York HFC-410A manual Unit Weights

Page 36

Unit Weights

 

 

 

FORM 100.50-EG5 (108)

 

 

 

 

 

TABLE 23 – UNIT WEIGHTS

 

 

 

 

 

Model

050

051

060

 

061

Basic Unit*

7433

7433

7800

 

7819

Economizers

 

 

 

 

 

No Outside Air

240

240

240

 

240

25% Outside Air Fixed Position Maual Damper

446

446

446

 

446

25% Outside Air 2 Position Actuated Damper

476

476

476

 

476

Full Modulation with Minimum Position

476

476

476

 

476

Power Exhausts

 

 

 

 

 

Fan, Motor, Modulating Damper and Hood

501

501

501

 

501

Fan, Motor, VFD, Barometric Damper and Hood

506

506

506

 

506

Gas Heat

 

 

 

 

 

375 MBH

162

162

162

 

162

750 MBH

324

324

324

 

324

1125 MBH (Bottom Discharge)

486

486

486

 

486

Options

 

 

 

 

 

Open Perimeter Curb

544

544

544

 

544

Condenser Coil Wire Guard

64

64

64

 

64

Copper Evaporator Coils (additional)

312

312

416

 

416

Copper Condenser Coils (additional)

516

516

773

 

773

12” Rigid Filters (additional)

319

319

319

 

319

*Unit includes FC fan w/ 20 hp motor, VFD and 2” throwaway filters

92

Y

Center of Gravity

BC

Condenser

Coil End

AD

X 339

TABLE 24 – UNIT CENTER OF GRAVITY

Model

 

050

 

051

X

 

Y

X

 

Y

 

 

 

Basic Unit

184.1

 

50.2

184.1

 

50.2

Basic Unit w/ Econ.

191.0

 

49.9

191.0

 

49.9

Basic Unit w/ Econ. & Heating

187.4

 

50.0

187.4

 

50.0

Basic Unit w/ Econ. & Heating & Power Exhaust

194.9

 

49.5

194.9

 

49.5

Model

 

060

 

061

X

 

Y

X

 

Y

 

 

 

Basic Unit

179.8

 

49.9

179.6

 

50.0

Basic Unit w/ Econ.

186.7

 

49.7

186.5

 

49.7

Basic Unit w/ Econ. & Heating

183.5

 

49.8

183.2

 

49.8

Basic Unit w/ Econ. & Heating & Power Exhaust

190.9

 

49.3

190.7

 

49.3

36

JOHNSON CONTROLS

Image 36
Contents Ashrae 90.1Compliant MEA 231-02-EIndoor air quality features for the indoor environ- ment IntroductionLower total cost of ownership Simplicity Elite controller OptionTable of Contents Features and Benefits Communications Filter OptionsOutside AIR Damper Options Relief SystemCondenser Features and Options Cabinet Features and OptionsEvaporator Section Roof CurbsAccessories Unit Placement Application DataGeneral LocationDuct Considerations Unit OrientationHorizontal Applications EconomizerVAV Supply AIR Pressure Control Harsh Environments Condenser and Evaporator Coil ProtectionCopper-Fin Evaporator and Condenser Coil Building Pressure Control SystemsAcoustical Considerations This page intentionally left blank Nomenclature YorkPhysical Data Physical DataModel 050 051 060 061 Gas FurnacesMinimum OA Temp for Mech. Cig Low Ambient Option Min. OA Temp Minimum Airflow HeatingModel Iplv IeerEER Model Supply Blower Cooling Only Gas Heat TypeAltitude and Temperature Corrections Air Altitude feet TempALTITUDE/TEMPERATURE Conversion Factor Cooling Performance Data 050 Model Cooling Performance DATA* 50 TON Standard CapacityCooling Performance Data 051 Model Cooling Performance DATA* 55 TON High CapacityCooling Performance Data 060 Model Cooling Performance DATA* 60 TON Standard CapacityCooling Performance Data 061 Model Cooling Performance DATA* 65 TON High CapacitySupply Fan Data Total Static Pressure inches of water columnCFM STD. AIR BHP RPM Component Static Pressure Drops CFMExhaust Fan Data Exhaust FAN Motor Sizing InstructionsCFM STD AIR BHP RPMElectrical Service Sizing Electrical DataLoad Definitions RLA LRAFLA Unit Size QuantityFans AmpsUnoccupied / Occupied Switching ControlsGAS Heating Operation Morning WARM-UPEconomizer Operation Ventilation Control SequencesExhaust Control Sequences Smoke Purge Sequence LOW-AMBIENT/HEAD-PRESSURE Control OperationSupply FAN Operation Cooling OperationPOWER-SUPPLY-CONDUCTOR Size Range Heating OperationDual-Point TB Supply Single-PointGeneral Arrangement General Arrangement DrawingDrawing Side Supply / Rear ReturnDrawings TOP ViewCurb Layout Drawing General Arrangement DrawingUnit Weights Unit Corner Weights Guide Specifications Warranties EquipmentProduct Specification Unit ConstructionFilter Section Evaporator SectionSupply Fan Section Discharge PlenumCondenser Section Controls Simplicity Elite Installation ExecutionInspection and START-UP Supervision ALL Rights Reserved