FORM
is called from the thermostat, the Supply Fan will start. Ventilation functions (if equipped) will be permitted to run with an occupied signal. Economizer functions will operate with a “G” call and a call for cooling.
HEATING OPERATION
Thermostat Control
If a
the thermostat. With this operation, the unit remains idle until it receives a stage call from the thermostat. If “G” is called from the thermostat, the Supply Fan will start. Ventilation functions (if equipped) will be permitted to run with an occupied signal.
TABLE 22 – POWER-SUPPLY-CONDUCTOR SIZE RANGE
|
|
|
| ||
|
|
|
|
| |
Supply |
| TB 1 | TB 2 | ||
Voltage | TB | Disconnect | |||
|
| ||||
208V | (2*) 250 | (2*) 2 | 6 | 6 | |
|
|
|
|
| |
230V | (2*) 250 | (2*) 2 | 6 | 6 | |
|
|
|
|
| |
460V | 6 | 6 | 14 | 14 | |
|
|
|
|
| |
575V | 6 | 6 | 14 | 14 | |
|
|
|
|
|
NOTE: 2* = Dual pairs per phase
JOHNSON CONTROLS | 31 |