York HFC-410A Supply Fan Data, Total Static Pressure inches of water column, Cfm Std. Air Bhp Rpm

Page 23

FORM 100.50-EG5 (108)

Supply Fan Data

TABLE 12 – 28" x 28" FORWARD-CURVED FAN

Total Static Pressure (inches of water column)

CFM

 

1.0

 

2.0

 

3.0

4.0

 

5.0

 

 

6.0

STD. AIR

BHP

 

RPM

BHP

 

RPM

BHP

 

RPM

BHP

 

RPM

BHP

 

RPM

BHP

 

RPM

12000

 

 

 

 

 

 

12.3

 

639

16.8

 

730

21.5

 

808

26.4

 

879

14000

 

 

 

 

 

 

14.3

 

642

19.2

 

738

24.3

 

818

29.7

 

890

16000

 

 

 

10.8

 

528

16.2

 

642

21.8

 

742

27.3

 

826

33.2

 

900

18000

 

 

 

12.7

 

537

18

 

643

24.4

 

742

30.6

 

829

36.8

 

906

20000

10.4

 

447

15

 

550

20.3

 

648

26.8

 

742

33.9

 

830

40.8

 

908

22000

12.9

 

471

17.6

 

566

23.3

 

657

29.4

 

745

36.9

 

830

 

 

 

24000

15.7

 

496

20.8

 

586

26.8

 

700

33

 

752

40

 

832

 

 

 

26000

19.1

 

522

24.5

 

607

30.5

 

686

37.3

 

762

 

 

 

 

 

 

TABLE 13 – 28" AIRFOIL FAN

Total Static Pressure (inches of water column)

CFM

 

1.0

 

2.0

 

3.0

 

4.0

5.0

 

 

6.0

STD. AIR

BHP

 

RPM

BHP

 

RPM

BHP

 

RPM

BHP

 

RPM

BHP

 

RPM

BHP

 

RPM

12000

 

 

 

 

 

 

 

 

 

12.6

 

1133

15.9

 

1241

19.5

 

1343

14000

5.2

 

806

8.1

 

947

11.4

 

1068

14.8

 

1177

18.4

 

1278

22.1

 

1374

16000

6.8

 

877

10

 

1011

13.5

 

1125

17.3

 

1228

21.2

 

1324

25.2

 

1415

18000

8.7

 

951

12.3

 

1077

16

 

1186

20.1

 

1285

24.3

 

1376

28.7

 

1462

20000

10.9

 

1027

15

 

1146

19

 

1251

23.3

 

1345

27.9

 

1433

32.6

 

1515

22000

13.6

 

1105

18.1

 

1218

22.4

 

1318

26.9

 

1409

31.8

 

1493

36.8

 

1572

24000

16.6

 

1184

21.7

 

1291

26.5

 

1387

31.2

 

1474

36.2

 

1556

 

 

 

26000

20.2

 

1265

25.7

 

1366

31

 

1457

36.1

 

1542

 

 

 

 

 

 

JOHNSON CONTROLS

23

Image 23
Contents 231-02-E Ashrae90.1 Compliant MEASimplicity Elite controller Option Indoor air quality features for the indoor environ- mentIntroduction Lower total cost of ownershipTable of Contents Features and Benefits Relief System CommunicationsFilter Options Outside AIR Damper OptionsRoof Curbs Condenser Features and OptionsCabinet Features and Options Evaporator SectionAccessories Location Unit PlacementApplication Data GeneralEconomizer Duct ConsiderationsUnit Orientation Horizontal ApplicationsBuilding Pressure Control Systems VAV Supply AIR Pressure ControlHarsh Environments Condenser and Evaporator Coil Protection Copper-Fin Evaporator and Condenser CoilAcoustical Considerations This page intentionally left blank York NomenclaturePhysical Data Physical DataLow Ambient Option Min. OA Temp Minimum Airflow Heating Model050 051 060 061 Gas Furnaces Minimum OA Temp for Mech. CigModel Supply Blower Cooling Only Gas Heat Type ModelIplv Ieer EERAir Altitude feet Temp Altitude and Temperature CorrectionsALTITUDE/TEMPERATURE Conversion Factor Cooling Performance DATA* 50 TON Standard Capacity Cooling Performance Data 050 ModelCooling Performance DATA* 55 TON High Capacity Cooling Performance Data 051 ModelCooling Performance DATA* 60 TON Standard Capacity Cooling Performance Data 060 ModelCooling Performance DATA* 65 TON High Capacity Cooling Performance Data 061 ModelCFM STD. AIR BHP RPM Supply Fan DataTotal Static Pressure inches of water column CFM Component Static Pressure DropsAIR BHP RPM Exhaust Fan DataExhaust FAN Motor Sizing Instructions CFM STDRLA LRA Electrical Service SizingElectrical Data Load DefinitionsAmps FLAUnit Size Quantity FansMorning WARM-UP Unoccupied / Occupied SwitchingControls GAS Heating OperationExhaust Control Sequences Economizer OperationVentilation Control Sequences Cooling Operation Smoke Purge SequenceLOW-AMBIENT/HEAD-PRESSURE Control Operation Supply FAN OperationSupply Single-Point POWER-SUPPLY-CONDUCTOR Size RangeHeating Operation Dual-Point TBGeneral Arrangement Drawing General ArrangementSide Supply / Rear Return DrawingTOP View DrawingsGeneral Arrangement Drawing Curb Layout DrawingUnit Weights Unit Corner Weights Guide Specifications Unit Construction WarrantiesEquipment Product SpecificationEvaporator Section Filter SectionCondenser Section Supply Fan SectionDischarge Plenum Controls Simplicity Elite Inspection and START-UP Supervision InstallationExecution ALL Rights Reserved