Lochinvar 150 - 800 service manual No Flame Ign

Page 26

Service Manual

3Troubleshooting

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

The unit has failed to prove main burner

• Inspect spark electrode and associated wiring for

 

ignition after four (4) attempts.

damage and connection. Reference page 19 of this

 

 

manual for removal and cleaning procedures.

 

Exception: Models 500 - 800 will lock out

Replace if necessary.

 

after one retry for ignition. It will require a

• Check for proper electrical grounding of the unit.

 

manual reset before attempting to fire again.

 

 

• Check incoming supply gas pressure. Natural gas

 

 

pressures should be between 4 - 14 inches w.c. and

 

 

LP gas pressures should be between 8 - 14 inches w.c.

 

 

Refer to Section 7 - Gas Connections of the Armor

 

 

Water Heater Installation and Operation Manual for

 

 

detailed information concerning the gas supply.

 

 

• Verify that the plastic hose from the gas valve to the air

 

 

inlet is connected and is not damaged.

 

 

• Verify that the vent/air intake pipes are correctly

 

 

installed and that there are no obstructions.

 

 

• Check for 24 VAC to the gas valve at the 2-pin

No Flame Ign

 

connection on the side of the main control board during

 

the ignition attempt. If no voltage is present, replace

(will require a manual

 

the main control board.

reset once the condition

 

• If 24 VAC is present at the main control board, check

has been corrected.

 

 

the wiring between the main control board and the gas

Press the RESET button

 

 

valve. Replace the wiring if necessary. Do not

on the SMART SYSTEM

 

 

disconnect the wiring from the gas valve and attempt to

display to reset.)

 

 

measure voltage at that point. The main control board

 

 

 

 

can detect if the gas valve is not connected and will

 

 

display the GV / Relay Fail fault.

 

 

• If 24 VAC is present, check the outlet of the valve to

 

 

ensure the valve is flowing gas. With a manometer

 

 

connected to the outlet tap of the gas valve, when the

 

 

unit is in the prepurge period, there should be a

 

 

negative pressure present. When the valve is

 

 

energized a change in pressure should occur. If the

 

 

pressure change does not occur, the gas valve is not

 

 

opening. Replace the gas valve.

 

 

• Inspect flame sensor and associated wiring.

 

 

Reference page 19 of this manual for removal and

 

 

cleaning procedures. Replace if necessary.

 

 

• Inspect the burner. Reference page 19 of this manual

 

 

for removal and cleaning procedures. Replace if

 

 

necessary.

 

 

• Replace the main control board.

 

 

 

26

Image 26
Contents Models 150 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials Maintenance What is in this manual?Service TroubleshootingService Armor water heater displayControl inputs Control outputs Sequence of operation General OperationHow the water heater operates Saving parametersSequence of operation Display panel menu access Use this procedure to access menus from the display panelDisplay panel parameter access Button Operation Display CommentsParameter table WHRViewable and changeable control parameters Not used Data loggingNot used Control modes WHR settingsFunctions Service Notification Circulation pumpsOwner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check expansion tank Flue vent system and air pipingCheck water system Check water heater relief valveCheck control settings Check ignition ground wiringCheck all water heater wiring Perform start-up and checksReview with owner Check flame signalCleaning heat exchanger Oiled bearing circulatorsCheck control module fuses TroubleshootingBefore troubleshooting Check the followingOperation No DisplayNo Burner Unit Does Not Checking temperature sensors Temperature F Resistance ΩRelief Valve NoisyNo Pump OpeningSequence Flow SwitchFlame GV/RelayNo Flame Ign No Flame RunningFan Low Manual ResetHigh Limit Fan Speed LowSensor Open Fan HighFan Speed High Sensor ShortedProgr Rem Ctrl FltParameters No Error Stored Service BlkWatch Dog Error Low 24 VACOr Obstruction Combustion Analysis ProcedureGas Valve Adjustment Gas Supply PressureModel Gas valve adjustment procedureModels 150 4Gas Valve Adjustment Model Models 600