Service Manual
2Maintenance
Maintenance and annual startup
Table 2A Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
| General: |
|
|
|
| |
| • Address reported problems |
| ||||
| • Inspect interior; clean and vacuum if | |||||
| necessary; |
|
|
| ||
| • Clean condensate trap and fill with fresh | |||||
| water |
|
|
|
| |
| • Check | for | leaks | (water, gas, | flue, | |
| condensate) |
|
|
| ||
| • Verify flue and air lines in good condition | |||||
UP | and sealed tight |
|
| |||
• Check | system water pressure/system | |||||
START- | ||||||
piping/expansion tank |
| |||||
|
| |||||
| • Check control settings |
| ||||
ANNUAL | • Check ignition and flame sense electrodes | |||||
(sand | off | any | deposits; | clean | ||
| ||||||
| and reposition) |
|
| |||
| • Check wiring and connections |
| ||||
| • Perform | checkout | and | |||
| performance verification per Section 10 | |||||
| in the Armor Installation and Operation | |||||
| Manual. |
|
|
|
| |
| • Flame inspection (stable, uniform) |
| ||||
| • Flame signal (at least 10 microamps at | |||||
| high fire) |
|
|
| ||
| • Clean | the | heat | exchanger if | flue | |
| temperature is more than 54°F above | |||||
| return water temperature. |
| ||||
| • Check Delta T (Temperature Rise) |
|
If combustion or performance indicate need:
•Clean heat exchanger
•Remove and clean burner using compressed air only
•Clean the blower wheel
Owner maintenance | ||||
|
| |||
| • Check water heater area | |||
| • Check pressure/temperature | |||
| gauge |
|
|
|
Daily |
|
|
|
|
|
|
| ||
| • Check vent piping |
| ||
| • Check air piping |
| ||
Monthly | • Check | air and vent | termination | |
| screens |
|
| |
| • Check relief valve |
| ||
| • Check condensate drain system | |||
| • Check air vents |
| ||
| • Check | Delta | T (Temperature | |
| Rise) |
|
|
|
|
|
|
|
|
Every |
|
|
|
|
6 months | • Check | water | heater | piping (gas |
| and water) for leaks |
| ||
| • Operate relief valve |
| ||
|
|
|
|
|
16