FORM
Controls (continued)
proportionally controlled open and the Exhaust Fan is controlled ON. If the Building Pressure falls, the Exhaust Damper is proportionally controlled closed and the Ex- haust Fan is controlled OFF. The position of the Exhaust Damper in which the Exhaust Fan is controlled ON and OFF as well as the Building Pressure setpoint are user- selectable from the Rooftop Unit User Interface.
SMOKE PURGE SEQUENCE
A contact closure input (PURGE) is provided to place the unit in smoke purge mode. When the contact is closed the unit will operate as follows:
•Turn off all heating and cooling operation
•Set the outdoor air damper output to 100%
Powered, Variable-Volume Exhaust-VFD Controlled
This optional
LOW-AMBIENT/HEAD-PRESSURE CONTROL OPERATION
The Rooftop Unit controller continuously monitors the outside air temperature to determine if mechanical cool- ing should be allowed. As a safety, if the Outside Air temperature falls to or below the Low Ambient Lockout temperature, mechanical cooling is prevented from operating.
For units with economizers, the Low Ambient Lockout temperature is typically low enough that mechanical cooling will rarely be required. However, for some ap- plications, mechanical cooling is required when the Outside Air temperature is lower than the Low Ambient Lockout temperature.
For these applications, the unit must be equipped with optional Low Ambient controls. For optional Low Ambi- ent operation, the Rooftop Unit controller monitors the
•Close the return to 0%
•Turn the supply fan on
•On VAV unit set the supply fan output to 100%.
•Turn the power exhaust fan on
•On VFD driven exhaust fans set the exhaust fan output to 100%
Note that 24 volts terminal (R) on the Simplicity control board must be used as the 24 Volt AC source for switch the contact to the Unit Controller Smoke Purge (PURGE) input. Use of any power source external to the controller will result in damage to the Unit Controller.
VAV SPECIFIC SEQUENCES
SUPPLY FAN OPERATION
For VAV units, the supply fan is controlled ON and OFF based on the occupancy state. When the unit goes into the Occupied mode of operation, the Rooftop Unit controller will monitor the static pressure within the
CV SPECIFIC SEQUENCES
COOLING OPERATION
Thermostat Control
If a
30 | JOHNSON CONTROLS |