York HFC-410A manual Physical Data

Page 14

Physical Data

 

 

FORM 100.50-EG5 (108)

 

 

 

 

TABLE 3 – PHYSICAL DATA

 

 

 

 

MODEL

 

050

051

060

061

General Data

 

 

 

 

Length without hood (inches)

 

339

339

339

339

Width (inches)

 

92

92

92

92

Height (inches)

 

82

82

82

82

Compressor Data

 

 

 

 

Quantity

 

4

4

4

4

Type

 

Scroll

Scroll

Scroll

Scroll

Unit Capacity Steps

 

4

4

4

4

R410a Charge (SYS 1/2) (lb-oz)

 

50 / 50

50 / 50

58 - 11 / 58 - 11

58 - 11 / 58 - 11

Supply Fan

 

 

 

 

Quantity

 

1

1

1

1

Type

 

FC

FC

FC

FC

Size

 

28 - 28

28 - 28

28 - 28

28 - 28

Motor Size Range (HP)

 

10 - 40

10 - 40

10 - 40

10 - 40

Air Flow Range (CFM)

 

10,000 - 22,500

10,000 -22,500

12,500 - 24,000

12,500 - 24,000

Static Pressure Range (Total)

 

1.0" - 6.0"

1.0" - 6.0"

1.0" - 6.0"

1.0" - 6.0"

Optional Supply Fan

 

 

 

 

Quantity

 

1

1

1

1

Type

 

AF

AF

AF

AF

Size

 

28

28

28

28

Motor Size Range (HP)

 

10 - 40

10 - 40

10 - 40

10 - 40

Air Flow Range (CFM)

 

10,000 - 24,000

10,000 - 24,000

12,500 - 24,000

12,500 - 24,000

Static Pressure Range (Total)

 

1.0" - 8.0"

1.0" - 8.0"

1.0" - 8.0"

1.0" - 8.0"

Exhaust Fan

 

 

 

 

Quantity Fans/Motors

 

2 / 1

2 / 1

2 / 1

2 / 1

Type

 

FC

FC

FC

FC

Size

 

18 - 18

18 - 18

18 - 18

18 - 18

Motor Size Range (HP)

 

5 - 20

5 - 20

5 - 20

5 - 20

Air Flow Range (CFM)

 

4,000 - 22,500

4,000 - 22,500

4,000 - 24,000

4,000 - 24,000

Static Pressure Range (Total)

 

0.1" - 1.5"

0.1" - 1.5"

0.1" - 1.5"

0.1" - 1.5"

Evaporator Coil

 

 

 

 

Size (square feet)

 

52

52

52

52

Rows/FPI

 

3 / 17

3 / 17

4 / 17

4 / 17

Condenser Coil

 

 

 

 

Size (square feet)

 

88

88

88

88

Rows/FPI

 

2 / 17

2 / 17

3 / 17

3 / 17

Condenser Fans

 

 

 

 

Quantity

 

4

4

4

4

Type

 

Prop.

Prop.

Prop.

Prop.

Diameter (inches)

 

36

36

36

36

Motor HP

 

2

2

2

2

Filters - 2" throwaway (pre-filter position - angled)

 

 

 

 

Quantity

 

8 / 12

8 / 12

8 / 12

8 / 12

Size (length x width) (in.)

 

25x16 / 25x20

25x16 / 25x20

25x16 / 25x20

25x16 / 25x20

Total Filter Face Area (square feet)

 

61.6

61.6

61.6

61.6

Filters - 2" cleanable (pre-filter position - angled)

 

 

 

 

Quantity

 

8 / 12

8 / 12

8 / 12

8 / 12

Size (length x width) (in.)

 

25x16 / 25x20

25x16 / 25x20

25x16 / 25x20

25x16 / 25x20

Total Filter Face Area (square feet)

 

63.9

63.9

63.9

63.9

Filters - 2" pleated, 30% efficient (pre-filter position - angled)

 

 

 

 

Quantity

 

8 / 12

8 / 12

8 / 12

8 / 12

Size (length x width) (in.)

 

25x16 / 25x20

25x16 / 25x20

25x16 / 25x20

25x16 / 25x20

Total Filter Face Area (square feet)

 

63.9

63.9

63.9

63.9

14

JOHNSON CONTROLS

Image 14
Contents Compliant MEA Ashrae90.1 231-02-ELower total cost of ownership Indoor air quality features for the indoor environ- mentIntroduction Simplicity Elite controller OptionTable of Contents Features and Benefits Outside AIR Damper Options CommunicationsFilter Options Relief SystemEvaporator Section Condenser Features and OptionsCabinet Features and Options Roof CurbsAccessories General Unit PlacementApplication Data LocationHorizontal Applications Duct ConsiderationsUnit Orientation EconomizerCopper-Fin Evaporator and Condenser Coil VAV Supply AIR Pressure ControlHarsh Environments Condenser and Evaporator Coil Protection Building Pressure Control SystemsAcoustical Considerations This page intentionally left blank Nomenclature YorkPhysical Data Physical DataMinimum OA Temp for Mech. Cig Model050 051 060 061 Gas Furnaces Low Ambient Option Min. OA Temp Minimum Airflow HeatingEER ModelIplv Ieer Model Supply Blower Cooling Only Gas Heat TypeAltitude and Temperature Corrections Air Altitude feet TempALTITUDE/TEMPERATURE Conversion Factor Cooling Performance Data 050 Model Cooling Performance DATA* 50 TON Standard CapacityCooling Performance Data 051 Model Cooling Performance DATA* 55 TON High CapacityCooling Performance Data 060 Model Cooling Performance DATA* 60 TON Standard CapacityCooling Performance Data 061 Model Cooling Performance DATA* 65 TON High CapacityCFM STD. AIR BHP RPM Supply Fan DataTotal Static Pressure inches of water column Component Static Pressure Drops CFMCFM STD Exhaust Fan DataExhaust FAN Motor Sizing Instructions AIR BHP RPMLoad Definitions Electrical Service SizingElectrical Data RLA LRAFans FLAUnit Size Quantity AmpsGAS Heating Operation Unoccupied / Occupied SwitchingControls Morning WARM-UPExhaust Control Sequences Economizer OperationVentilation Control Sequences Supply FAN Operation Smoke Purge SequenceLOW-AMBIENT/HEAD-PRESSURE Control Operation Cooling OperationDual-Point TB POWER-SUPPLY-CONDUCTOR Size RangeHeating Operation Supply Single-PointGeneral Arrangement General Arrangement DrawingDrawing Side Supply / Rear ReturnDrawings TOP ViewCurb Layout Drawing General Arrangement DrawingUnit Weights Unit Corner Weights Guide Specifications Product Specification WarrantiesEquipment Unit ConstructionFilter Section Evaporator SectionCondenser Section Supply Fan SectionDischarge Plenum Controls Simplicity Elite Inspection and START-UP Supervision InstallationExecution ALL Rights Reserved