Electrical Data

ELECTRICAL SERVICE SIZING

In order to use the electrical service required for the cool- ing-only Eco2 rooftop, use the appropriate calculations listed below from U.L. 1995. Based on the configuration of the rooftop, the calculations will yield different MCA (minimum circuit ampacity), and MOP (maximum over- current protection).

Using the following load definitions and calculations, determine the correct electrical sizing for your unit. All concurrent load conditions must be considered in the calculations, and you must use the highest value for any combination of loads.

Load Definitions:

LOAD1 is the current of the largest motor – com- pressor or fan motor.

LOAD2 is the sum of the remaining motor currents that may run concurrently with LOAD1.

TABLE 16 – COMPRESSOR ELECTRICAL DATA

LOAD3 is the current of the electric heaters – zero for cooling-only units.

LOAD4 is the sum of any remaining currents greater than or equal to 1.0 amp.

Use the following calculations to determine MCA and MOP for units supplied with a single-point power con- nection:

MCA = (1.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4 MOP = (2.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4

If the MOP does not equal a standard current rating of an overcurrent protective device, then the marked maximum rating is to be the next lower standard rating. However, if the device selected for MOP is less than the MCA, then select the lowest standard maximum fuse size greater than or equal to the MCA.

 

 

 

 

 

Nominal Voltage

 

 

 

Model

Compressor

Model

208-230/3/60

460/3/60

 

575/3/60

 

 

 

 

RLA*

LRA

RLA*

 

LRA

RLA*

 

LRA

 

1A

ZP120

33.3

239

17.9

 

125

12.8

 

80

050

1B

ZP137

48.0

245

18.6

 

125

14.7

 

100

2A

ZP121

33.3

239

17.9

 

125

12.8

 

80

 

 

 

 

2B

ZP137

48.0

245

18.6

 

125

14.7

 

100

 

1A

ZP137

48.0

245

18.6

 

125

14.7

 

100

051

1B

ZP137

48.0

245

18.6

 

125

14.7

 

100

2A

ZP137

48.0

245

18.6

 

125

14.7

 

100

 

 

 

 

2B

ZP137

48.0

245

18.6

 

125

14.7

 

100

 

1A

ZP137

48.0

245

18.6

 

125

14.7

 

100

060

1B

ZP182

55.7

340

26.9

 

172

23.7

 

132

2A

ZP137

48.0

245

18.6

 

125

14.7

 

100

 

 

 

 

2B

ZP182

55.7

340

26.9

 

172

23.7

 

132

 

1A

ZP154

51.3

300

22.4

 

150

19.8

 

109

061

1B

ZP182

55.7

340

25.0

 

172

23.7

 

132

2A

ZP137

48.0

245

18.6

 

125

14.7

 

100

 

 

 

 

2B

ZP182

55.7

340

25.0

 

172

23.7

 

132

TABLE 17 – POWER SUPPLY VOLTAGE LIMITS

Power Supply

Minimum Voltage

Maximum Voltage

208V/3Ph/60Hz

187

228

230V/3Ph/60Hz

207

253

460V/3Ph/60Hz

414

506

575V/3Ph/60Hz

518

632

26

JOHNSON CONTROLS

Image 26
Contents Compliant MEA Ashrae90.1 231-02-ELower total cost of ownership Indoor air quality features for the indoor environ- mentIntroduction Simplicity Elite controller OptionTable of Contents Features and Benefits Outside AIR Damper Options CommunicationsFilter Options Relief SystemEvaporator Section Condenser Features and OptionsCabinet Features and Options Roof CurbsAccessories General Unit PlacementApplication Data LocationHorizontal Applications Duct ConsiderationsUnit Orientation EconomizerCopper-Fin Evaporator and Condenser Coil VAV Supply AIR Pressure ControlHarsh Environments Condenser and Evaporator Coil Protection Building Pressure Control SystemsAcoustical Considerations This page intentionally left blank Nomenclature YorkPhysical Data Physical DataMinimum OA Temp for Mech. Cig Model050 051 060 061 Gas Furnaces Low Ambient Option Min. OA Temp Minimum Airflow HeatingEER ModelIplv Ieer Model Supply Blower Cooling Only Gas Heat TypeAltitude and Temperature Corrections Air Altitude feet TempALTITUDE/TEMPERATURE Conversion Factor Cooling Performance Data 050 Model Cooling Performance DATA* 50 TON Standard CapacityCooling Performance Data 051 Model Cooling Performance DATA* 55 TON High CapacityCooling Performance Data 060 Model Cooling Performance DATA* 60 TON Standard CapacityCooling Performance Data 061 Model Cooling Performance DATA* 65 TON High CapacityCFM STD. AIR BHP RPM Supply Fan DataTotal Static Pressure inches of water column Component Static Pressure Drops CFMCFM STD Exhaust Fan DataExhaust FAN Motor Sizing Instructions AIR BHP RPMLoad Definitions Electrical Service SizingElectrical Data RLA LRAFans FLAUnit Size Quantity AmpsGAS Heating Operation Unoccupied / Occupied SwitchingControls Morning WARM-UPExhaust Control Sequences Economizer OperationVentilation Control Sequences Supply FAN Operation Smoke Purge SequenceLOW-AMBIENT/HEAD-PRESSURE Control Operation Cooling OperationDual-Point TB POWER-SUPPLY-CONDUCTOR Size RangeHeating Operation Supply Single-PointGeneral Arrangement General Arrangement DrawingDrawing Side Supply / Rear ReturnDrawings TOP ViewCurb Layout Drawing General Arrangement DrawingUnit Weights Unit Corner Weights Guide Specifications Product Specification WarrantiesEquipment Unit ConstructionFilter Section Evaporator SectionCondenser Section Supply Fan SectionDischarge Plenum Controls Simplicity Elite Inspection and START-UP Supervision InstallationExecution ALL Rights Reserved