York HFC-410A manual Exhaust Fan Data, Exhaust FAN Motor Sizing Instructions, Cfm Std, Air Bhp Rpm

Page 25

FORM 100.50-EG5 (108)

Exhaust Fan Data

EXHAUST FAN MOTOR SIZING INSTRUCTIONS

In order to determine the proper exhaust fan motor size, add the return duct static pressure to the appropriate damper pressure drop value in Table 14 to get the total static pressure applied to the exhaust fan. Based on the exhaust fan airflow and total static pressure, determine the brake horsepower and RPM of the exhaust fan.

TABLE 15 FORWARD-CURVED FAN

CFM STD.

 

 

 

Total Static Pressure (inches of water column)

 

 

 

0.3

 

 

0.5

 

0.8

 

1

AIR

 

 

 

 

BHP

 

RPM

BHP

 

RPM

BHP

 

RPM

BHP

 

RPM

 

 

 

 

 

6000

 

 

 

 

 

 

 

 

 

 

 

 

8000

 

 

 

 

 

 

 

 

 

 

 

 

10000

 

 

 

 

 

 

 

 

 

 

 

 

12000

 

 

 

 

 

 

 

 

 

 

 

 

14000

 

 

 

 

 

 

 

 

 

5.4

 

645

16000

5

 

528

5.7

 

584

6.4

 

633

7.2

 

680

18000

6.8

 

579

7.7

 

632

8.5

 

678

9.3

 

721

20000

9.1

 

632

10.1

 

681

11.1

 

725

12

 

765

22000

11.8

 

685

13

 

731

14.1

 

772

15.1

 

811

24000

15.1

 

739

16.4

 

782

17.6

 

821

18.8

 

858

26000

18.9

 

794

 

 

 

 

 

 

 

 

 

NOTE: For performance at operating points not included in these tables, consult your local YORK representative.

JOHNSON CONTROLS

25

Image 25
Contents 90.1 AshraeCompliant MEA 231-02-EIntroduction Indoor air quality features for the indoor environ- mentLower total cost of ownership Simplicity Elite controller OptionTable of Contents Features and Benefits Filter Options CommunicationsOutside AIR Damper Options Relief SystemCabinet Features and Options Condenser Features and OptionsEvaporator Section Roof CurbsAccessories Application Data Unit PlacementGeneral LocationUnit Orientation Duct ConsiderationsHorizontal Applications EconomizerHarsh Environments Condenser and Evaporator Coil Protection VAV Supply AIR Pressure ControlCopper-Fin Evaporator and Condenser Coil Building Pressure Control SystemsAcoustical Considerations This page intentionally left blank York NomenclaturePhysical Data Physical Data050 051 060 061 Gas Furnaces ModelMinimum OA Temp for Mech. Cig Low Ambient Option Min. OA Temp Minimum Airflow HeatingIplv Ieer ModelEER Model Supply Blower Cooling Only Gas Heat TypeAir Altitude feet Temp Altitude and Temperature CorrectionsALTITUDE/TEMPERATURE Conversion Factor Cooling Performance DATA* 50 TON Standard Capacity Cooling Performance Data 050 ModelCooling Performance DATA* 55 TON High Capacity Cooling Performance Data 051 ModelCooling Performance DATA* 60 TON Standard Capacity Cooling Performance Data 060 ModelCooling Performance DATA* 65 TON High Capacity Cooling Performance Data 061 ModelTotal Static Pressure inches of water column Supply Fan DataCFM STD. AIR BHP RPM CFM Component Static Pressure DropsExhaust FAN Motor Sizing Instructions Exhaust Fan DataCFM STD AIR BHP RPMElectrical Data Electrical Service SizingLoad Definitions RLA LRAUnit Size Quantity FLAFans AmpsControls Unoccupied / Occupied SwitchingGAS Heating Operation Morning WARM-UPVentilation Control Sequences Economizer OperationExhaust Control Sequences LOW-AMBIENT/HEAD-PRESSURE Control Operation Smoke Purge SequenceSupply FAN Operation Cooling OperationHeating Operation POWER-SUPPLY-CONDUCTOR Size RangeDual-Point TB Supply Single-PointGeneral Arrangement Drawing General ArrangementSide Supply / Rear Return DrawingTOP View DrawingsGeneral Arrangement Drawing Curb Layout DrawingUnit Weights Unit Corner Weights Guide Specifications Equipment WarrantiesProduct Specification Unit ConstructionEvaporator Section Filter SectionDischarge Plenum Supply Fan SectionCondenser Section Controls Simplicity Elite Execution InstallationInspection and START-UP Supervision ALL Rights Reserved