and Condenser Coil VAV Supply AIR Pressure ControlHarsh Environments Condenser and Evaporator Coil Protection Building Pressure Control SystemsAcoustical Considerations This page intentionally left blank Nomenclature YorkPhysical Data Physical DataMinimum OA Temp for Mech. Cig Model050 051 060 061 Gas Furnaces Low Ambient Option Min. OA Temp Minimum Airflow HeatingEER ModelIplv Ieer Model Supply Blower Cooling Only Gas Heat TypeAltitude and Temperature Corrections Air Altitude feet TempALTITUDE/TEMPERATURE Conversion Factor Cooling Performance Data 050 Model Cooling Performance DATA* 50 TON Standard CapacityCooling Performance Data 051 Model Cooling Performance DATA* 55 TON High CapacityCooling Performance Data 060 Model Cooling Performance DATA* 60 TON Standard CapacityCooling Performance Data 061 Model Cooling Performance DATA* 65 TON High CapacityTotal Static Pressure inches of water column Supply Fan DataCFM STD. AIR BHP RPM Component Static Pressure Drops CFMCFM STD Exhaust Fan DataExhaust FAN Motor Sizing Instructions AIR BHP RPMLoad Definitions Electrical Service SizingElectrical Data RLA LRAFans FLAUnit Size Quantity AmpsGAS Heating Operation Unoccupied / Occupied SwitchingControls Morning WARM-UPVentilation Control Sequences Economizer OperationExhaust Control Sequences Supply FAN Operation Smoke Purge SequenceLOW-AMBIENT/HEAD-PRESSURE Control Operation Cooling OperationDual-Point TB POWER-SUPPLY-CONDUCTOR Size RangeHeating Operation Supply Single-PointGeneral Arrangement General Arrangement DrawingDrawing Side Supply / Rear ReturnDrawings TOP ViewCurb Layout Drawing General Arrangement DrawingUnit Weights Unit Corner Weights Guide Specifications Product Specification WarrantiesEquipment Unit ConstructionFilter Section Evaporator SectionDischarge Plenum Supply Fan SectionCondenser Section Controls Simplicity Elite Execution InstallationInspection and START-UP Supervision ALL Rights Reserved